ADDRESSES 477-490: RELAY PARAMETERS
Output relay modules are optional add-on peripherals that are connected to the control panel via the
LSCP bus. Relays can be used for various purposes including status indication, additional bell outputs
and access control. Each individual relay is programmed at two addresses.
477
Operation Mode Relay 1(and onboard relay K5)
Each relay can be programmed to activate or deactivate based on specific events or status
conditions. The following table lists the various relay operation mode options.
Note: In some
cases, changing the relay’s mode type can activate the relay for the duration of the
cutoff time.
Type
Description
Activated by
Deactivated by
Value
Access
Access control
Pressing SELECT, 9
on the keypad
Cutoff
00
Status
System 1 armed
System 1 armed
System disarmed/ Cutoff
01
Status
System 2 armed
System 2 armed
System disarmed/ Cutoff
02
Status
System 3 armed
System 3 armed
System disarmed/ Cutoff
03
Status
System 4 armed
System 4 armed
System disarmed/ Cutoff
04
Event
Silent alarm
Keypad Emergency,
Police Emergency, Duress
Cutoff
05
Event
System 1 alarm
System 1 alarm
Cutoff / System 1 disarm
06
Event
System 2 alarm
System 2 alarm
Cutoff / System 2 disarm
07
Event
System 3 alarm
System 3 alarm
Cutoff / System 3 disarm
08
Event
System 4 alarm
System 4 alarm
Cutoff / System 4 disarm
09
Event
Fire alarm
Fire zone in alarm or keypad fire
emergency
Cutoff
0A
Status
System 1 status
System 1 Not ready, Pulsing if
system has bypassed zones
System 1 ready without
bypassed zones
0C
Status
System 2 status
System 2 Not ready, Pulsing if
system has bypassed zones
System 2 ready without
bypassed zones
0D
Status
System 3 status
System 3 Not ready, Pulsing if
system has bypassed zones
System 3 ready without
bypassed zones
0E
Status
System 4 status
System 4 Not ready, Pulsing if
system has bypassed zones
System 4 ready without
bypassed zones
0F
Status
Power trouble
System power trouble (AC or
Battery)
System power is OK
10
Event
Telephone trouble
Failed communication attempt
(only activated after all message
attempts have failed)
Cutoff
11
Status
Pre-alarm
Pre-Alarm (if 20 sec bell delay)
Bell activated/Bell
Cancel/ System disarm
12
Status
Exit/Entry sys. 1
System 1 in Exit/Entry
System 1 not in
Exit/Entry
14
Status
Exit/Entry sys. 2
System 2 in Exit/Entry
System 2 not in
Exit/Entry
15
Status
Exit/Entry sys. 3
System 3 in Exit/Entry
System 3 not in
Exit/Entry
16
Status
Exit/Entry sys. 4
System 4 in Exit/Entry
System 4 not in
Exit/Entry
17
Status
Bell
Bell activated
Bell deactivated
18