Page 56
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
EL 9000 B 15U/24U Series
These device alarms can’t be configured and are based on hardware:
Short Long
Description
Indication
PF
P
ower
F
ail
AC supply over- or undervoltage. Triggers an alarm if the AC supply is
out of specification or when the device is cut from supply, for example
when switching it off with the power switch. The DC input will be switched
off which could be only temporarily, depending on the situation and
setting
DC input after PF alarm
).
Display, analog &
digital interfaces
OT
O
ver
T
em
-
perature
Triggers an alarm if the internal temperature of at least one unit in the
cabinet reaches a certain limit. The DC input will be switched off which
could be only temporarily, depending on the setting
DC input after OT
alarm
).
Display, analog &
digital interfaces
MSP M
aster-
S
lave
P
rotection
Triggers an alarm if the master unit loses contact to any slave unit. The
DC input will be switched off. The alarm can be cleared by re-initializing
the MS system.
Display, digital IF
► How to configure the device alarms
1.
While the DC input is switched off tap the touch area
on the main screen.
2.
On the right side tap the arrows to select
2. Protect
.
3.
Set the limits for the equipment alarm relevant to your application if the default value of 103% resp. 110%
is unsuitable.
The set values can also be entered using a numeric pad, which appears when tapping the
numpad symbol on this screen.
The user also has the possibility of selecting whether an additional acoustic signal will be sounded if an alarm or
user defined event occurs.
► How to configure the alarm sound (also see “
„3.4.3. Configuration via MENU“
)
1.
While the DC input is switched off tap the touch area
on the main screen.
2.
In the menu page, tap
HMI Setup
.
3.
In the following menu page, tap
Alarm Sound
.
4.
In the settings page tap the button to select between alarm sound on or off and confirm with
.