2-1
PRODUCT DATA SHEET
Revision Y05-01
Service Manual - EMD Series
2. PRODUCT
DATA
SHEET
2.1 R22/R407C
Model (Indoor & Outdoor)
EMD 27 & OU6-27 RC R22
Installation method
Ducted
Characteristics Units
Cooling
Heating
Btu/Hr 26600
27300
Capacity
Kw 7.8
8.0
Power input
Kw
2.8
2.4
COP W/W
2.79
3.28
Power supply
V/Hz/Ph
230V/50Hz/1PH
Rated current
A
11.6
10.0
Starting current
A
67
Circuit breaker rating
A
20
Fan type & quantity
Centrifugal & 1
Fan speeds
H/ M/ L
RPM
900
800
700
Air flow
*
H/
M/
L
M³/Hr
1800 1560 1300
External static pressure
Min-Max
Pa
25 - 70
Sound power level
**
H/
M/
L
dBa 68.2
65.5
61.3
Sound pressure level
***
H/
M/
L dBa
54.3
51.5
48.5
Moisture removal
Lt/Hr
1.7
Condensate drain tube I.D
mm
19
Dimensions
W/ H / D
mm
785
400
595
Weight Kg
32
Package dimensions
W/ H / D
mm
825
425
610
Package weight
Kg
34
Units per pallet
Units
8
INDOOR
Stacking height
Units
4
Refrigerant control
Capillary tube
Compressor type
Scroll
Fan type & quantity
Axial & 1
Fan speeds
H / L
RPM
920
Air flow
H / L
M³/Hr
2350
Sound power level
H / L
dBa
69
Sound pressure level ***
H / L
dBa
62
Dimensions
W/ H / D
mm
900
580
340
Weight Kg
64
Package dimensions
W/ H / D
mm
985
640
410
Package weight
Kg
67
Units per pallet
Units
9
Stacking height
Units
3
Refrigerant type
R22
Charge / Distance
Kg/ M
2.1/ 7.5
Additional charge per 1 meter
Grams
25
Liquid line
Inch
3/8
Suction line
Inch
5/8
Max. tubing length
Meter
25
OUTDOOR
Connections
between
units
Max. height difference
Meter
10
Operation control type
LCD Remote control
Heating elements
Kw
No
Others
Crankcase
heater
(60W)
*
Airflow in ducted units; according to nominal external static pressure.
** Sound power in ducted units is measured at air outlet side.
*** Sound pressure level is measured at 1-meter distance from the unit.
Содержание EMD 27
Страница 35: ...6 2 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 2 Model EMD 35 RC Heat Pump...
Страница 36: ...6 3 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 3 Models EMD 27 35 ST Cooling Only...
Страница 37: ...6 4 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 4 Models EMD 40 45 50 60 RC Heat Pump...
Страница 38: ...6 5 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 5 Model EMD 40 45 50 ST Cooling Only...
Страница 43: ...7 4 CONTROL SYSTEM Revision Y05 01 Service Manual EMD Series GANG BOARD DISPLAY BOARD...