System configurations
Electric connection
Remote Interface Modul
The module has five digital inputs with
optocouplers and an isolated BMS
Modbus RTU port with variable baud
rate.
The dip switch bank S1 is used to
inform the MCU of the configuration
parameters: BMS port baud rate, unit
type, pump type, remote control acti-
vation, HMI Modbus port activation.
Termination of the BMS modbus port
is available on dip switch bank S2.
Power supply for the unit is 7 to 17 V
ac/dc.
Digital inputs for potential-free
contacts:
a.
On/Off
b.
Heat/cool mode
c.
Domestic hot water
d.
Double set-point;
e.
Silent mode
Auto Modbus address acquisition
(shake hands function) from HMI;
HMI and BMS Modbus ports are
equipped with status LED for Rx Tx
visual monitoring.
Wide range AC/DC power supply in-
put compliance (From 7~17Vac/Vdc).
Port Definition
HMI side:
CN1: A, B
power supply 7-17Vac/dc
CN2: E, E
HMI side GND connection
CN3: HMI Modbus RTU
port H2, H1 (H2 = +, H1 = -)
User side:
CN4: SA 4 ON/OFF
Voltage free digital input
CN5: SA 5 C/H
Voltage free digital input
CN6: SA 6 DHW
Voltage free digital input
CN7: SA 7 D-P-S
Voltage free digital input
CN8: SA 8 Silent
Voltage free digital input
CN9: BMS port
Modbus RTU over RS485 (H2 +, H1 -)
CN10: E’E’
floating GND connection (customer
side)
Status LED of the digital input
Contact closed: LED on, contact
open: LED off
Third party Modbus or BMS isolat-
ed communication interface
(communication speed selectable:
from 1200bps to 115200bps) Parity
NONE, word length 8, Stop Bit 1;1