Doc
#
E149701
C-14
C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
30
16
4
Positive VARs,
3-Ph,
Maximum Avg
Demand
SINT16
-32768 to
+32767
1, 10, 100, or
1000
VAR
30
17
4
Negative
Watts, 3-Ph,
Maximum Avg
Demand
SINT16
-32768 to
+32767
1, 10, 100, or
1000
W
30
18
4
Negative
VARs, 3-Ph,
Maximum Avg
Demand
SINT16
-32768 to
+32767
1, 10, 100, or
1000
VAR
30
19
4
VAs, 3-Ph,
Maximum Avg
Demand
SINT16
-32768 to
+32767
1, 10, 100, or
1000
VA
30
20
4
Angle, Phase A
Current
SINT16
-1800 to
+1800
0.1
degree
30
21
4
Angle, Phase B
Current
SINT16
-1800 to
+1800
0.1
degree
30
22
4
Angle, Phase C
Current
SINT16
-1800 to
+1800
0.1
degree
30
23
4
Angle, Volts
A-B
SINT16
-1800 to
+1800
0.1
degree
30
24
4
Angle, Volts
B-C
SINT16
-1800 to
+1800
0.1
degree
30
25
4
Angle, Volts
C-A
SINT16
-1800 to
+1800
0.1
degree
30
26
4
CT numerator
SINT16
1 to 9999
N/A
none
CT ratio =
(numerator
* multiplier)
/ denomina-
tor
30
27
4
CT multiplier
SINT16
1, 10, or 100
N/A
none
30
28
4
CT
denominator
SINT16
1 or 5
N/A
none
30
29
4
PT numerator
SINT16
1 to 9999
N/A
none
PT ratio =
(numerator
* multiplier)
/ denomina-
tor
30
30
4
PT multiplier
SINT16
1, 10, or 100
N/A
none
30
31
4
PT
denominator
SINT16
1 to 9999
N/A
none
30
32
4
Neutral
Current
SINT16
0 to 32767
(10 / 32768)
A
Point value
= Actual
Amps/divisor
30
33
4
PowerFactor,
Phase A
SINT16
-1000 to
+1000
0.001
None
30
34
4
Power Factor,
Phase B
SINT16
-1000 to
+1000
0.001
None
30
35
4
Power Factor,
Phase C
SINT16
-1000 to
+1000
0.001
None
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments