ElectrIQ eiQ-FC18K Скачать руководство пользователя страница 13

13 

 

FILTERS 

 

 

Turn off the appliance from the consumer unit before attempting to service the filters. Never attempt 
servicing the unit while the power is on. If the unit is celling mounted, please ensure enough space is left 
to service the filters 

 
 

Identify the filters and remove them as per 
the procedure bellow 

 
 
 
 
 

Find the groove on the panel and pull the filter out 

When removing the filter please make sure you do it from middle or use both hands ensuring it is 
pulled with equal force. Failure to do this may damage the filter. 

 

 

Содержание eiQ-FC18K

Страница 1: ...PUMP eiQ FC18K 18 000 BTU eiQ FC24K 24 000 BTU eiQ FC36K 36 000 BTU Thank you for choosing electriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for futu...

Страница 2: ...CONTROL 8 REPLACING THE BATTERIES 10 FILTERS 13 START OF SEASON 14 END OF SEASON 14 INSTALLATION GUIDE 15 TOOLS RECOMMENDED FOR INSTALLATION 18 INSTALLATION OF THE OUTDOOR UNIT 23 PIPELINES CONNECTION...

Страница 3: ...not intended for use by persons including children with reduced physical sensory or mental capabilities It is also not intended for use by those with a lack of experience and knowledge unless they hav...

Страница 4: ...ssary depending on the air quality For the initial startup set the fan speed to maximum and the thermostat to 4 5 degrees lower than the current temperature After set the fan switch to low and set the...

Страница 5: ...ilter and over the evaporator 1 blowing the cooled air back into the room The heat is moved to the compressor along with the gas A fan 8 draws air over the condenser and blows the warm air away 1 Evap...

Страница 6: ...6 ALTERNATIVE WAYS TO MOUNT CEILING MOUNTED FLOOR MOUNTED...

Страница 7: ...mperatures the unit will enter defrost mode to prevent compressor damage and the compressor will heat for a while TIMER YELLOW Indicates the timer is active PROTECTION RED Fault protection mode may be...

Страница 8: ...s on the remote CLOCK Press to adjust the current time LIGHT Dependant on Model Forced closing or lighting of display panel Decide whether to have this function according to the actual model HORIZONTA...

Страница 9: ...ION FAN MODE ECON FUNCTION HEATING MODE CLEANING FUNCTION TEMPERATURE DISPLAY REMOTE LOCKED CURRENT TEMPERATURE Ranges between 16 32 C BATTERY LOW FAN SPEED AUTO CONFIG LENGTH OF BAR INDICATES FAN SPE...

Страница 10: ...n pressing this button the desired temperature will be increased by 1 C When pressing this button in dehumidification and fan modes the desired temperature will not be adjusted 2 After the clock butto...

Страница 11: ...set to 26 4 When ECON mode is turned off the desired temperature will return to the value before the button was pressed 5 Switching between modes will turn off ECON mode SLEEP 1 Sleep mode can be acti...

Страница 12: ...the heat pump will degrade with lowering external temperatures Please note the performance will reduce when the outdoor temperature drops below 5 C CAPACITY The required cooling or heating capacity d...

Страница 13: ...unit is cellingmounted pleaseensureenoughspaceis left to servicethe filters Identify the filters and remove them as per the procedure bellow Find the groove on the panel and pull the filter out When...

Страница 14: ...intake and exhaust openings free of debris etc Cleaning with chemicals may cause damage Use professional installers to service the fan or the other parts START OF SEASON If the air conditioner is to b...

Страница 15: ...nances and standards Check the mains voltage and frequency This unit is only suitable for earthed electrical supply connection voltage 230V 50 Hz The fuse used should be 1 5 3 times the maximum power...

Страница 16: ...tioner must not be installed in a wet environment such as a bathroom shower or swimming pool etc Make sure that there is a minimum of 35 mm clearance in all directions A B C When outdoor unit is insta...

Страница 17: ...or unit installation is made in respect to installation dimension diagram with easy maintenance access Select a place where it is out of reach of children Do not block utilities access or fire escapes...

Страница 18: ...e Cutter Spirit Level Number 14 7mm Masonry Drill Pencil and Chalk 1 5 inch number 10 screws Small Stepladder 7mm Wall Plugs Protective Glasses and Mask Pipe and Cable Detector 4 inch Plastic Ties 2 I...

Страница 19: ...esired length and then place it in the drilled hole CEILING MOUNTING The mounting surface should be solid brick concrete or other equivalent strength structure with sufficient loading capacity Failing...

Страница 20: ...ipes drain pipes control and electrical wires before you permanently hang the indoor unit The installation steps for embedded style are basically the same with the hanging style but remove the left an...

Страница 21: ...re of the ceiling set the thread pitch based on the size of this unit as bellow WOODEN STRUCTURES STEEL SKELETON STRUCTURES Place the square bar on the girders and install the lifting bolts Set direct...

Страница 22: ...dity is very high Tidy up the copper pipes electrical cables and water drains and pass them through the piping wall hole drilled before Notes 1 Either the indoor unit or the outdoor unit can be higher...

Страница 23: ...bolts and nuts to fix the outdoor unit firmly on the supports and keep on the same level If the unit is installed on the wall or at the rooftop the supports have to be firmly fixed so as to resist ear...

Страница 24: ...24 FOOTPRINT OF THE OUTDOOR UNITS DIMENSIONS mm Unit eiQ FC18 A B C D E 925 366 700 590 340...

Страница 25: ...25 DIMENSIONS mm Unit eiQ FC24 A B C D E F 958 392 843 600 360 330 DIMENSIONS mm Unit eiQ FC36 A B C D E F 1030 432 788 707 389 370...

Страница 26: ...surface of the pipe against the connector vertically twist the connectors to the bottom of the bolt and finally tighten them with a torque wrench AIR PURGING WITH VACUUM PUMP 1 Check that pipelines c...

Страница 27: ...ength This operation can only be performed by a professional F Gas engineer for the additional gas amount see the below Liquid pipe diameter Additional Refrigerant Additional Refrigerant 6 3 or 6 1 4...

Страница 28: ...ipeline connection is done use a leakage inspection device to carefully check if there is any leakage at the joints This is an important step to ensure the quality of installation Once a leak is detec...

Страница 29: ...ing radius please make the packed soft pipes vertical before Please do not extend only one side of the packed soft pipes Please make use of semicircle pulley to keepthe allowed bending angle Extreme b...

Страница 30: ...ELECTRICAL WIRING DIAGRAMS For ease of installation the indoor unit of most models will be provided pre wired with 5 metres of interconnecting cable eiQ FC18K eiQ FC24K eiQ FC36K Indoor Unit Outdoor U...

Страница 31: ...ON OF THE POWER CORD Supply the power to both indoor outdoor units following the wiring diagrams in this manual Where discrepancies are found between the diagram within the manual and the circuit diag...

Страница 32: ...se sequence fault E0 Indoor and out unit communication failure E1 Timing lights flash Temperature sensor T1 fault E2 Running lights flash Pipe temperature sensor in the evaporator T2 fault E3 Running...

Страница 33: ...rved Display Error description Display Error description P0 reserved H0 Communication error between outdoor unit main board and driver board P1 reserved H1 reserved P2 reserved H2 reserved P3 Primary...

Страница 34: ...inverter current operating capacity factor adjusted from outdoor unit requirements T4 eiq FC18K 5 3kw eiq FC24K 7 1kw eiq FC36K 10 5kw eiq FC48K 14kw The kw is converted approximatively to hp in the...

Страница 35: ...valve has 500 steps from close position The display will show from 0 20 to 60 500 which is the valve step divided by 8 12 Primary current AC Primary circuit load Amps 13 Secondary circuit current AC S...

Страница 36: ...1400 1400 Insulation class E E Indoor coil Number of rows 2 3 Tube pitch a xrow pitch b Mm 21 13 37 21 13 37 Fin spacing Mm 1 4 1 4 Fin type Hydrophilic Hydrophilic Tube outside dia and type mm 7 7 i...

Страница 37: ...min 1400 Insulation class E Indoor coil Number of rows 3 Tube pitch a xrow pitch b mm 21 13 37 Fin spacing mm 1 4 Fin type Hydrophilic Tube outside dia and type mm 7 inner grooved Coil length x heigh...

Страница 38: ...This means that if your air conditioner develops a fault during the guarantee period we will arrange for it to be repaired or replaced Faults arising from a faulty installation are specifically exclud...

Страница 39: ...our local household waste recycling centres WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall be stored in...

Отзывы: