Parameter description
6
5.
Parameter description
01 Information level
03 Parameter system
Display
Designation
Description
08:01
Heat capacity
Current heat capacity in W
X1
08:02
Heat balance
Display of cumulative heat energy in kWh
X1
08:03
Display pump
function
0: Pump is switched off
1: Pump is switched on
08:04
Temperature
Heat supplier
Sensor temperature of heat supplier (e.g. collector, solid fuel
boiler) at input F3
08:05
Temperature
Heat storage tank
Sensor temperature of heat storage tank at input F1
08:06
Return temperature
Sensor temperature of return at input F2, if available.
08:07
Pump operating
hours
Number of pump operating hours
08:08
Pump starts
Number of pump starts
Display
Designation
Description
03:01
Code entry
Setting range:
0 … 999
Factory setting:
0
Function:
Show parameters marked with X3.
03:02
Automatic set
function
0=OFF, no automatic sensor detection
X3
1=ON, automatic sensor detection
03:03
Bus address
Setting range:
21…25
X3
Factory setting:
21
Function:
If more than one CETA 100 or 101 has to be connected via data
bus within a system, each unit must be set to a unique address.
03:06
Automatic exit time
Setting range:
0.5 … 10 min
X3
Factory value:
0.5 min
Function:
When unit is not operated during the set time, the display
returns to basic display.