12.1.5.2 Compressor starting control for DCI 72 / 80
Step 1
Whenever the compressor starts up, after it has been off for more than 45 minutes, the compressor
frequency cannot go below
Step1RPS
for 3 continuous minutes (
this rule comes to ensure oil return
to the compressor
).
Step 2
The compressor speed cannot go above
Step2RPS
once after each compressor start up for 3
continuous minutes (
this rule comes to prevent oil exit from the compressor after its start up)
.
Step 3
The speed cannot go higher than
Step3RPS
unless it was operating for more than 1 continuous
minutes between
Step3RPS
– 5 and
Step3RPS
.
After passing above
Step3RPS
, this rule is re-applied when passing below
Step3RPS
-5.
12.1.6
Minimum On and Off Time
3 minutes
12.1.7
Indoor Fan Control
8 Indoor fan speeds are determined for each model. 4 speeds for cool/dry/fan modes and 4 speeds
for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly
at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
12.1.7.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature > 22 for cooling, or < 25 for heating.
12.1.8
Outdoor Fan Control
12.1.8.1 Outdoor Fan Control for DCI 50 / 60
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3
speeds for heat mode, and a very low speed.
Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT).
4 routines for fan control are determined. The control routine selection depends on operation mode,
compressor speed, outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions
A
Heating with OAT < 15°C
or
Cooling with OAT > 20°C,
or
Faulty OAT
B
Cooling with 20°C > OAT > 7°C
C
Cooling with 7°C > OAT
D
Heating with OAT > 15°C
CONTENTS
Содержание Dci 25
Страница 16: ...4 3 OUTLINE DIMENSIONS SM LEXDCI 1 E 1 GB 4 5 Outdoor Unit DCI 72 Z CONTENTS...
Страница 107: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 4 Outdoor Unit DCI 25 35 CONTENTS...
Страница 109: ...14 6 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 6 Indoor Unit LEX 50 60 72 DCI CONTENTS...
Страница 113: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 10 Outdoor Unit DCI 50 CONTENTS...
Страница 115: ...14 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 12 Outdoor Unit DCI 60 CONTENTS...
Страница 117: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM LEXDCI 1 E 1 GB 14 14 Outdoor Unit DCI 72 Z CONTENTS...
Страница 120: ...16 1 APPENDIX A SM LEXDCI 1 E 1 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...