background image

- Programming of the transformation ratio of the external voltage transformers

 

After the precedent programming phase, on 

display will appear the inscription VT  (voltage transformer) and the value 

of the transformation rate of the external TV (set to 1 from the constructor), considered as the rate between primary and 
secondary (example with TV 15/0.1 kV the value will be 150). 
In the same way at the programming of the CT rate will be possible to set this value. If the external TV are not used the 
value to set will be 1. To confirm the value press the 

button. 

 

Programming of the average time (

seT AVG  T’

)

 

After the programming phase previously described, pressing another time the 

key, on the 

display will appear the 

message AVG  T’ and the average time settable from 1 to 30 minutes. To increase the value press the 

key. To 

decrease it, press the 

and 

keys together (from the condition of 

pressed). To confirm it press the 

key. 

The average time is the time used to calculate the average parameters (

avg

) and the maximum demand (

maxD

). 

 

Programming insertion mode

 

It’s possible to set the following mode of insertion: UN_BAL in a unbalanced three-phase system (default), BALANC in 
a balance three phase system and 1PH   L3 in a single phase insertion. 
In the 1PH  mode are displayed only the measures of l3 phase and the relative hour counter; the status of phase rotation 
is not displayed. 
In the BALANC the current and the power factor of the L3 phase are used for the calculation of L1 and L2 measures. 

 

Programming wiring connection mode

 

This setting allows to definite the wiring type connection. It’s possible to chose 3 wires or 4 wires. With the 4 wires 
connection the neutral parameter are displayed and enabled to use for the digital outputs settings. 

 

Programming of the synchronism type

 

In this setting for the synchronization type, it’s possible to choose L3 to use the external frequency (on L3 phase) or 50, 
60 Hz to use the internal clock. 

 

Activating or cancelling the automatic scrolling

 

This allows selecting ON for activating or OFF for cancelling the automatic scrolling of the measures visualisation. 

 

Programming of the Password

 

The instrument is supplied without password. When a password (from 0002 to 9999) is set, using the 

(to increase), 

(to decrease) and 

(to confirm) keys, only who know this value can to enter in the setup. The password, in fact, is 

required all the time that someone try to enter in the setup (pressing the 

key at least 5 seconds). If the password is 

wrong, the message PASS  ERR will appear on 

display and the instrument go back to the measures visualization. To 

input the password, when required by the instrument, at the enter of the setup, use the 

A

and 

keys as the same way 

done previously. 

 

PEAK VALUES AND ENERGY COUNTERS RESET (

RESET

)

 

Enter in setup mode, press the 

key up to show the message ReseT on the 

display, press the 

key, on the display 

will appear RES  ALL  NO, press the 

key another time, the message commute in RES  ALL  yes, confirming with 

the 

key all stored data will be deleted. Automatically the instrument come back to the measure visualization. 

 

ELM-96 

instruction manual

IM425-U v3.1 

pag. 8

 

Entry to menu: 

seT  UP  

Æ

 

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   HR_ 
--- OFF   OFF  

(the visualization depends on the settings and the I/O status) 

 

To enable the chosen type, press the 

key to change the indication on display 

from NO  to yes. Confirm enabling 

cancellation, by pressing the 

key. The indication on 

display change from yes to  ---  . 

Содержание ELM-96

Страница 1: ...DELS ELM 96 ACCESSORI ED OPZIONI accessories transparent cover for frontal protection options C1 auxiliary power supply 230 V C2 auxiliary power supply 115 V 1A current inputs for CT 1Amp T current in...

Страница 2: ...se to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phas...

Страница 3: ...ith 3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 3 P1 L1 S1 L2 S1 L3 P1 N S1 S2 P1 P2 LOAD ELM INSERTION ON THRE...

Страница 4: ...ERTION ON THREE PHASE LINE WITH 2 CT insertion AARON L1 S1 P1 L2 L3 N S1 S2 P1 P2 LOAD ELM VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES WITH 2 VT This insertion is possible only with the interna...

Страница 5: ...3 wires without neutral or with neutral not supplied the N terminal must not be connected ELM 96 instruction manual IM425 U v3 1 pag 5 L1 L2 L3 S1 S2 P1 P2 LOAD ELM INSERTION ON SINGLE PHASE LINE Only...

Страница 6: ...lise on display E C LED s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter reading k kilo x1000 D LED for indicating the visualisation of the me...

Страница 7: ...Decrease Confirm and end of general settings Programming of the transformation rate of the external CT s The programming of the CT s rate considered as the rate between primary and secondary example w...

Страница 8: ...With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronism type In this setting for the synchronization type it...

Страница 9: ...e ALR Dl Decrease ENTER IN THE SETUP Confirm and end of digital output settings Fromthemeasuresvisualization presstheAkeyforatleast5seconds themessageSeT Up willappearontheEdisplays CHOOSE THE DIGITAL...

Страница 10: ...delay Functioning for exceeding the maximum threshold With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is ena...

Страница 11: ...s SELECT THE PARAMETER TO LINK TO THE HOURS COUNTER From the previous setting pressing the B key it s possible to set the hours counter the message SET HR_ appears on the E display Press the A key to...

Страница 12: ...urrent LED Hz ON on L3 display is showed the frequency measured on L3 phase on L1 display will appear the message PHASE ROTATION with a bright dash that rotate clockwise to indicate that the phase rot...

Страница 13: ...LED L on VL N k VL L k A k VL N VL L In balanced three phase system mode BALANC are available only the visualization 7 and 8 In single phase mode PH L3 the pages displayed are the following ELM 96 ins...

Страница 14: ...key are as follows Parameter Display Signalling LED VL N maximum instantaneous PEA HI VL N VL N minimum instantaneous Pea LO VL N VL L maximum instantaneous PEA HI VL L I phase maximum instantaneous P...

Страница 15: ...oad 20 impedance at the input 1 M Three phase wiring with 3 or 4 wires and single phase wiring MV connection through external VT with programmable transformation ratio from 1 to 400 Current inputs Fro...

Страница 16: ...panel 96 96 90 92 ELM 96 R3 avg 92 20 For other applications please contact with ELCO technical assistance department Via Lago di Molveno 20 36015 Schio VI Tel 39 0445 661722 Fax 39 0445 661792 http...

Отзывы: