12-6
CONTROL SYSTEM
SM LEXDCI 1-E.1 GB
12.3 Cool
Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
12.4 Heat
Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
12.4.1 Temperature
Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room temperature
reading (except when in I-Feel mode), to compensate for temperature difference between high and
low areas in the heated room, and for coil heat radiation on room thermistor.
The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit
Controller
Model
J2 Shorted
J2 Opened
Wall mounted
Compensation Disabled
Compensation Enabled
Cassette
Compensation Enabled
Compensation Disabled
Ducted
Compensation Enabled
Compensation Disabled
Floor/Ceiling
Compensation Disabled
Compensation Enabled
12.4.2
Indoor Fan Control in Heating Mode
Indoor fan speed depends on the indoor coil temperature:
12.5
Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (.T). Unit will
switch from cool to heat when compressor is off for 3 minutes, and .T < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and .T < -3.
CONTENTS
Содержание Dci 25
Страница 16: ...4 3 OUTLINE DIMENSIONS SM LEXDCI 1 E 1 GB 4 5 Outdoor Unit DCI 72 Z CONTENTS...
Страница 107: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 4 Outdoor Unit DCI 25 35 CONTENTS...
Страница 109: ...14 6 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 6 Indoor Unit LEX 50 60 72 DCI CONTENTS...
Страница 113: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 10 Outdoor Unit DCI 50 CONTENTS...
Страница 115: ...14 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 12 Outdoor Unit DCI 60 CONTENTS...
Страница 117: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 14 Outdoor Unit DCI 72 Z CONTENTS...
Страница 120: ...16 1 APPENDIX A SM LEXDCI 1 E 1 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...