88
I/P Vent Hood
RH42PC60GS
Top
Controls
Wiring box
Air outlet -
7
7
/
8
" diam.
Dimensions
from base of
hood to ceiling,
and include
clearance
required for
installation.
41
7
/
8
"
25
3
/
16
"
2
11
/
16
"
12
1
/
8
"
13
3
/
16
"
35"
min.
57"
max.
28"
( min.
height
with one
cover)
K = Kitchen height
C = Counter height
P = Preferred height
of hood bottom
above counter
(24"- 30"
allowed, NOT
more than 36"
recommended)
A = Canopy height
H = Hood height for
installation
H = K-C-P
S = Chimney
structure height
for installation
S = H-A
PRE-INSTALLATION CALCULATIONS
S H
A
K
P
C
Counter Height
36" standard
cooking
Island Vent Hoods
Optional
Accessories
Duct-Free Kit
PN # RHDFP60GS
planning
information
For 42" model:
RH42PC60GS
Note:
For planning
purposes only. Refer
to Product Installation
Guide on the web at
electroluxicon.com for
detailed instructions.
Specifications subject
to change.
Ducted Option Specifications
•
For outside ventilation.
•
Exhaust Duct Required – 8" round
•
For most efficient airflow exhaust, use a straight run or as
few elbows as possible.
•
Use metallic flex ducting only to connect rigid duct directly
to transitions
(if allowed by code).
•
Thermal breaks such as short section of nonmetallic duct,
should be used in areas of extreme cold.
•
Cold weather installations should have additional backdraft
damper installed.
•
Refer to installation instructions on web for detailed exhaust
duct preparation and converting vent blower system for
recirculating inside.
Pre-Installation Calculations
•
Select hood preference height (P) that is comfortable
for user (24" - 30" minimum allowed, NOT more than
36" recommended).
•
Calculate hood height (H) for installation (H = K-C-P).
•
Confirm that (H) is within minimum to maximum range for
hood. If not, adjust installation.
•
Calculate chimney structure height (S). Use formulas,
check dimensions of hood. Save calculation for use later
in installation.
Installation Specifications
•
Product Weight – 87 Lbs.
•
Island / Peninsula Ceiling-Mount Installation
•
Ventilation system is preset to exhaust air outside. If
outside ducting is not possible, optional Duct-Free Kit
(PN # RHDFP60GS) is available to convert ventilation
to allow air to recirculate inside.
(Refer to Ducted
Option Specifications for outside ventilation.)
•
Sones Rating – 9.9
•
Voltage Rating – 120V / 60 Hz / 15 Amps
•
Connected Load (kW Rating) @ 120 Volts = 0.516 kW
(For use on adequately wired 120V, dedicated circuit
having 2-wire service with a separate ground wire.
Appliance must be grounded for safe operation.)
•
Amps @ 120 Volts = 4.16 Amps
•
Always consult local and national electric codes.
Check local building codes for installation requirements,
as they may vary per locale.
•
Minimum installation height allowed from bottom of
hood to cooking surface is 24" - 30" for electric and 30"
for gas.
(NOT more than 36" recommended.)
•
To prepare mounting surface, adequate structure and
support must be provided, capable of supporting 150 lbs.
Содержание ICON Professional E30DF74GPS
Страница 1: ...design guide ...
Страница 4: ...4 ...