Technical data
Electrical data
Supply voltage 400/3/50+N
AEROTOP L
54
61
65
79
88
F.L.A. - Full load current at max admissible conditions
F.L.A. - Total
A
38,5
38,5
59,7
59,7
59,7
F.L.I. - Full load power input at max admissible conditions
F.L.I. - Total
kW
25,6
25,6
40,1
40,1
40,1
M.I.C. - Maximum inrush current
M.I.C. - Total
A
46,0
46,0
60,2
60,2
60,2
Power supply 400/3/50 (+ NEUTRAL) +/- 10%. Maximum Phase Unbalance: 2%.
For non standard voltage please contact ELCO technical office
Wiring cross sections and fuse protection
AEROTOP L
Remote ON - OFF
External power supply
Power supply
Switch manual
fuses
Wiring
(Lmax = 20 mt)
54 - 61
380-415V 3N~ 50Hz
100A
63A
25mm
2
X 5
65 - 88
380-415V 3N~ 50Hz
100A
80A
25mm
2
X 5
Deviating connection lengths and electrical fuses must be calculated according to the country-specific regulations.
EVU-Lock
Special tariffs with reduced electricity
prices are available from many energy
supply companies (EVU) for the oper-
ation of heat pumps. In return, the
utility company is allowed to shut
down the heat pump at certain times
and the building cannot be reheated
by the heat pump for this period. Cov-
erage is then usually provided by a
buffer storage tank. In solidly built
houses, especially in connection with
underfloor heating, blocking periods
can be bridged by the storage mass.
A buffer tank or second heat genera-
tor is then not required. If a second
heat generator (bivalent parallel oper-
ation) is available, the blocking time
can be neglected for the dimensioning
of the heat pump.
There are some country-specific
differences for blocking periods:
Tariffs in Germany are regulated ac-
cording to the Federal Tariff Ordi-
nance (Federal tariff regulation heat
pumps) on Heat Pumps. Shutdown
can occur up to 3 times per day for
two hours each. Shutdown can be
time-controlled, demand-controlled
(balancing of load peaks) or not at all.
A distinction is made between hard
and soft shutdown. In the case of hard
shutdown, the main power supply
(compressor current) is interrupted.
Alternatively, many utilities offer shut-
down via a ripple control signal. Addi-
tional electric heating inserts mounted
outside the heat pump (e.g. in the
storage tank) may continue to be op-
erated up to a maximum output of
2kW.
In practice, the following surcharge factors have proven effective, since never all
rooms are heated and the standard outside temperature is rarely reached.
Sum of blocking times per day [h]
Factor for additional heating power
2
1,05
4
1,1
6
1,15