Page 7
www.elector-water-treatment.com
CLARIMAX 1200 DM pH+ LED – Water-filter-system for treatment of heating-system make-up water
2.2 Scope of delivery
For installation of an CLARIMAX 1200 DM pH+ LED you need the pressure housing (incl. filter cartridge) and
the filter head.
Please check the scope of delivery prior use:
• Pressure housing
• Filter head with integrated measurement device
• Filter cartridge
• Power adapter
Please contact your supplier if parts are missing.
2.3 Assembly of the Pressure housing and the filter head
Place both feet on the floor brackets #4. Lift pressure housing #1 and turn clockwise so that the handles #5
are in one line with the floor brackets. At one handle you can finde a security lock at the side. Press it and turn
the filter head #3 counter-clockwise, lift it to the top to remove it from the housing.
Remove the red transport cap from the filter cartridge #2 and check the o-ring-seals for correct installation,
integrity and cleanliness. Place cartridge #2 in pressure housing #1.
Place both feet on the floor brackets #4. Place filter head #3 in position „INSERT“ at pressure housing #1.
Turn the filter head clockwise until it snaps back to the security lock.
2.4 Assembly of inlet and outlet
Note:
Inlet and outlet hoses are not included in the delivery.
Caution:
The maximum tightening torque at the connections must not exceed 15 Nm! Only connections with flat
gaskets may be used. Conical Connections will damage the connections of the filter head and will lead to the
extinguishing of warranty claims. The direction of flow indicated on the filter head by arrows must be observed.
Operate the system only vertically. Please observe the relevant regulations, such as DIN EN 1717 or DIN 1988.