Doc
#
E149701
C-7
C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 10 - Binary Output States
Read with Object 10, Var 2, and Qualifiers 0, 1, 2 or 6. (Included in Class 0
responses.)
Supported Flags:
Bit 0: ONLINE (0=Offline, 1=Online) (If the Input is not present it will be shown as
Offline.)
Bit 1: RESTART (1=The Object is in the Initial State and has not been updated since
Restart.)
Bit 7: STATE (0=Off, 1=On)
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
10
0
2
Reset Energy
Counters
BYTE
Always 1
N/A
None
10
1
2
Change to
Modbus RTU
Protocol
BYTE
Always 1
N/A
None
10
2
2
Reset Demand
Counters (Max
/ Min )
BYTE
Always 1
N/A
None
10
3
2
Read Relay 1
State RO1S
Relay 1
(expansion
port 1)
BYTE
Bit Flags
N/A
None
Returns the Status and
State of the Relay in
the Flags.
10
4
2
Read Relay 2
State RO1S
Relay 2
(expansion
port 1)
BYTE
Bit Flags
N/A
None
Returns the Status and
State of the Relay in
the Flags.
10
5
2
Read Relay 3
State RO1S
Relay 1
(expansion
port 2)
BYTE
Bit Flags
N/A
None
Returns the Status and
State of the Relay in
the Flags.
10
6
2
Read Relay 4
State RO1S
Relay 2
(expansion
port 2)
BYTE
Bit Flags
N/A
None
Returns the Status and
State of the Relay in
the Flags.
Содержание Shark 200