RATING CONDITIONS
3. RATING
CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating
Limits
Indoor
Outdoor
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Cooling
Lower limit
21
o
C DB 15
o
C WB
-10
o
C DB
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Heating
Lower limit
10
o
C DB
-15
o
C DB -16
o
C WB
1PH
198 – 264 V
Voltage
3PH
N/A