5.2.2 Device
A disabled device generates no alarm or fault events and never activates, but it keeps sending
its analogue value during the polling (the cyclical interrogation of all addresses made by the
loop board). Key in a loop number (as in
5.1.3.2
) and press ENT to display the list of that loop’s
devices. Disable/enable them as with zones.
Disabling every device of a zone also disables the zone itself. If such a
Z
one
(
chap
. 5.2.1)
is
enabled again, all of its devices get automatically enabled.
L1A001 EN
>L1A002 DIS
L1A003 EN
ESC -> <- ENT
5.2.3 Unit outputs
The relay 2 and bell output A, B and C can be disabled.
A disabled unit output never activates and stops being supervised.
To enable or disable an output, use -> and <- to select it and press ENT.
RELAY 2 ON
>BELL A ON
BELL B ON
ESC -> <- ENT
5.2.4 Delayed mode
This function enables/disables the
D
elayeD
moDe
(
chap
. 4.1.3)
, making it operative for each zone
enabled from the programming menu.
Press ENT to switch to editing mode and use -> or <- to toggle the mode On and Off.
Delayed Mode
Status: OFF
ESC -> Ed <- ENT
If the delayed mode is enabled (“Status: ON”), the new Short Time line appears.
Press ENT again to edit this new line, where the new option can be turned On or Off.
Delayed Mode
Status: ON
Short Time: OFF
ESC -> Ed <- ENT
5.3 Display
5.3.1 Messages cleared
The existing standards mandate absolute priority for alarm messages, included hiding all other messages while alarm
messages are present. This function lets you look at the hidden messages.
A new alarm message, idling for 20 seconds or pressing ENT will bring back the alarm messages.
Alarm and fault messages are detailed in
u
nit
scReens
system
messages
(
chap
. 4.3).
5.3.2 Events filter
5.3.2.1 Date
The
e
vents
(
chap
. 5.3.3)
function will only display the saved events whose date falls in the range
set through this editing page.
The default range is from 1st January 2000 to 31st December 2099.
EVENTS
from 01-01-00
to 31-12-99
ESC -> Ed <- ENT
5.3.2.2 Class
The
e
vents
(
chap
. 5.3.3)
function will only display the saved events whose class is set to On in
this editing page.
The
s
ystem
events
table
(
chap
. 7)
details the system event classes.
ALARM YES
>FAULT NO
SYSTEM YES
ESC -> <- ENT
5.3.2.3 Origin
The
e
vents
(
chap
. 5.3.3)
function will only display the saved events whose origin is set to On
in this editing page.
The
s
ystem
events
table
(
chap
. 7)
details the system event origins.
DEVICE YES
>UNIT NO
LOOP YES
PERIPHERAL YES