06/2014 - Art. Nr. 4200 1057 7400
58
Initial start-up
Configuration data
Air adjustment
Low Flame air adjustment (A).
Intervene on screw A in the picture:
• turning it anti-clockwise increases
the flow rate;
• turning it clockwise decreases
the flow rate.
High Flame air adjustment (B).
Intervene on screw B in the picture:
• turning it anti-clockwise increases
the flow rate;
• turning it anti-clockwise decreases
the flow rate.
The above adjustments are
basic
adjustments
. With these settings,
normally, the burner can be started up.
The adjustment must then be verified
using a combustion analyser.
It may be necessary to perform
corrections subject to the single plant.
Favourable combustion values can be
obtained by using the following nozzles:
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Adjusting the combustion head (B).
Intervene on the screw shown in the
picture:
• turn it using a hex spanner until it
reaches the desired value
(index from 0 to 5).
+
-
0
1
2
3
4
B
+
-
A
B
A
Burner
Burner power
kW
Fuel-oil flow
kg/h
Nozzle
60°W
Gph (Danfoss)
Pump pressure
bar
Firing head setting
mm
Air flap position
1. stage 2. stage 1. stage 2. stage
1. stage
2. stage 1. stage
2. stage
1. stage 2. stage
P2.190 L-Z
(SV)
84
111
7.1
9.3
1.75
0
11
20
0
1.8
2.5
106
140
8.9
11.8
2.25
0
11
20
1.5
2
4
122
160
10.2
13.5
2.50
0
11
20
2.5
2.2
5
P2.300 L-Z
(SV)
101
152
8.5
12.9
2.25
2,25+1,10
10
10
0
1.6
2.5
122
199
10.2
16.8
2.50
2,50+1,50
12
12
0
1.8
4
239
239
20.2
20.2
2.75
2,75+2,00
12
12
5
2
5
Bold : Delivery setting; 1kg fuel-oil at 10°C = 11.86kWh