ELCOS CEM-120 Скачать руководство пользователя страница 2

 ELCOS SRL 

- Parma - CEM-120 – PROG – EN

2

REPLACING THE CONTROL UNIT

TRANSFER OF PROGRAMMING OPERATIONS

MEMORY

Press and

wait for

completion of the

transfer.

Check that the

memory

is inserted

correctly.

    WARNING

 

THE TYPE AND REVISION

 

OF THE TWO CONTROL 

 

UNITS MUST BE THE 

 SAME.

Before replacing the control unit, we advise transferring all the programming settings to the new control 

unit; if this operation is not carried out, the new control unit will operate with the factory programming 

settings. In this case, it is necessary to carry out programming of the current transformer.

  PROCEDURE

 

 

TO BE CARRIED OUT WITH ENGINE STOPPED

 

 

AND CONTROL UNIT NOT POWERED

 

 

       NEW CONTROL UNIT   

 

 

CONTROL UNIT TO BE REPLACED

        

Remove the

memory 

and 

 

    

eliminate it                                                         

       

 

 

 

 

MEMORY

 

 

 

Supply power to the control unit

  

 

 

The following is read on the display

  

     

or

  

     or 

       

        Repeat the procedure

 

It is possible to transfer the programming operations of a standard control unit onto several memories.

We advise you not to exceed fifty transfers.
Example:

 

       CONTROL UNIT 

A

 

          (STANDARD)   

 

CONTROL UNITS 

B - C - D

 TO BE UPDATED

Remove the

memory 

and insert it

in the new control

unit

If, during normal

operation, the

fault is activated

the memory is no 

longer used.

To reset press

A

B

C

D

CONTROL UNIT STAND BY

After 30 seconds of inactivity, the control unit enters STAND BY and completely switches off all the 

notifications (led and display). 

To exit STAND BY, press one of the buttons. 

RESTORATION OF FACTORY PROGRAMMING OPERATIONS OF THE PROGRAMMING OPERATIONS: 

ENGINE, GENERATOR AND PROGRAMMABLE TIMES 

Disconnect the battery power supply to the control unit (we suggest opening the protection fuse).

Supply power to the control unit again, simultaneously press (within 8 sec.) 

the three buttons, wait for the following to be written on the display: 

STANDARD PROGRAMMING.

1. 

Switch off the power to the control units.

2. 

Remove the memory from control unit A.

3. 

Remove the memory from control unit B.

4. 

Insert memory B in control unit A.

5. 

Supply power to control unit A.

6. 

The following message is displayed.

 

“UPDATE THE CONTROL UNIT?”.

7. 

Press the 

STOP

 button.

8.  

The following message is displayed 

 

“SAVE DATA IN MEMORY?”

9. 

Press the 

START

 button.

10.  

The following message is displayed 

 

“END OF  

TRANSFER”.

 

11. 

Switch off the power to control unit A.

12.  

Remove memory B from control unit A.

13. 

 Insert memory B in control unit B.

14.  

Supply power to control unit B. 

15. 

 The following message is displayed 

     

 

“UPDATE THE CONTROL UNIT?”.

16.  

Press the 

START

 button.

17.  

The following message is displayed “END OF  

 TRANSFER”.

18 

Repeat from point 3 for memories C and D.

UPDATE THE 

CONTROL UNIT?

END OF

TRANSFER

ERROR IN 

TRANSFER

MEMORY NOT 

INSTALLED

ERROR 

MEMORY

             

Содержание CEM-120

Страница 1: ...SRL Parma CEM 120 PROG EN 1 COMBINED CONTROL UNIT FOR CONTROLLING AN INDEPENDENT GENERATOR SET AND IRRIGATION MOTOR PUMP TYPE CEM 120 RESERVED FOR THE MANUFACTURER TECHNICAL PROGRAMMING OPERATIONS MA...

Страница 2: ...UNIT STAND BY After 30 seconds of inactivity the control unit enters STAND BY and completely switches off all the notifications led and display To exit STAND BY press one of the buttons RESTORATION OF...

Страница 3: ...rogrammed fuel float Programming of the ohmic values of the pressure transmitter Procedure for switching instruments on and off Procedure for deleting the switching off Programming of ohmic values of...

Страница 4: ...AGE The preset language is Italian the selectable languages are ENGLISH FRENCH GERMAN SPAIN PORTUGUESE SELECT LANGUAGE ENGLISH ENGLISH Press to select the language Press and wait for the system to wri...

Страница 5: ...s the test cycle GENERATOR FREQUENCY Press to choose Press to choose Press to choose Press to choose Press to choose Factory setting Factory setting Factory setting Factory setting Factory setting REA...

Страница 6: ...o stop and message describing the fault or 2 Disabling of control unit protection devices when the input is connected to ground only the following protection devices remain active OVERSPEED OVERFREQUE...

Страница 7: ...n needs to be carried out but if it is necessary to carry it out stop the engine Run the engine at a costant and known rpm value for example by means of a portable revolution counter Run the engine at...

Страница 8: ...er reaches the programmed value Notification number 4 is cyclic and triggers after the programmed hours and whole multiples of them The request for maintenance is indicated by the flashing of the hour...

Страница 9: ...tinuous operation WEEKLY SELF TEST DURATION When the test time expires the engine stops 1 to 60 minutes 3 minutes INSUFFICIENT INTERVENTION TIME OR PUMP WATER OVERPRESSURE after the increase or loweri...

Страница 10: ...h no time limits INSUFFICIENT INTERVENTION TIME OF PUMP WATER OR PUMP WATER OVERPRESSURE After the increase or lowering of pump water pressure and when this time has expired the stopping process begin...

Страница 11: ...switch no programming is possible 133 FAILURE TO STOP AFTER STOP CON TROL 60 YES See description on page 5 of the user instruction manual no programming is possible 135 LOW LEVEL IN RADIATOR ALWAYS AC...

Страница 12: ...he connections of the mains phases are incorrect The generator contactor is not closed no programming is possible 231 G S ASYMME TRY OUT OF RANGE 5 to 20 15 1 to 600 15 YES YES STOPS The percentage di...

Страница 13: ...next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press and wait for the system to write PROGRAMMED THIS IS DISPLAYED ON THE DISPLAY THIS IS DISPLAYED...

Страница 14: ...AGE PRESENT G S UNDERFREQUENCY G S OVERFREQUENCY G S OVERVOLTAGE Press when the arrow is next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press when th...

Страница 15: ...urrent triggers the intervention at 100A but only when the current transformer withstands this current PUMP PROGRAMMING G S OVERLOAD WARNING DIFFERENTIAL OVERPRESSURE G S OVERLOAD G S DOES NOT SUPPLY...

Страница 16: ...24 140 156 170 Press to display choice of pressure transmitters Press and wait for the system to write PROGRAMMED PROGRAMMABLE PRESSURE TRANSMITTER Press and wait for the system to write PROGRAMMED PR...

Страница 17: ...E VALUES OHM TEMPERATURE TRANSMITTERS PRESSURE TRANSMITTERS Decreases Increases Decreases Increases By factory default the control unit is set for pressure and temperature transmitters TYPE TPO 403 Pr...

Страница 18: ...rol unit is programmed for a float with rheostat suitable for FUEL LEVEL indication MANAGEMENT OF FUEL W It is possible to program the use of a float with contact that closes to ground when there is n...

Страница 19: ...ction GENERAL ALARM switching off is possible when this intervenes to warn of an imminent automatic start up except for a call start up It cannot be switched off when the intervention is caused by a f...

Страница 20: ...rds control units can be addressed SERIAL PORT RS232 MOD BUS GSM MODEM Select GSM 9600 bps to activate the connection with the telephone number to be notified when the G S is in alarm condition Press...

Отзывы: