7-7
CONTROL SYSTEM
Revision Y05-01
Service Manual - EMD Series
2
General functions for all models
2.1 COMP operation
2.1.1
For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting, excluding
DEICING Mode (see 7.2.1).
2.1.2
The Min operation time of COMP under different operating conditions is
Operation Mode
Min operation time of
COMP
Heat, Cool, H.P protection or Auto Modes
3 min.
Fan, Dry, Overflow, Protection modes, or mode change
ignored
2.2 IFAN
operation
2.2.1
Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.
2.2.2
Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
2.2.3
IFAN speed in Heat/Cool Autofan Mode is determined according to the following chart:
T [
o
c]
L
M
H
IFAN speed
3
1
4
2
where in
Heat
Mode:
'
T = SPT - RT
in
Cool
Mode:
'
T = RT- SPT
2.3 OFAN
operation
2.3.1
Min time interval between OFAN ON/OFF state change is 30 sec.
2.4 HE
operation
2.4.1
Minimum Heaters ON or OFF time is 30 sec.
2.4.2
Heaters can never be in operation while IFAN is OFF.
2.4.3
In RH group, HE-1 and HE-2 will be activated only when COMP is not operating, except in Dry Mode.
2.5 Protections
2.5.1
High pressure protection is applicable to all operating modes.
2.5.2
Deicing control is valid in Heat and Auto Heat Mode only.
2.5.3
Defrosting control is valid in Dry, Cool, and Auto Cool Modes.
Содержание EMD 27
Страница 35: ...6 2 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 2 Model EMD 35 RC Heat Pump...
Страница 36: ...6 3 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 3 Models EMD 27 35 ST Cooling Only...
Страница 37: ...6 4 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 4 Models EMD 40 45 50 60 RC Heat Pump...
Страница 38: ...6 5 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 5 Model EMD 40 45 50 ST Cooling Only...
Страница 43: ...7 4 CONTROL SYSTEM Revision Y05 01 Service Manual EMD Series GANG BOARD DISPLAY BOARD...