TROUBLESHOOTING
No SYMPTOM
PROBABLE
CAUSE
CORRECTIVE
ACTION
Indoor coil block
Clean filters and/or remove block
Outdoor coil block
Remove block and/or avoid air by-
pass
EEV problem
Check EEV (12.4.7)
11.
Compressor is over heated and unit does
Refrigerant leakage
Indoor coil block
Check refrigeration system (12.2)
Clean filters and/or remove block
not generate capacity
Outdoor coil block
Remove block and/or avoid air by-
pass
12. Compressor stops during operation
Electronic control
Check diagnostics (see 12.3
below)
Refrigerant leakage
Check refrigeration system (12.2)
13.
Not all units are operating
Communication problems
Check diagnostics (see 12.3
below)
14.
Compressor does not start
Electronics control problem
or protection
15.
Unit works in wrong mode (cool instead
of heat or heat instead of cool)
Electronics or RV problem
Check RV (12.4.6)
16.
All components are operating properly
but no cooling or no heating
Refrigerant leak
Check refrigeration system (12.2)
17.
Compressor motor is generating noise
and no suction occurs
Phase order to compressor
is wrong
Check compressor phase order
18.
Freezing of outdoor unit in heat mode
and outdoor unit base is blocked with ice
Connect
base
heater
19.
The unit stop suddenly during operation
EMC interference to the A/C
unit
Check for EMC problems
(12.4.10.1)
20.
Indoor unit(s) Indicator(s) leds may flicker
21.
Other home appliances operation is faulty
such as noise appears in the television
picture, or the picture is distorted or static
occurs in the radio sound
EMC interference by the A/C
unit
Check for EMC problems
(12.4.10.2)
22. All others
Specific problems of indoor
or outdoor units
Check diagnostics (see 12.3
below)
12.2
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in technician Mode where the system operates as in fixed settings. The performance curves
given in this manual are given for unit performance in Technician mode when high indoor fan
speed is selected.
For entering technician mode check
11.7
.
12.3 Diagnostics
12.3.1
Outdoor unit diagnostics and corrective actions
No
Fault Name
Fault Description
Corrective Action
1 OCT
bad
Thermistor not connected or damaged
Check Thermistor ( 12.4.8)
2 CTT
bad
3 HST
bad
4 OAT
bad
5 TSUC
bad
6 RGT
bad
7 OFAN/Compressor
Feedback Loss
OFAN halls or wires bad. Compressor
wire cable bad or IPM bad or compresor
bad
Check OFAN motor ( 12.4.4) and compressor
(12.4.5)
8
OFAN - IPM fault
Over current / Over temperature of
OFAN IPM
Check no obstruction to controller air opening
Check OFAN motor ( 12.4.4)
Check motor type matches motor jumpers in
controller
9
OFAN Lock
Fan does not rotate
Check OFAN motor ( 12.4.4)
12-2
Revision
0
Содержание ECF12 DCI INV
Страница 14: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 Indoor Unit WNG 9 12 DCI 4 2 Indoor Unit WNG 18 DCI...
Страница 15: ...OUTLINE DIMENSIONS 4 3 Indoor Unit ECF 9 12 18 DCI 4 4 Indoor Unit PXD 9 1 18 DCI 4 2 Revision 0...
Страница 16: ...OUTLINE DIMENSIONS 4 5 Indoor Unit LS 35 DCI 4 6 Outdoor Units TRIO QUATTRO DCI 0...
Страница 51: ...WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 Outdoor Units TRIO QUATTRO DCI Revision 0 8 1...
Страница 87: ......