3-1
RATING CONDITIONS
Revision Y05-01
Service Manual - EMD Series
3. RATING
CONDITIONS
NOTES:
1. Rating conditions ISO/CD 13253R
Cooling: indoor: 27
q
C (80
q
F) DB 19
q
C (66
q
F) WB
Outdoor: 35
q
C (95
q
F) DB
Heating: indoor: 20
q
C (68
q
F) DB
Outdoor: 7
q
C (45
q
F) DB 6
q
C (43
q
F) WB
Refrigerant tubing length (one way) 7.5m (24.6 ft)
2. Guaranteed operating range:
Indoor
Outdoor
Upper limit
32
q
C DB, 23
q
C WB
46
q
C DB
Cooling
Lower limit
21
q
C DB, 15
q
C WB
21
q
C DB
Upper limit
27
q
C DB
24
q
C DB, 18
q
C WB
-5
q
C DB, -6
q
C WB (For R22)
Heating
Lower limit
20
q
C DB
-9
q
C DB, -10
q
C WB (For R407C)
1 PH
198 – 242 V
Voltage
3 PH
360 – 440 V
Содержание EMD 27
Страница 35: ...6 2 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 2 Model EMD 35 RC Heat Pump...
Страница 36: ...6 3 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 3 Models EMD 27 35 ST Cooling Only...
Страница 37: ...6 4 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 4 Models EMD 40 45 50 60 RC Heat Pump...
Страница 38: ...6 5 REFRIGERATION DIAGRAMS Revision Y05 01 Service Manual EMD Series 6 5 Model EMD 40 45 50 ST Cooling Only...
Страница 43: ...7 4 CONTROL SYSTEM Revision Y05 01 Service Manual EMD Series GANG BOARD DISPLAY BOARD...