SAFETY INSTRUCTIONS 

 

Important! 

  Carefully read the instructions before operating the unit. 

  This  appliance  comprises  of  an  indoor  and  an  outdoor  unit.  The  indoor  slim  evaporator  is 

designed exclusively for indoor floor, wall or ceiling installations while the external condenser 
should be installed outside while still away from flood water or snow line. 

  Rating: This unit must be only connected to a 220-240 V / 50 Hz earthed power source. 

  Installation must be in accordance with the regulations of the country where it is used. 

  European Union regulations requires for an F-Gas trained engineer to handle any operation 

where  non-qualified  intervention  could  cause  fluorinated  gas  escape.  A  commissioning 
certificate must be issued with any installation. 

  This air conditioner contains R32 which is a safe efficient refrigerant which has a lower 

environmental burden than traditional refrigerants. 

  The refrigerant used in this air conditioner is an environmentally friendly hydrocarbon R32, 

which has a very low Global Warming Potential compared to traditional refrigerants. 

  R32 is classed as slightly flammable and as such naked flames and sources of ignition 

should be kept a safe distance from the unit. 

  If you are in any doubt about the suitability of your electrical supply have it checked and, if 

necessary, modified by a qualified electrician. 

  This air conditioner has been tested and is safe to use. However, as with any electrical 

appliance - use it with care. 

  Disconnect the power before dismantling, assembling or cleaning. 

  Avoid touching any moving parts within the appliance. 

  Never insert fingers, pencils or any other objects through the guard 

  This appliance is not intended for use by persons (including children) with reduced physical, 

sensory or mental capabilities. It is also not intended for use by those with a lack of experience 
and knowledge, unless they have been given supervision or instruction concerning the use of 
the  appliance  by  a  person  responsible for their safety.  Do  not  leave children  unsupervised 
with this appliance. 

  Do not clean the unit by spraying it or immersing it in water. 

  Never connect the unit to an electrical outlet using an extension cord. Both the indoor and 

outdoor units must be hardwired by a qualified electrician. 

  Never operate this appliance if the cord is damaged. Ensure the power cord is not stretched 

or exposed to sharp objects / edges. 

  A damaged supply cord should be replaced by the manufacturer or a qualified electrician in 

order to avoid a hazard. 

  Any  service  other  than  regular  cleaning  or  filter  replacement  should  be  performed  by  an 

authorized service representative or a qualified air conditioning engineer. Failure to comply 
could result in a voided warranty. 

  Do not use the appliance for any purpose other than its intended use. 

  The outdoor part of the air conditioner unit must always be stored and transported upright, 

otherwise  irreparable  damage  may  be  caused  to  the  compressor;  if  in  doubt  we  suggest 
waiting at least 24 hours before starting the unit. 

  Avoid restarting the air conditioner unless 3 minutes have passed since being turned off. 

This prevents damage to the compressor. 

  Never use the mains as a switch to start and turn off the air conditioning unit. Use the 

provided ON/OFF button located on the remote control. 

  Always place the unit on a dry and stable surface. Install the outdoor unit on a wall with wall- 

mounted brackets or fix  on floor slab with special floor mounting slab or brackets. 

  The indoor unit should not be installed in laundry or wet rooms. 

Содержание eiQ-FC18K

Страница 1: ...PUMP eiQ FC18K 18 000 BTU eiQ FC24K 24 000 BTU eiQ FC36K 36 000 BTU Thank you for choosing electriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for futu...

Страница 2: ...CONTROL 8 REPLACING THE BATTERIES 10 FILTERS 13 START OF SEASON 14 END OF SEASON 14 INSTALLATION GUIDE 15 TOOLS RECOMMENDED FOR INSTALLATION 18 INSTALLATION OF THE OUTDOOR UNIT 23 PIPELINES CONNECTION...

Страница 3: ...not intended for use by persons including children with reduced physical sensory or mental capabilities It is also not intended for use by those with a lack of experience and knowledge unless they hav...

Страница 4: ...ssary depending on the air quality For the initial startup set the fan speed to maximum and the thermostat to 4 5 degrees lower than the current temperature After set the fan switch to low and set the...

Страница 5: ...ilter and over the evaporator 1 blowing the cooled air back into the room The heat is moved to the compressor along with the gas A fan 8 draws air over the condenser and blows the warm air away 1 Evap...

Страница 6: ...6 ALTERNATIVE WAYS TO MOUNT CEILING MOUNTED FLOOR MOUNTED...

Страница 7: ...mperatures the unit will enter defrost mode to prevent compressor damage and the compressor will heat for a while TIMER YELLOW Indicates the timer is active PROTECTION RED Fault protection mode may be...

Страница 8: ...s on the remote CLOCK Press to adjust the current time LIGHT Dependant on Model Forced closing or lighting of display panel Decide whether to have this function according to the actual model HORIZONTA...

Страница 9: ...ION FAN MODE ECON FUNCTION HEATING MODE CLEANING FUNCTION TEMPERATURE DISPLAY REMOTE LOCKED CURRENT TEMPERATURE Ranges between 16 32 C BATTERY LOW FAN SPEED AUTO CONFIG LENGTH OF BAR INDICATES FAN SPE...

Страница 10: ...n pressing this button the desired temperature will be increased by 1 C When pressing this button in dehumidification and fan modes the desired temperature will not be adjusted 2 After the clock butto...

Страница 11: ...set to 26 4 When ECON mode is turned off the desired temperature will return to the value before the button was pressed 5 Switching between modes will turn off ECON mode SLEEP 1 Sleep mode can be acti...

Страница 12: ...the heat pump will degrade with lowering external temperatures Please note the performance will reduce when the outdoor temperature drops below 5 C CAPACITY The required cooling or heating capacity d...

Страница 13: ...unit is cellingmounted pleaseensureenoughspaceis left to servicethe filters Identify the filters and remove them as per the procedure bellow Find the groove on the panel and pull the filter out When...

Страница 14: ...intake and exhaust openings free of debris etc Cleaning with chemicals may cause damage Use professional installers to service the fan or the other parts START OF SEASON If the air conditioner is to b...

Страница 15: ...nances and standards Check the mains voltage and frequency This unit is only suitable for earthed electrical supply connection voltage 230V 50 Hz The fuse used should be 1 5 3 times the maximum power...

Страница 16: ...tioner must not be installed in a wet environment such as a bathroom shower or swimming pool etc Make sure that there is a minimum of 35 mm clearance in all directions A B C When outdoor unit is insta...

Страница 17: ...or unit installation is made in respect to installation dimension diagram with easy maintenance access Select a place where it is out of reach of children Do not block utilities access or fire escapes...

Страница 18: ...e Cutter Spirit Level Number 14 7mm Masonry Drill Pencil and Chalk 1 5 inch number 10 screws Small Stepladder 7mm Wall Plugs Protective Glasses and Mask Pipe and Cable Detector 4 inch Plastic Ties 2 I...

Страница 19: ...esired length and then place it in the drilled hole CEILING MOUNTING The mounting surface should be solid brick concrete or other equivalent strength structure with sufficient loading capacity Failing...

Страница 20: ...ipes drain pipes control and electrical wires before you permanently hang the indoor unit The installation steps for embedded style are basically the same with the hanging style but remove the left an...

Страница 21: ...re of the ceiling set the thread pitch based on the size of this unit as bellow WOODEN STRUCTURES STEEL SKELETON STRUCTURES Place the square bar on the girders and install the lifting bolts Set direct...

Страница 22: ...dity is very high Tidy up the copper pipes electrical cables and water drains and pass them through the piping wall hole drilled before Notes 1 Either the indoor unit or the outdoor unit can be higher...

Страница 23: ...bolts and nuts to fix the outdoor unit firmly on the supports and keep on the same level If the unit is installed on the wall or at the rooftop the supports have to be firmly fixed so as to resist ear...

Страница 24: ...24 FOOTPRINT OF THE OUTDOOR UNITS DIMENSIONS mm Unit eiQ FC18 A B C D E 925 366 700 590 340...

Страница 25: ...25 DIMENSIONS mm Unit eiQ FC24 A B C D E F 958 392 843 600 360 330 DIMENSIONS mm Unit eiQ FC36 A B C D E F 1030 432 788 707 389 370...

Страница 26: ...surface of the pipe against the connector vertically twist the connectors to the bottom of the bolt and finally tighten them with a torque wrench AIR PURGING WITH VACUUM PUMP 1 Check that pipelines c...

Страница 27: ...ength This operation can only be performed by a professional F Gas engineer for the additional gas amount see the below Liquid pipe diameter Additional Refrigerant Additional Refrigerant 6 3 or 6 1 4...

Страница 28: ...ipeline connection is done use a leakage inspection device to carefully check if there is any leakage at the joints This is an important step to ensure the quality of installation Once a leak is detec...

Страница 29: ...ing radius please make the packed soft pipes vertical before Please do not extend only one side of the packed soft pipes Please make use of semicircle pulley to keepthe allowed bending angle Extreme b...

Страница 30: ...ELECTRICAL WIRING DIAGRAMS For ease of installation the indoor unit of most models will be provided pre wired with 5 metres of interconnecting cable eiQ FC18K eiQ FC24K eiQ FC36K Indoor Unit Outdoor U...

Страница 31: ...ON OF THE POWER CORD Supply the power to both indoor outdoor units following the wiring diagrams in this manual Where discrepancies are found between the diagram within the manual and the circuit diag...

Страница 32: ...se sequence fault E0 Indoor and out unit communication failure E1 Timing lights flash Temperature sensor T1 fault E2 Running lights flash Pipe temperature sensor in the evaporator T2 fault E3 Running...

Страница 33: ...rved Display Error description Display Error description P0 reserved H0 Communication error between outdoor unit main board and driver board P1 reserved H1 reserved P2 reserved H2 reserved P3 Primary...

Страница 34: ...inverter current operating capacity factor adjusted from outdoor unit requirements T4 eiq FC18K 5 3kw eiq FC24K 7 1kw eiq FC36K 10 5kw eiq FC48K 14kw The kw is converted approximatively to hp in the...

Страница 35: ...valve has 500 steps from close position The display will show from 0 20 to 60 500 which is the valve step divided by 8 12 Primary current AC Primary circuit load Amps 13 Secondary circuit current AC S...

Страница 36: ...1400 1400 Insulation class E E Indoor coil Number of rows 2 3 Tube pitch a xrow pitch b Mm 21 13 37 21 13 37 Fin spacing Mm 1 4 1 4 Fin type Hydrophilic Hydrophilic Tube outside dia and type mm 7 7 i...

Страница 37: ...min 1400 Insulation class E Indoor coil Number of rows 3 Tube pitch a xrow pitch b mm 21 13 37 Fin spacing mm 1 4 Fin type Hydrophilic Tube outside dia and type mm 7 inner grooved Coil length x heigh...

Страница 38: ...This means that if your air conditioner develops a fault during the guarantee period we will arrange for it to be repaired or replaced Faults arising from a faulty installation are specifically exclud...

Страница 39: ...our local household waste recycling centres WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall be stored in...