12-1
CONTROL SYSTEM
SM LEXDCI 1-E.1 GB
12.
CONTROL SYSTEM for LEX 50, LEX 60, LEX 72 Z DCI
12.1
General Functions and Operating Rules
The DCI software is fully parametric.
All the model dependent parameters are shown in Blue color and with Italic style [
parameter
].
The parameters values are given in the last section of this control logic chapter of the service
manual.
12.1.1
System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system
‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the
system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode
avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented by
aparameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it
represents the heat or cool load felt by the indoor unit.
12.1.2
Compressor Frequency Control
12.1.2.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme.
The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOADcalculation,
the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating
Indoor Fan Speed
Maxium NLOAD Cooling
Maxium NLOAD Heating
Low
MaxNLOADIF1C
MaxNLOADIF1H
Medium
MaxNLOADIF2C
MaxNLOADIF2H
High
MaxNLOADIF3C
MaxNLOADIF3H
Turbo
MaxNLOADIF4C
MaxNLOADIF4H
Auto
MaxNLOADIF5C
MaxNLOADIF5H
NLOAD limits as a function of power shedding:
Mode
Power Shedding OFF
Power Shedding ON
Cooling
No limit
Nominal Cooling
Heating
No limit
Nominal heating
12.1.3
Target Frequency Setting
12.1.3.1 Target Frequency Setting for DCI 50 / 60 / 72 Z
The compressor target frequency is a function of the NLOAD number sent from the indoor
controller and the outdoor air temperature.
Basic Target Frequency Setting:
NLOAD
Target Frequency
127
Maximum Frequency
10<NLOAD<127
Interpolated value between minimum and maximum frequency
10
Minimum frequency
0
Compressor is stopped
CONTENTS
Содержание Dci 25
Страница 16: ...4 3 OUTLINE DIMENSIONS SM LEXDCI 1 E 1 GB 4 5 Outdoor Unit DCI 72 Z CONTENTS...
Страница 107: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 4 Outdoor Unit DCI 25 35 CONTENTS...
Страница 109: ...14 6 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 6 Indoor Unit LEX 50 60 72 DCI CONTENTS...
Страница 113: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 10 Outdoor Unit DCI 50 CONTENTS...
Страница 115: ...14 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 12 Outdoor Unit DCI 60 CONTENTS...
Страница 117: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 14 Outdoor Unit DCI 72 Z CONTENTS...
Страница 120: ...16 1 APPENDIX A SM LEXDCI 1 E 1 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...