11/2010 - Art. Nr. 4200 1029 8600A
10
Operation
Pump
The pump is a gear pump. It must be
connected as a two-line pump via a
bleed filter. For the connection of the fuel
oil tank and the bleed filter, it is better to
use the single line option
.
An intake filter
and two oil pressure regulators are
integrated in the pump. Pressure
gauges for pressure measurements
4
and negative pressure measurements
5
must be connected before the
equipment is commissioned.
1
Return connection
G 1/4
2
Vacuum connection
G 1/4
3
Nozzle supply line
connection
G1/8
4
Pressure gauge connection
5
Vacuum gauge connection
8
Pressure setting, 1st stage
9
Pressure setting, 2nd stage
Y1
Solenoid valve, 1st stage
Y5
Solenoid valve, 2nd stage
Содержание VL 2.120 D
Страница 26: ...11 2010 Art Nr 4200 1029 8600A 26...
Страница 27: ...11 2010 Art Nr 4200 1029 8600A 27...