Parameter description 

6. Parameter description 

01 Information level 

Display 

Designation 

Description 

08:01 

Heat capacity 

A

T1 

Current heat capacity in W 

X1 

08:02 Heat 

balance 

A

T1 

Display of cumulative heat energy in kWh 

X1 

08:03 

Display pump 

0: Pump is switched off 

 

function 

A

T1 

1: Pump is switched on 

08:04 

Temperature 

Sensor temperature of heat supplier (e.g. collector, solid fuel 

 

heat supplier 

A

T1 

boiler) at input F3 

08:05 

Temperature 

heat storage tank 

Sensor temperature of heat storage tank at input F1 

 

A

T1 

 

08:06 

Temperature 
return 

A

T1 

Sensor temperature of return at input F2, if available. 

X5 

08:07 

Pump operating 
hours 

A

T1 

Number of pump operating hours 

08:08 Pump 

starts 

A

T1 

Number of pump starts 

09:03 

Display pump 

0: Pump is switched off 

 

function 

A

T2 

1: Pump is switched on 

09:04 

Temperature 

Sensor temperature of heat supplier (e.g. collector, solid fuel 

 

heat supplier 

A

T2 

boiler) at input F4 

09:05 

Temperature 

Sensor temperature of heat storage tank at input F1 

X5 

 

heat storage tank 

(or F2, if available) 

 

A

T2 

 

09:07 

Pump operating 
hours 

A

T2 

Number of pump operating hours 

09:08 

Pump starts 

A

T2 

Number of pump starts 

 

03 Parameter system 

Display 

Designation 

Description 

03:01 

 

 Code entry 

Setting range: 

0 ... 999 

Factory setting: 

Function: 
Show parameters marked with X3. 

Содержание CETA 101

Страница 1: ...Operating manual 101 Double differential temperature control Version 1043 22 Art 0450021015 GB ...

Страница 2: ... Installation 19 Connection diagram 20 Fault clearance 21 Declaration of conformity 22 Technical data 23 Liability 23 Disposal 23 Elektronikbau und Vertriebs GmbH Heisterner Weg 8 12 D 57299 Burbach This document may not be reproduced nor disclosed to third parties particularly competitors in original or copy form without our prior explicit consent The document is subject to our proprietary rights...

Страница 3: ...Intended use The unit is manufactured in accordance with state of the art technology and approved safety regulations Nevertheless using the unit can cause danger to the user or third persons or damage to the unit and other assets The unit must be used exclusively as differential temperature controller Safety All electrical connections safety measures and protections have to be carried out by an au...

Страница 4: ... setting Save value Plus or Minus Change parameter Change menu item Esc Exit setting Keep old value Select next higher menu level Esc Lang Return to basic display 2 Version display when starting c 101 Type designation Ceta 101 24 02 Version display due to update it can differ from example shown ...

Страница 5: ...age tank 1 AT1 Display pump function P1 AT2 Display pump function P2 H GEN Display burner block Use to switch to 2 Basic display 2 75 5 C Temperature F4 heat supplier 2 e g collector or solid fuel boiler 51 5 C Temperature F2 heat storage tank 2 if sensor F2 is available AT1 Display pump function P1 AT2 Display pump function P2 H GEN Display burner block ...

Страница 6: ...p Escape from mannual mode Function Mannual mode pump activation for inspection purposes 0 Pump off 1 Pump on Attention This function must be used only by the technician When the manual mode is on the safety settings of the CETA 101 are de activated In case of faulty usage may cause damage to the installation e g stagnation ...

Страница 7: ... 385 110 1 423 120 1 461 130 1 498 140 1 536 150 1 573 160 1 611 170 1 648 180 1 685 190 1 722 200 1 758 210 1 795 220 1 832 230 1 868 240 1 905 250 1 941 T C R kOhm 10 1 783 12 1 812 14 1 840 16 1 869 18 1 898 20 1 928 25 2 002 30 2 078 35 2 155 40 2 234 45 2 314 50 2 395 55 2 478 60 2 563 65 2 648 70 2 735 75 2 824 80 2 914 85 3 005 90 3 098 95 3 192 100 3 287 ...

Страница 8: ...Select menu level Prog Basic display 27 Calibration 28 Relay test 01 Menu01 02 Menu 02 Prog Esc Set parameter value 02 01 Parameter 01 Select parameters 02 02 Parameter 02 Prog Valuen Value 2 Value1 Esc Return without saving Prog 02 nn Last parameter Return and save ...

Страница 9: ...nsor F1 03 01 Code entry 28 01 Relay test Output R1 X1 09 03 Pump sT2 On Off 8 1 X2 X2 X3 03 02 Auto set function 09 Inhibition Heat generator 08 Inhibition Heat generator X1 09 04 Temperature Heat supplier 2 27 02 Calib sensor F2 X1 08 02 Heat balance 28 02 Relay test Output R2 8 Switch on differential 10 Switch on differential X2 X2 X5 X5 09 05 Temperature Heat storage tank 2 08 Heat balance On ...

Страница 10: ...supplier 08 0 Max temp heat supplier 08 1 Reset counter 09 0 Final switch off temp Heat supplier 09 0 Max temp Heat storage tank 08 1 Heat capacity HT medium 08 1 Density HT medium 09 0 Min temp Heat supplier 09 0 Max temp heat supplier 09 1 Reset counter 27 04 Calib sensor F4 09 16 4T2 Changeover sensor F2 8 Minimum running time Pump 1 Minimum running time Pump 08 Volume flow HT medium X5 08 06 T...

Страница 11: ...rn A T1 Sensor temperature of return at input F2 if available X5 08 07 Pump operating hours A T1 Number of pump operating hours 08 08 Pump starts A T1 Number of pump starts 09 03 Display pump 0 Pump is switched off function A T2 1 Pump is switched on 09 04 Temperature Sensor temperature of heat supplier e g collector solid fuel heat supplier A T2 boiler at input F4 09 05 Temperature Sensor tempera...

Страница 12: ...ection against blocking when function is activated 03 09 Code heating Setting range 0 999 specialist Factory setting 0 Function Hide parameters marked with X3 03 10 Total reset Reset to factory settings 08 Parameter DeltaT1 Display Designation Description 08 01 08 02 Control mode A T1 Switch on differential AT1 Setting range 0 Delta T OFF 1 Delta T without return flow sensor 2 Delta T with return ...

Страница 13: ... has exceeded the set value 08 06 Maximum Setting range OFF 30 110 C temperature heat Factory setting 90 C supplier A T1 Function Irrespective of switching differentials the pump performs a forced switch on after the sensor of heat supplier F3 has exceeded the set value 08 07 Final switch off Setting range OFF 70 210 C temperature heat Factory setting OFF supplier A T1 Function Irrespective of swi...

Страница 14: ...rameter 08 12 Volume flow HT Setting range 0 0 30 l min medium A T1 Factory setting 0 0 l min Function Here the volume flow is set in litre minute when calculating flow rate according to respective pump capacity 08 13 Density HT medium Setting range 0 8 1 2 kg l AT1 Factory setting 1 05 kg l Function Using this parameter the density of the heat transfer medium is entered in kilogramme per litre ac...

Страница 15: ...stat Switch On temperature Setting range 5 C switch off temperature 3K Factory setting 30 C Function If F3 temperature drops under the setting 08 20 then the pump is being activated 08 21 Thermostat Switch Off temperature Setting range Switch On temperature 3K 120 C Factory setting 90 C Function If F3 temperature rises over the setting 08 20 then the pump is being deactivated 08 22 Inverse Setting...

Страница 16: ...et value the pump switches off 09 04 Minimum running Setting range OFF time pump A T2 0 5 60 min Factory setting 3 min Function Minimum switch on time of pump per start 09 05 Minimum Setting range OFF temperature heat 5 80 C supplier A T2 Factory setting OFF Function Irrespective of switching differentials the pump switches on only after the sensor of heat supplier F4 has exceeded the set value 09...

Страница 17: ...urner block when pump is active 2 Burner block only for DHW when pump is active 09 10 Inhibition heat Setting range OFF 24h X2 generator A T2 Factory setting OFF Function After burner block is active the heat generator is also blocked for the duration of the set time 09 15 Reset counter A T2 Setting range 0 no reset 1 reset counter Factory setting 0 Function When value is changed to 1 and confirme...

Страница 18: ...ture rises over the setting 09 20 then the pump is being deactivated 09 22 Inverse Setting range 0 1 thermostat Factory setting 0 Function Inverts the pump function 0 normally close 1 normally open 09 23 Frost protection Solar collector temperature Setting range Off 15 C 10 C Factory setting Off Function Solar pump switches on when the temperature from the solar collector drops below the 09 23 val...

Страница 19: ...28 02 Test pump output see 28 01 Delta T2 28 03 Test output burner block see 28 01 7 Mounting Hazard Mounting must be performed by an authorised professional electrician Ensure that unit is de energised before opening it Drilling pattern for wall fastening 1 Remove terminal area cover from casing 2 For mounting first put a screw into the wall 3 Hang controller into the opening 4 Use controller as ...

Страница 20: ...onnections L Phase 230V mains 1 L1 230V Connection Delta T1 pump 2 L1 230V Connection Delta T2 pump Connection without function N Neutral 230V mains pumps Connection burner block isolated Earthing Bus connections for networking see parameter 03 03 Connections without function Connections without function F1 Sensor heat storage tank Delta T1 KVT20 F2 Sensor heat storage tank Delta T2 return flow De...

Страница 21: ...or F1 heat storage tank 1 has short circuit Use to switch to 2 Display 2 1 C Sensor F4 Heat supplier 2 z B collector2 solid fuel boiler2 has short circuit 0 C Sensor F2 option heat storage tank 2 is interrupted Fault overview Fault code Cause Repair 0 1 Fault Display text not visible Tank sensor interruption Short circuit on tank sensor Cause No power defective fuse in unit Check cable and plug co...

Страница 22: ...22 Declaration of conformity 10 Declaration of conformity ...

Страница 23: ...in an environmentally sound manner in compliance with applicable statutory regulations of the corresponding country Company stamp Mains voltage Rated frequency Power input Fuse Output relay contact load Ambient temperature Storage temperature Degree of protection Protection class according to EN 60730 CE compliance Casing dimensions Casing material Weight Mains connection technology Sensor connect...

Отзывы: