CONTROL SYSTEM
11.5.2.5 Speed Step Limitations
11.5.2.5.1
Step 1 and step 2
The compressor speed cannot go below
Step1RPS
or above
Step2RPS
during 3 continuous
minutes once after the compressor starts up when the ODU unit changes from STBY
11.5.2.5.2
Step 3 limit
The speed cannot go higher than
Step3RPS
unless it was operating for more than 1
continuous minute between
Step3RPS
– 5 and
Step3RPS
.
11.5.3 EEV
Control
11.5.3.1 Operation
Range
The EEV operation range is defined according to the operation mode as following
ODU Mode
Normal operation
IDU inactive
Compressor off
SB
200
200
COOL
80
to
350
0
HEAT
70
to
400
60
to
140
11.5.3.2 Reaching
target
value
rules
For all cases except at EEV initialization procedure, each EEV can move no more than
20
steps at a time.
When required the EEV’s move, one by one in sequence, till the target position is achieved for
every EEV.
The following diagram presents the EEV steps till the target position is set.
EEV3
EEV1
EEV2
EEV3
EEV4
EEV1
EEV3
EEV4
EEV4
EEV3
EEV3
EEV2
EEV1
EEV4
EEV3
set
set
set
set
11.5.3.3 EEV Operation when ODU changes to SB Mode
When the ODU mode is changed to SB, the following is performed immediately:
-
All EEV’s are set to
200
.
-
They remain in this position for
60
Sec.
-
Then, performs reset (
homing
) procedure.
11-12
Revision
0
Содержание ECF12 DCI INV
Страница 14: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 Indoor Unit WNG 9 12 DCI 4 2 Indoor Unit WNG 18 DCI...
Страница 15: ...OUTLINE DIMENSIONS 4 3 Indoor Unit ECF 9 12 18 DCI 4 4 Indoor Unit PXD 9 1 18 DCI 4 2 Revision 0...
Страница 16: ...OUTLINE DIMENSIONS 4 5 Indoor Unit LS 35 DCI 4 6 Outdoor Units TRIO QUATTRO DCI 0...
Страница 51: ...WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 Outdoor Units TRIO QUATTRO DCI Revision 0 8 1...
Страница 87: ......