- PUMP START UP TEMPERATURE
temperature at which circulation pomp starts up is
o
o
PLYNNIE adjustable within the range 30 - 5 C
below temperature set up for the boiler, i.e. CH
o
temperature is set up for 60 C, then range of
o
o
pump regulation may be set between 30 C and 55 C.
- CH PRIORITY
in this mode pumps start working
when boiler temperature reaches temperature set
up in pump start up function. (CH pump works
permanently and HSW pump turns on after reaching desired temperature.)
In this mode HSW temperature cannot be higher than CH temperature.
- HSW hysteresis
that function is to set up service
water hysteresis, it consists in delaying HSW
pump start up by set up number of degrees, i.e.
o
o
hystheresis 2 , set up temperature 50 C - pump
shall start up when service water temperature
o
decreases to 48 C. This function works in HSW priority and summer mode.
4
PUMP START TEMP.
PUMP START TEMP.
0
35 c
FUNCTIONS
- MANUAL OPERATION
function is to fire up the
boiler, it enables independent start up of controller
and blower outputs.
Pressing ENTER button turns on one of the outputs. With ( ) and ( ) you
change output to be turned on or off. Pressing EXIT returns to set up menu.
- CH/HSW PRIORITY
- HSW PRIORITY
HSW pump starts up and works
until achieves set up temperature. When services
water reaches set up temperature HSW pump
turns off and CH pump turns on.
SP 16 Manual
Manual operation
Blower
2
0
C
HSW hysteresis
Hysteresis temp.
HSW
CH/HSW Prority
HSW Prority
CH Prority