SURFACE MOUNT LEDFIRE III EMERGENCY INSTALLATION INSTRUCTIONS

DRAFT

2. overvieW

Ektor Generation III platform introduces you to a new era of emergency lighting control. With years in the 

making, the third generation platform builds on the Ektor product ranges’ increasing quality, reliability and 

performance. In choosing this Ektor product you can be comfortable that you have the best. 

Out of the box this product can be wired in any of these configurations:

•   Self-testing  unit
•  Standalone unit
•   Standalone unit controlled with a switch or sensor
•   DALI controlled remote testing unit

And can be used with a central battery system (monitored and non-monitored)

An optional wireless module can be added to allow you to connect to standard Wi-Fi networks for remote 
testing and reporting.

Our Ektor Generation III platform also brings class leading technology which increases performance and 
reliability including:

•   Smart battery charging technology which reduces power consumption up to 90% while 

 

increasing the service life of the battery

•   Smart battery conditioning to ensure the best performance from the battery
•   450V Electrolytic capacitors which increase the products reliability
•   Highly efficient design to reduce fatigue on the product

For buildings requiring longer durations such as 3, 4 and 8 hours the installer can change the jumpers found 
on the unit for automatic scaling of the output. Moreover should you require non-maintained or maintained
output, the installer can select this on installation.

2

3. safety Warnings

1. tHis ProDUct mUst only Be installeD By a licenseD electrician.
2. Before commencing installation tUrn off anD isolate tHe electrical sUPPly.
3. Do not energise WitH ProDUct oPen or DisassemBleD.
4. sUPPly voltages WitHin ProDUct. isolate sUPPly voltages Before oPening or servicing.
5. tHe only User serviceaBle Part is tHe Battery PacK.
6. Do not attemPt to service otHer Parts of tHe fitting as tHis Will voiD tHe Warranty.
7. as tHe installer, it is yoUr resPonsiBility to ensUre yoU comPly to all relevant BUilDing anD safety 
    coDes for eXamPle tHe Bca, as3000. refer to aPPlication stanDarDs for tHe relevant rUles.

8. WHEN tHE INStALLAtION IS COMPLEtE, LEAVE tHIS MANUAL WItH tHE BUILDING’S OWNER/S FOR FUtURE REFERENCE.

Содержание EV-LEDFIRE-III-SM

Страница 1: ...V LEDFIRE III SM 1690 EV LEDFIRE III SM B 1 Welcome Overview Safety warnings Installation Mounting options Terminal block wiring Maintaining your SM Ledfire III luminaire Replacing the battery Battery life Power and battery charge Wireless daughterboard Self test standard wiring central battery system DALI wiring central battery system Using the inverter with a switch Using the inverter with a sen...

Страница 2: ...of the battery Smart battery conditioning to ensure the best performance from the battery 450V Electrolytic capacitors which increase the products reliability Highly efficient design to reduce fatigue on the product For buildings requiring longer durations such as 3 4 and 8 hours the installer can change the jumpers found on the unit for automatic scaling of the output Moreover should you require ...

Страница 3: ...roduct is satisfactory proceed with the installation 2 When mounting the Surface Mount Ledfire III the cover MUST be removed Remove the cover using a flat blade screwdriver to release the clips and pull the cover upwards as shown below 3 The cover must also be removed for battery replacement and servicing All installation options can be found in the following section of this manual NOTE Ensure the...

Страница 4: ...tion 1 Disassemble the Surface Mount Ledfire III as shown in the installation instructions in section 4 page 3 of this manual This will allow for the rod mount to be assembled to the products top cover 2 Ensure rod is mounted ONLY on a flat surface and fasten with the appropriate fixing e g masonry anchor for concrete 3 A 25 tube is to be used pushed firmly in on both ends and fastened SURFACE MOU...

Страница 5: ...e battery as was previously installed and then reinstall inverter battery pack or install as per all relevant standard requirements 5 Replace the Surface Mount Ledfire III back into its previously mounted ceiling position and ensure the green charge light is illuminated Allow a few minutes for the battery to charge 6 Allow a minimum 24 hours charging time before carrying out any discharge tests as...

Страница 6: ...the battery performance as long as 12 discharge cycles per year is not exceeded The Ektor Generation III platform uses smart battery charging technology which reduces power consumption and increases battery life During the first stage of operation the battery charger charges the battery until full Afterwards the unit goes into a stage which charges the battery periodically This reduces the battery...

Страница 7: ...to the inverter is shown below The inverter can be used in an automatic self test mode which reduces the need for a test switch timer The self test ability automatically disables if the unit is wired to DALI or the wireless daughterboard is attached Additionally the third generation platform can be wired to a central battery system With this wiring the system cannot report the light status see Sel...

Страница 8: ...n be monitored through DALI When used as a central battery system the devices can be tested with DALI A mains rated switch can be wired with this product to turn ON OFF the non emergency light in normal use This does not affect operation in emergency mode A mains rated sensor can be wired with this product to turn ON OFF the light in normal use This does not affect operation in emergency mode Figu...

Страница 9: ...e 13 Discharge rating selection Remove expansion cover C B A PART HOURS INDICATOR CODE EVOLT CODE A STATUS B C DESCRIPTION COMPLETE UNITS Ledfire III Surface Mount White Ledfire III Surface Mount Black 1 hour 2 hours default 3 hours 4 hours 8 hours Central battery operation N A N A NON MAINTAINED MAINTAINED MODE 1689 1690 PARTS REPLACEMENTS Ledfire III Surface Mount inverter White Battery 3000mAh ...

Страница 10: ...For more information refer to the Configurations Status LEDs and Device Modes document INDICATOR DESCRIPTION YELLOW 2sec ON 2sec OFF YELLOW 4sec ON 1sec OFF YELLOW 0 5sec ON 0 5sec OFF GREEN 1xFlash Device is performing a duration test Last duration test passed The duration was met when last run Test ran less than five days ago Last duration test failed Failed to meet duration The device is not cu...

Страница 11: ... voltage Charging time Charger operation Charger type N A Surface mounted Hard wired 6 4V 16 hours Multi state Smart charge 230 240V 50Hz 40 C LiFePO4 2 Dependant on jumper IP20 0 50 C 7 Watts 21 PRODUCT SPECIFICATIONS SURFACE MOUNT LEDFIRE III 230mm 230mm 53mm 11 NOTE Maximum power consumption in the following configuration 230VAC 50Hz 1 hour discharge maintained mode charging active ...

Страница 12: ...gatively on the battery life It is not recommended that you connect the Ektor emergency products to the power supply if such conditions are prevalent If you choose to expose the Ektor emergency products to such harsh operating conditions Evolt may not honour any warranty on the life of the batteries or the product enclosure This Ektor emergency product is designed to undergo regular discharge test...

Страница 13: ... to be permanently connected to the mains supply at the time of installation you must give it the mandatory 2 hour test when you connect it permanently to the mains supply 26 PROBLEM SOLVING PROCEDURE If you have installed and connected the Ektor Surface Mount Ledfire III as per the instructions contained within this manual and the product fails to work properly please use the following table as a...

Страница 14: ... in any way or used other than in accordance with their instructions are not covered by this warranty This warranty is not transferrable and is valid only in the hands of the purchaser of the product The warranty does not cover Ektor products other than those purchased from Evolt Proof of purchase must be provided to Evolt with any warranty claim Evolt recommends that the purchaser attaches their ...

Страница 15: ...A1 2009 A2 2009 EN 61000 3 3 2008 Luminaires Part 1 General requirements and tests Luminaires Part 2 22 Particular requirements Luminaires for emergency lighting Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment Equipment for general lighting purposes Electromagnetic compatibility EMC immunity requirements Electromagnetic compatibil...

Страница 16: ...DRAFT Ph 612 9502 1161 Fax 612 9502 1154 Email sales evolt com au evolt com au Reference 602893_V2 ...

Отзывы: