System Variables (Var31 through Var36)
Var31.

 Hour_Meter_Warning_Time in Hours.

(Alarms as: Hour Meter display’s discrete Yellow LED only, with 
no relays involved).

The Hour Meter keeps track of how long the system has been in 
operation, assuming a few prerequisites are first met.
The Hour Meter increments and its discrete Green/Yellow/Red 
LEDs light-up only if all three of the following cases are true:

 

If 

Var31

 

is 

non-zero. 

    

(i.e., 

Var31

 = 0000 disables the Hour Meter).

 

AND If in Normal Mode, not in Program Mode.   
(i.e., Being in Program Mode disables the Hour Meter).

 

AND If the Hour_and_Speed_Enable command is present 
at 

TB34

. (i.e., The Hour_and_Speed_Disable command 

disables the Hour Meter).

If any one of these three prerequisites are NOT met, then the 
Hour Meter does NOT increment hours, NOR do the Hour 
Meter’s discrete Green/Yellow/Red LEDs light-up as per the 
number of hours reached.

The Hour Meter value is automatically saved once every 10 
minutes, because of this at most only 10 minutes of operating 
time is ignored if the ES1’s Vac power is lost.
For normal Hour Meter operation once the 

Var31

 Hour value is 

exceeded, then the Hour Meter’s discrete Green LED turns ‘OFF’ 
and its discrete Yellow LED turns ‘ON’.
When operation exceeds the 

Var32

 Hour value, then the Hour 

Meter’s discrete Yellow LED turns ‘OFF’ and its discrete Red 
LED turns ‘ON’.
The Hour_Meter feature does NOT trigger the Horn-Relay alarm, 
nor the Yellow-Lightstack-Relay alarm, nor the
Red-Lightstack-Relay alarm, nor the Unit_Alarm_LEDs.
If not manually cleared after 9999 hours, the Hour Meter holds at 
9999 hours with its discrete Yellow or Red LEDs ‘ON’.

There is an Hour_Meter_RESET button on the Front-Panel, and 
an AUX_Hour_Meter_RESET at input 

TB31:1,2

, that can be 

used to ‘clear’ the Hour Meter.  When an Hour_Meter_RESET 
command is given for longer than 3 seconds it returns the meter 
to 0000 and turns OFF the Hour Meter’s discrete Yellow/Red 
LEDs, and turns ON the Hour Meter’s discrete Green LED.

Note:  A 

Var31

 = ‘0000’ disables the Hour Meter (i.e., keeps it 

from growing), and also turns ‘OFF’ the Hour Meter’s 
discrete Green/Yellow/Red LEDs.  This 

Var31

 = 0000 

feature does NOT clear the Hour Meter, but rather keeps 
it from growing any further when an Hour_and_Speed_
Enable command is present.

Note:  If the UserVar programming LCD screen is in Program 

Mode, then the Hour Meter feature is disabled and the 
Hour Meter cannot increase (even if an Hour_and_Speed_
Enable command is present). Also when in Program Mode 
the Hour_Meter_RESET command is disabled.

Var31

 range is 0000 to 9999 Hours.

Factory default for Var31 is 9000 Hours.

Var32.

 Hour_Meter_Maintenance_Time in Hours.

(Alarms as: Hour Meter display’s discrete Red LED only, with no 
relays involved).

Var32

 range is 0000 to 9999 Hours.

Factory default for Var32 is 9500 Hours.

Var33. 

Horn_Operation_Select.

Var33

 selects how the user wants the Horn-Relay to sound.  

Var33

 range is 0000 to 1999.

The 

Var33

 value is limited to these below listed choices.

X

Var33=

The left-most digit selects Horn ‘type’:

0 = the Horn is a solid blast.

1 = the Horn is an oscillating blast.

            (1 sec ON, 3 sec OFF, etc.).

The three right-most digits set  the

Horn sounding ‘time’:

000 to 998 = the number of minutes to 

 

sound the Horn.

 

(See Note

5

).

999 = sound the Horn indefinitely.

5

X X X

Note

5

:   The user can always give a manual ‘Silence_Horn/

Alarm_RESET’ command at any time to turn OFF the 
Horn, and keep it OFF, until the Horn sounds again for 
the next alarm event.

The usable values of 

Var33

 are 0000 to 1999. Some examples are 

shown in the table below:

Var33

Value

Horn

Type 

Horn 

Time 

Notes

0000

Solid Blast

Indefinite

This has the same effect as 

Var33

=0999

0001

Solid Blast

1 Min.

---

0030

Solid Blast

30 Min.

---

0999

6

Solid Blast

Indefinite

Solid Horn until a ‘Silence_

Horn/Alarm_RESET’ given

1000

Oscillating

0

This is an oscillating blast 
for ‘0’ minutes, consisting 

of only one ‘beep’ lasting 

1 second ON and then a 

continuous OFF

1001

Oscillating

1 Min.

---

1030

Oscillating

30 Min.

---

1999

Oscillating

Indefinite

Oscillate Horn until a 

‘Silence_Horn/Alarm_

RESET’ given.

Note

6

: Factory default for Var33 is 0999 for solid blast until a 

‘Silence_Horn/Alarm_RESET’ command is given.

6

Содержание Electry-Sentry 1

Страница 1: ...r 990 005500 Revision D Electro Sensors Inc 6111 Blue Circle Drive Minnetonka MN 55343 9108 Contact us at Local 952 930 0100 National 1 800 328 6170 Fax 952 930 0130 Web www electro sensors com Sales sales electro sensors com Support tech electro sensors com ...

Страница 2: ...l Persons installing setting up and operating the Electro Sentry 1 should have good knowledge and understanding of electrical and mechanical concepts and principles pertaining to speed and temperature monitoring and associated alarms Again the Electro Sentry 1 should be installed by qualified personnel only Notices Installing Electro Sensors Inc products is the responsibility of the purchaser and ...

Страница 3: ...through Var25 4 Temperature Display Select Var30 5 System Variables Var31 through Var36 6 Electro Sentry 1 Operation Notes Section 9 Alarms 9 Latching and holding of Alarms 9 How to clear Alarms 9 Using multiple Electro Sentry 1 s in the same application 10 Built in Test Features Section 10 Temperature Rise and Speed Drop Alarm Test Features 10 Troubleshooting Section 11 Standard Temperature vs 4 ...

Страница 4: ...the left of the J7 ribbon cable The Factory default setting of SW9 is for an NPN Pulse Train Encoder which is SW9 s switch 1 ON switch 2 OFF switch 3 OFF Note Electro Sensors Pulse Train Encoders are NPN encoders Variable Default Value User s Value Var01 Encoder_Type_Select 0000 4 20mA Analog Encoder 0001 Pulse Train Encoder 0000 For applications using a 4 20 mA Analog Speed Encoder i e Var01 0000...

Страница 5: ...y 0001 sec Var08 Underspeed_Start_Delay 0005 sec Var09 Speed_Display_Select 0000 and Enable 0001 RPM and Enable 0002 and Disable 0003 RPM and Disable See Note3 0000 Var34 Hour_and_Speed_ Command_Select 0000 Maintained Disable Enable 0001 One Shot Disable Enable with Disable Closed 0002 One Shot Disable Enable with Disable Open 0000 Factory default for Var34 is 0000 for a Maintained Disable Enable ...

Страница 6: ...Factory default for Var11 is 0000 for all Analog Inputs are set for 4 20 mA Temperature sensors C For those Analog Inputs that you are not using i e those Analog Inputs having no Temperature sensors or no Contact Closure sensors connected to them You must turn OFF the effect of any unused Analog Inputs by setting their BIAS Temperature Setpts to 0999 The BIAS Setpts are in Var14 through Var25 and ...

Страница 7: ...put as set by the position of the Analog Input s corresponding 3 digit LED display on the ES1 s Front Panel See section 3 C above for the correlation between VarXX BIAS Temperature Setpts and the Analog Input s See the UserVar Variables section in the Reference portion of the User Manual for details on any of the above mentioned VarXX s if so needed G What Temperature or Contact Closure alarms do ...

Страница 8: ...e i e Being in Program Mode disables the Hour Meter AND If the Hour_and_Speed_Enable command is present i e The Hour_and_Speed_Disable command disables the Hour Meter If any one of these three prerequisites are NOT met then the Hour Meter does NOT increment hours NOR do the Hour Meter s discrete Green Yellow Red LEDs light up as per the number of hours reached 6 Leave Var35 Test Mode Select at the...

Страница 9: ...absence of the VAR icon in the lower left corner of the LCD display Program Mode This mode allows the user to change the UserVar variables The LCD display will display the name of the present active variable as PrXX or its value as XXXX The Program Mode is indicated by the presence of the VAR icon in the lower left corner of the LCD display Entering and Using Program Mode Programming is accomplish...

Страница 10: ..._Rev Value This is the number of pulses generated by the rotating magnetic target Var02 range is 0000 to 9999 PPR Factory default for Var02 is 0008 PPR Note If Var01 0000 for the 4 20 mA Analog Encoder Type then Var02 is irrelevant and its value is ignored and a value of 60 PPR is assumed for internal frequency calculations Var03 PULSE_MAX_RPM or RPM_at_20mA If Var01 0000 for 4 20mA encoder type t...

Страница 11: ... operated in pairs and are horizontally across from each other on the ES1 s Front Panel Var11 range is 0000 to 1111 with only 0 s and 1 s allowed The left most digit programs the Contact Closure s Sensor Logic The three right most digits program the Analog Input pair s Sensor Type 0 Var11 Tail Rub Block Pair Inputs 11 12 Sensor Type 0 4 20mA 1 Contact Closure Knee Rub Block Pair Inputs 7 8 Head Ru...

Страница 12: ...ternal resistor between 360Ω to 390Ω 1 watt minimum must be used in line with the corresponding Analog Input s Signal terminal TBx pin2 as shown in the figure below The Electro Sentry 1 is supplied with 8 eight 360Ω 1 watt resistors 360Ω to 390Ω 1 watt minimum Contact Closure Type Sensor ES1 s 4 20mA Input 1 TBx 2 3 The Warning and Shutdown SetPt Temperature Variables Var12 and Var13 Var12 Warning...

Страница 13: ...ature 1 Var14 Head Bearing Left BIAS SetPt 2 Var15 Head Bearing Right BIAS SetPt 3 Var16 Head Rub Block Left BIAS SetPt 4 Var17 Head Rub Block Right BIAS SetPt 5 Var18 Knee Bearing Left BIAS SetPt 6 Var19 Knee Bearing Right BIAS SetPt 7 Var20 Knee Rub Block Left BIAS SetPt 8 Var21 KneeRub Block Right BIAS SetPt 9 Var22 Tail Bearing Left BIAS SetPt 10 Var23 Tail Bearing Right BIAS SetPt 11 Var24 Ta...

Страница 14: ...ed LEDs and turns ON the Hour Meter s discrete Green LED Note A Var31 0000 disables the Hour Meter i e keeps it from growing and also turns OFF the Hour Meter s discrete Green Yellow Red LEDs This Var31 0000 feature does NOT clear the Hour Meter but rather keeps it from growing any further when an Hour_and_Speed_ Enable command is present Note If the UserVar programming LCD screen is in Program Mo...

Страница 15: ... if the Disable Stop command at TB32 is not present Note If not using Speed Monitoring then see Var09 for how to disable Speed Monitoring completely which then leaves the Var34 settings to apply to just the Hour_Meter Factory default for Var34 is 0000 for a maintained closed input is needed at TB34 for an Enable command Note See the Troubleshooting Section for related discussion of Concerning the ...

Страница 16: ...B34 Hour_and_Speed_Enable command 6 TB31 1 2 Aux_Hour_Meter_Reset or Hour_Meter_Reset button on Front Panel 5 TB31 3 4 Aux_Test_Left_Side or Test_Left_Side button on Front Panel 4 TB31 5 6 Aux_Test_Right_Side or Test_Right_Side button on Front Panel 3 TB31 7 8 Aux_Test_Speed or Test_Speed button on Front Panel 2 TB31 9 10 Aux_Silence_Horn Alarm_Reset 1 CAUTION Doing this Var35 test may cause actua...

Страница 17: ...rm relays do Latch once the speed drops below one of the Speed Setpts but the actual 4 digit Speed display itself does NOT Latch This is because for safety reasons we want to show live speeds at all times whether or not the speed sensor has previously dropped below one of the Speed Setpts and then since recovered on its own How to clear Alarms 7 There are four ways to give a manual Silence_Horn Al...

Страница 18: ...n Give a manual Silence_Horn Alarm_ RESET command to the ES1 to clear any alarms generated by this test See Operations Notes Section How to Clear Alarms for details CAUTION This test will cause actual system alarms 2 Press and hold the TEST_RIGHT_SIDE button on the Front Panel to artificially increase the temperature readings in the right side column of temperature displays Keep the button pressed...

Страница 19: ... LED Yellow Lightstack Relay Speed Temperature Warning Relay Horn Relay Also in this situation the opposite side companion sensor does NOT go into a BIAS Setpt Yellow_Alarm as a BIAS response for code is in place to see that the first sensor failed Because of this the second sensor does NOT compare to a out of range sensor B If a Temperature sensor fails as HI_mA or Closed_ckt then its 3 digit dis...

Страница 20: ...n RPM However the Speed s discrete Yellow and Red LEDs and Speed Alarm relays do Latch once an out of range sensor has Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 Revision D 12 been detected but the actual Speed display itself does NOT Latch This is because for safety reasons we want to show live speeds at all times whenever the speed sensor is...

Страница 21: ...d Display Message Definition Live Speed CLS Analog Speed Encoder is 20 83mA or more Live Speed HI Analog Speed Encoder is between 20 7mA and 20 83mA Stop LO Analog Speed Encoder is between 1 0mA and 3 9mA Stop OPn Analog Speed Encoder is 1 0mA or less Other LCD LED speed display messages are these are lowest ranking LCD Display Message LED Speed Display Message Definition Flashing 9999 FFFF Speed ...

Страница 22: ...isplayed on a ramp down to STOP after an Hour_and_Speed_Disable command has been given If an Hour_and_Speed_Enable command is present at TB34 AND if Var09 has Speed Monitoring Enabled then the Speed display s discrete Green Yellow Red LEDs and speed alarms are all enabled and will activate as needed Note Var09 can be used to disable Speed Alarm Monitoring thereby allowing the Hour_and_Speed_ Enabl...

Страница 23: ...n damaged 3 The Electro Sentry 1 uses on board resettable fuses in the power supply paths going to the 4 20 mA Temperature Contact Closure sensors the 4 20 mA Analog Speed encoder and the Frequency Pulse Train Speed encoder For the Temperature or Contact Closure sensors the Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 Revision D 15 resettable fu...

Страница 24: ... Warning and Shutdown Temperature Two Warning and Shutdown Temperature Bias Twelve Warning Only Hour Meter Two Warning and Maintenance Relay Output Data Parameters Relays 1 2 3 4 5 Amp Dual Form C SPDT Relays 5 6 7 8 5 Amp Single Form A SPST Relay Contact Rating 5 Amp 30 Vdc or 250 Vac resistive Physical Environment Parameters Enclosure Material Polycarbonate Recommended Minimum Installation Area ...

Страница 25: ...DE TEST RIGHT SIDE TEST SPEED UNIT ALARM TEST RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED YELLOW GREEN RED RED Messages For 4 20mA Sensors OPn Open Circuit LO 1 0 To 3 9 mA HI 20 1 To 20 8 mA CLS Closed or Shorted Circu...

Страница 26: ...is shipped with SW1 set for 115Vac and with the replaceable fuse F12 as a 115Vac 0 4Amp Slo Blo fuse If your application needs SW1 switched to 230Vac then also install a 230Vac 0 2Amp Slo Blo fuse into F12 The ES1 is shipped with one extra 115Vac 0 4Amp Slo Blo fuse and one 230Vac 0 2Amp Slo Blo fuse Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 ...

Страница 27: ...y 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Relay 8 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 NOTE Analog and Digital circuits are NOT the same 24Vout A Vs 24Vout D Ground A Vs Ground D Brown Black and Shield refers to the wires used on Electro Sensors TT420 temperature sensors DIGITAL CONNECTIONS FUSE F12 SLO BLO 0 4A 115VAC SLO BLO 0 2A 230VA...

Страница 28: ...ETAIL Hour_and_Speed Disable Input Dry Contact COM IN TB32 1 TB32 2 FIELD ELECTRO SENTRY 1 FOR VAR34 0001 0002 MOMENTARY CLOSED ENABLE WIRING DETAIL Hour_and_Speed Enable Input Dry Contact COM IN TB34 1 TB34 2 FIELD ELECTRO SENTRY 1 FOR VAR34 0000 MAINTAINED CLOSED ENABLE MAINTAINED OPEN DISABLE WIRING DETAIL Hour_and_Speed Disable Enable Input Dry Contact IN COM TB34 1 TB34 2 FIELD ELECTRO SENTRY...

Страница 29: ... Var17 Input 4 Bias Temp Set Point 4 0000 Var18 Input 5 Bias Temp Set Point 4 0000 Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 Revision D 21 Var19 Input 6 Bias Temp Set Point 4 0000 Var20 Input 7 Bias Temp Set Point 4 0000 Var21 Input 8 Bias Temp Set Point 4 0000 Var22 Input 9 Bias Temp Set Point 4 0000 Var23 Input 10 Bias Temp Set Point 4 0000...

Страница 30: ...Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 Revision D 22 Electro Sentry Enclosure Dimensions 7 88 7 57 12 68 7 63 12 05 14 88 14 00 13 41 ...

Страница 31: ...Free Catalog and Application Assistance 1 800 328 6170 Website www electro sensors com 990 005500 Revision D 23 This page left intentionally blank ...

Страница 32: ......

Отзывы: