GENERATOR PROGRAMMING
GENERATOR UNDERVOLTAGE.
The protection device is activated when the generator voltage steadily stays higher than the
programmed value for 10 seconds. The preset threshold is 335V with intervention delay of 3 seconds.
GENERATOR VOLTAGE PRESENT.
The generator contactor closes when the voltage steadily
remains above the programmed threshold for the entire generator connection to power user delay time.
GENERATOR UNDERFREQUENCY.
By factory default, the protection device is switched off. To activate it, you must program an intervention frequency
different from 0 Hz. The protection device is activated when the generator frequency steadily stays higher than the
programmed value for 10 seconds.
GENERATOR OVERFREQUENCY.
The factory set threshold is 60 Hz, suitable for 50 Hz systems. In the event of
OVERFREQUENCY, the engine is stopped. The stop is not programmable.
GENERATOR OVERVOLTAGE.
It is factory programmed to stop.
G.S.
UNDERVOLTAGE
G.S. VOLTAGE
PRESENT
G.S.
UNDERFREQUENCY
G.S.
OVERFREQUENCY
G.S.
OVERVOLTAGE
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press and wait for
the system to write
PROGRAMMED.
Delay
in intervention
Delay
for connection
Delay
in intervention
Delay
in intervention
Delay
in intervention
Stop
of engine
Stop
of engine
Stop
of engine
Without stop
STOP
Without stop
STOP
Without stop
STOP
Without stop
STOP
With stop
NO STOP
With stop
NO STOP
With stop
NO STOP
With stop
NO STOP
Threshold
Threshold
Threshold
Threshold
Threshold
355 V
7 s
45 Hz
5 s STOP
60 Hz
2 s
440 V
3 s STOP
355 V
7 s
335 V
3 s STOP
335 V
3 s STOP
45 Hz
5 s STOP
60 Hz
2 s STOP
440 V
3 s STOP
Press to
display.
Press to
display.
Press and wait for
the system to write
PROGRAMMED.
Press to
display.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press to
display.
Press and wait for
the system to write
PROGRAMMED.
Press to
display.