14
Parameter description
Display
Designation
Description
08:09
Burner block
Setting range:
0 ... 2
X2
heat generator
A
T1 Factory setting: 1
Function:
0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
08:10
Inhibition heat
Setting range:
OFF (----) ... 24h
X2
generator
A
T1 Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time.
08:11
Activation heat
Setting range:
OFF (----)
X3, X5
balance
A
T1
1 = Heat balancing via return sensor on
F2 (option)
Factory setting:
OFF
Function:
The settings of parameters 08:12 to 08:14 are only active if the
heat balance function has been switched on via this parameter.
08:12
Volume flow HT-
Setting range:
0.0 ... 30 l/min
medium
A
T1 Factory
setting:
0.0
l/min
Function:
Here the volume flow is set in litre/minute when calculating flow
rate, according to respective pump capacity.
08:13
Density HT-medium Setting range:
0.8 ... 1.2 kg/l
A
T1
Factory setting:
1.05 kg/l
Function:
Using this parameter, the density of the heat transfer medium is
entered in kilogramme per litre, according to manufacturer's data.
08:14
Heat capacity HT-
Setting range:
2.0 ... 5.0 kJ/kgK
medium
A
T1 Factory
setting:
3.6
kJ/kgK
Function:
This setting value is used to enter the specific heat capacity of
the heat transfer medium according to manufacturer's
information.
08:15
Reset counter
A
T1
Setting range:
0 = no reset, 1 = reset counter
Factory setting:
0
Function:
When value is changed to 1 and confirmed, all counters (heat balance,
operating hours and starts) are reset.