General installation
21
487 18 39 01 - 300/500/750 - GB
Tumble dryer evacuation system
Fresh- air
If the machine is to work at its best and with the
shortest possible drying time, it is important to
ensure that fresh air is able to enter the room
from the outside in the same volume as that
blown out of the room. To avoid a draught in the
room, it is advisable to place the air inlet behind
the machine. *The area of the air inlet opening
must be 5 times the size of the vent pipe area.
The resistance in the grating/slats should not
exceed 10 Pa (0.1 mbar).
300/30: The air consumption is approx.
430 - 925 m3/h.
500/50: The air consumption is approx.
840 - 1380 m3/h.
750/75/650: The air consumption is approx.
1500 m3/h.
*The area of the inlet opening is the area through
which the air can flow without resistance from
grating/slatted cover.
Note that gratings/slatted covers often block half
of the total fresh air vent area. Remember to take
this into account.
A
5
x
A
5 x A
2
1
1
2