INSTRUCTION MANUAL

 

IM425-U v3.1 

 

 

ELM-96 

MULTIFUNCTION VOLT/AMMETER

 

 

 

GENERAL

 

The digital Multifunction Volt/Ammeter series ELM-96 allow monitoring the 
main electrical parameters present on a distribution line. The local display of 
the electrical parameters is being made through 3 display with red LED, 
which grant a good and simultaneous reading of various measures. The 
intuitive selection of the measures to visualise, which are signalled by their 
corresponding LED, completes a clear and simple front panel, which offer a 
lot of useful information. 
On top of the instantaneous measuring, these instruments visualise the 
maximum peak of the main parameters (maximum peak and maximum 
demand or maximum average value). 
Multifunction Volt/Ammeter series ELM-96 replace, in an unique device, all 
the functions of voltmeters, ammeters and frequency meters, permitting a 
great economic saving, due to reducing of dimension and wiring, so as 
optimising the instruments management, since one has most of all in one, for 
electrical boards, switch-boards and Gen-Sets. 

 

AVAILABLE MODELS

 

ELM-96  

 

ACCESSORI ED OPZIONI

 

accessories

: transparent cover for frontal protection. 

 

options

C1     

auxiliary power supply 230 V 

C2 

auxiliary power supply 115 V 

1A 

current inputs for CT ../1Amp. 

current inputs with galvanic insulation 

(not for direct connection line insertion) 

n.2 digital output alarm signal (Photomos ca/cc). 

 

INTRODUCTION

 

The ELM-96 models are only featured for visualising the electrical parameters. The power supply is taken from the 
measured voltage or self-supplied. 

 

MESURED PARAMETERS

 

Parameters

 

Measuring units

 

Identification Symbols

 

Phase and three phase voltage

 

[V-kV]

 

L1-N 

L2-N 

L3-N 

Σ

 

L-N

 

Phase to phase and three phase system voltages

 

[V-kV]

 

L1-L2 

L2-L3 

L3-L1 

Σ

 

L-L

 

Phase and three phase currents

 

[A-kA]

 

L1 

L2 

L3 

Σ

 

I

 

Frequency

 

[Hz]

 

Hz 

L1

 

Hour meter

 

[hr]

 

hr1 hr2  hr3

 

 

STORED PARAMETERS

 

Instantaneous Values:

 

Maximum phase voltage

 

[V-kV]

 

L1-N max 

L2-N max 

L3-N max

 

Minimum phase voltage

 

[V-kV]

 

L1-N min 

L2-N min 

L3-N min

 

Maximum phase to phase voltage

 

[V-kV]

 

L1-L2 max 

L2-L3 max 

L3-L1 max

 

Maximum phase current

 

[A-kA]

 

L1 max 

L2 max 

L3 max

 

Measured value in 15’

 

 

Average phase current (maximum demand)

 

[A-kA]

 

L1 max (avg) 

L2 max (avg) 

L3 max (avg)

 

checks

 

 

Check phase rotation

 

ELM-96 

instruction manual

IM425-U v3.1 

pag. 1

 

Содержание ELM-96

Страница 1: ...DELS ELM 96 ACCESSORI ED OPZIONI accessories transparent cover for frontal protection options C1 auxiliary power supply 230 V C2 auxiliary power supply 115 V 1A current inputs for CT 1Amp T current in...

Страница 2: ...se to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phas...

Страница 3: ...ith 3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 3 P1 L1 S1 L2 S1 L3 P1 N S1 S2 P1 P2 LOAD ELM INSERTION ON THRE...

Страница 4: ...ERTION ON THREE PHASE LINE WITH 2 CT insertion AARON L1 S1 P1 L2 L3 N S1 S2 P1 P2 LOAD ELM VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES WITH 2 VT This insertion is possible only with the interna...

Страница 5: ...3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 5 L1 L2 L3 S1 S2 P1 P2 LOAD ELM INSERTION ON SINGLE PHASE LINE Only...

Страница 6: ...lise on display E C LED s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter reading k kilo x1000 D LED for indicating the visualisation of the me...

Страница 7: ...Decrease Confirm and end of general settings Programming of the transformation rate of the external CT s The programming of the CT s rate considered as the rate between primary and secondary example w...

Страница 8: ...With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronism type In this setting for the synchronization type it...

Страница 9: ...e ALR Dl Decrease ENTER IN THE SETUP Confirm and end of digital output settings Fromthemeasuresvisualization presstheAkeyforatleast5seconds themessageSeT Up willappearontheEdisplays CHOOSE THE DIGITAL...

Страница 10: ...delay Functioning for exceeding the maximum threshold With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is ena...

Страница 11: ...s SELECT THE PARAMETER TO LINK TO THE HOURS COUNTER From the previous setting pressing the B key it s possible to set the hours counter the message SET HR_ appears on the E display Press the A key to...

Страница 12: ...urrent LED Hz ON on L3 display is showed the frequency measured on L3 phase on L1 display will appear the message PHASE ROTATION with a bright dash that rotate clockwise to indicate that the phase rot...

Страница 13: ...LED L on VL N k VL L k A k VL N VL L In balanced three phase system mode BALANC are available only the visualization 7 and 8 In single phase mode PH L3 the pages displayed are the following ELM 96 ins...

Страница 14: ...key are as follows Parameter Display Signalling LED VL N maximum instantaneous PEA HI VL N VL N minimum instantaneous Pea LO VL N VL L maximum instantaneous PEA HI VL L I phase maximum instantaneous P...

Страница 15: ...oad 20 impedance at the input 1 M Three phase wiring with 3 or 4 wires and single phase wiring MV connection through external VT with programmable transformation ratio from 1 to 400 Current inputs Fro...

Страница 16: ...panel 96 96 90 92 ELM 96 R3 avg 92 20 For other applications please contact with ELCO technical assistance department Via Lago di Molveno 20 36015 Schio VI Tel 39 0445 661722 Fax 39 0445 661792 http...

Отзывы: