5. USER MENU

The Program entry allows access to the programming menu, protected by a L3 password.

Press ESC to exit the password request screen.

5.1 Test

The Test LED will glow while the functions of this menu are active.

5.1.1 LED

Once  in  this  function,  press  ENT  again  to  start  the  test:  every  LED  in  the  Unit  group  and 

Selected unit areas will light up for some seconds, except red alarm LEDs.

To test red alarm LEDs, test bell output D (chap. 5.1.3.1).

To test the 8 LED columns, simulate an alarm or a fault on the corresponding unit.

      Lamp Test

Terminal ON Sequence

 

5.1.2 LCD

All LCD cells get filled with a same character.

Every second, the next character in the set is shown, in rotation.

Press ESC (the first function button on the left) to go back to the menu.

00000000000000000000
00000000000000000000
00000000000000000000
00000000000000000000

5.1.3 Outputs

5.1.3.1 Unit outputs

This  function  lets  you  select  a  unit  output  using  the  ->  and  <-  buttons,  pressing  ENT  to 

manually activate or deactivate it. Activating bell output D lets you test the backup alarm 

propagation line and the red alarm LEDs in the front panel (chap. 5.1.1).

Remember that the outputs might disturb the peace.

Press ESC to quit this function, deactivating (OFF) any output that had been activated manually.

 RELAY 2          OFF
>BELL A           ON
 BELL B          OFF
 ESC  ->    <-  ENT

5.1.3.2 Loop outputs

This function works like the previous one, but you need to choose a loop first (type the 

corresponding digit and press ENT to confirm).

The “Invalid value” message pops up if the loop has no outputs.

The “Not Saved” message pops up if the typed number doesn’t match an existing loop.

It is possible to type a new digit and press ENT even while the messages are active.

 L1A001           ON
>L1A005          OFF
 L1A012           ON
 ESC  ->    <-  ENT

5.2 Disablement

The functions in this menu enable (EN) or disable (DIS) entire zones, single devices or unit outputs. Their default value is 

ENabled; when they get DISabled, the General disable LED and the appropriate disable LEDs light up.

This menu also contains the function to activate/deactivate the delayed mode, which is deactivated by default.

5.2.1 Zone

Devices from a disabled zone can’t generate or receive alarm or fault signals.

Chose the zone to enable/disable using -> and <-.

Press ENT to start editing mode, use -> and <- to decide if the zone has to be enabled or 

disabled, then press ENT again to save and quit editing mode.

 ZONE1            EN
>ZONE2           DIS
 ZONE3            EN
 ESC  ->    <-  ENT

 ¤   

Содержание 090010932

Страница 1: ...FXUP FXPRO expansion unit with integrated power supply unit 090010932 USER MANUAL Declaration of performance nº 0051 CPR 0455 15 Standards EN54 2 2007 EN54 4 2007 ...

Страница 2: ... and people we invite the user to proportion the level of protection that the system offers to the actual risk also taking into account the possibility that the system was operated in a degraded manner because of faults and the like as well reminding that there are precise laws for the design and assemblage of the systems destined to these kind of applications The system s operator is hereby advis...

Страница 3: ...DERS Glowing A user has issued a temporary sounders silencing request SILENCE BUZZER Glowing A user has issued a temporary buzzer silencing request DELAYED MODE Glowing Delayed mode is ON TEST Glowing Test mode is ON MAINS green Glowing Mains supply is working DISABLE COMMON Glowing At least one element has been disabled DISABLE DEVICES Glowing At least one device has been disabled DISABLE OUTPUTS...

Страница 4: ...ibed in the programming manual for unit menus 3 3 Screen structure and function buttons meaning Emulated and panel screens are structured as in the example on the right three lines of text with instructions or informations a fourth line reminds what the 4 function buttons in the first row of the keypad mean The more used meaning are ESC to go back to the previous menu or page and to select the fol...

Страница 5: ... in the programming menus 4 1 2 Zones The applicable standards have the devices on a loop divided in zones geographical partitions of the monitored environment If a fault happens in a zone it is possible to disable it from the Disablement Zone chap 5 2 1 menu and after identifying the faulty device thanks to its address proceed with the maintenance operations 4 1 3 Delayed mode The contents of thi...

Страница 6: ...ent Some specific system events can be used to activate outputs e g by default the Fire event activates all bell outputs the relay 2 output and every output of the loop 4 2 Main screen When no system messages are shown the main screen of the unit shows the date and time the 5 digit ID used by GLOBALPRO to identify the unit and the other data shown on the right The star in the third row is only sho...

Страница 7: ...uate procedure Get to the unit s main screen ENT n n n n L2 PASSWORD To go back to the welcome screen of the panel press Selected unit 0 4 6 Unit screens user menu The following chapter illustrates the user menu entries mapped here Program User menu Disablement Zone Device Unit outputs Delayed mode Display Messages cleared Print Address Type Events filter Events filter Date Class Origin Device Out...

Страница 8: ...line and the red alarm LEDs in the front panel chap 5 1 1 Remember that the outputs might disturb the peace Press ESC to quit this function deactivating OFF any output that had been activated manually RELAY 2 OFF BELL A ON BELL B OFF ESC ENT 5 1 3 2 Loop outputs This function works like the previous one but you need to choose a loop first type the corresponding digit and press ENT to confirm The I...

Страница 9: ...nabled Status ON the new Short Time line appears Press ENT again to edit this new line where the new option can be turned On or Off Delayed Mode Status ON Short Time OFF ESC Ed ENT 5 3 Display 5 3 1 Messages cleared The existing standards mandate absolute priority for alarm messages included hiding all other messages while alarm messages are present This function lets you look at the hidden messag...

Страница 10: ... to display a list of every output device on that loop each one showing if it s been MANually or AUTOmatically activated If the loop has no output devices the No output on message appears MANually activated outputs are those activated using the Outputs activation chap 5 5 menu AUTOmatically activated ones are activated by the unit L1 A001 MAN L1 A002 AUTO L1 A003 AUTO ESC If an output has been AUT...

Страница 11: ...ctivate or deactivate output modules Key in the loop number and press ENT a list of all output modules appears with the rightmost column reading On if the output is active because of a manual activation Off it is deactivated or automatically active To activate deactivate an output use and to select it and press ENT L1A001 OFF L1A002 ON L1A003 OFF ESC ENT If the output is already active because of ...

Страница 12: ... EV H CS EV UV Heath Sensor 1 ST NCP AS2B ST NCP EN2 ST NCP IP EV MCP Call Point 1 EV PH Optical Smoke Sensor Heat Sensor 2 EV AIN1 Detector 1 EV AIO21 Dip switch set to 1 Detector 1 Dip switch set to 7 Output Module 2 Input Modules 3 Dip switch set to 9 10 or 12 Output Module 1 Dip switch set to 13 or 15 Output Module Input Module 2 EV AIN2 Dip switch set to 1 4 or 7 Detector 1 Dip switch set to ...

Страница 13: ... Fault Loop Panel Fault Password access System Panel Open pos loop Fault Loop Fault Delayed mode en System Panel Open neg loop Fault Loop Fault Delayed mode dis System Panel Short A loop Fault Loop Fault Temp silence System Panel Short B loop Fault Loop Fault Buzzer silence System Panel Short not detect Fault Loop Fault Panel reset System Panel Comm error Fault Device Loop Fault PC connect System ...

Страница 14: ...OOKLET Copy according to your needs File in two copies one for the installer and one for archive Installing company Address Telephone number Installer engineer Telephone number Installation date Action Date time Identified failure Remedial action taken Time used Signature ...

Страница 15: ...azione Sicurezza Parte 1 Requisiti generali Information technology equipment Safety Part 1 General requirements EN 54 2 1997 A1 2006 Sistemi di rilevazione e di segnalazione d incendio centr Di controllo e segn Fire detection and fire alarm system control and indicating equipment EN 54 4 1997 A1 2002 A2 2006 Sistemi di rilevazione e di segnalazione d incendio app di alimentazione Fire detection an...

Страница 16: ...0 35011 Campodarsego PD Italy Tel 390499203333 Fax 390499200306 Technical Ass 390499200426 www elmospa com info elmospa com 11 DATA SET BY THE INSTALLER Delayed mode Start time End time List of devices not influenced by delayed mode MO TU WE TH FR SA SU Acknowledgement time __________ Inspection time __________ Reduced Short time __________ Daylight savings time end D M ____ _____ Daylight savings...

Отзывы: