background image

Terminal block description for Monitoring system EKO-KE2

Terminal 1:    L/phase 230 V 
Terminal 2:    N/neutral 230 V 
Terminal 3:    PE

Terminal 4:   Buzzer alarm 1/fan output* 
Terminal 5:   Buzzer alarm 1/fan output*

Terminal 6:   Buzzer alarm 2/alarm output** 
Terminal 7:   Buzzer alarm 2/alarm output** 

Terminal 8:   Buzzer alarm 3/service output*** 
Terminal 9:   Buzzer alarm 3/service output***

Terminal 10:  Smoke detector loop (-) 
Terminal 11:  Smoke detector loop (+)

1   2   3  

4   5  

6   7  

8   9  

10   11   12   13   14   15  

16   . .   . .   2 3

TRIG IN

*   Breaks upon power outage, function text, error and alarm
**  Breaks upon power outage and alarm
**  Breaks upon power outage and error

Terminal 12:  External alarm input 1
Terminal 13:  External alarm input 1

Terminal 14:  External alarm input 2/Night closing
Terminal 15:  External alarm input 2/Night closing

Terminal 16, 20:  Actuator feed 1, AC 24 V 
Terminal 17, 21:  Actuator feed 2, +S1, +S4,
 

 

AC 24 V

Terminal 18, 22:  Signal contact S2
Terminal 19, 23:  Signal contact S6
 
Trigg in:  External timer

No Function

ON

OFF

Terminal Description

1

Smoke detector

Connected Disconnected

10-11

Detects if detector is present even if it is not 
selected. In such case, flashes red and yellow 
even during startup.

2

Night closing

Connected Disconnected

14-15

Alarm input 2. If night closing is not selected, no 
jumper is required at the input. If night closing 
is activated, both red and yellow light. Concluded 
with a manoeuvring operation.

3

Post-cooling

Connected Disconnected

4-5

Releases buzzer alarm 1 seven minutes before 
manoeuvring. Manoeuvring with button has no 
post-cooling.

4

External  
trigger input

Connected Disconnected

J10

A jumper is not necessary at the input if it is not 
used. If post-cooling is selected, it will be used.

5

Extra long closing 
and opening time

Connected Disconnected

16-23

60 sec. closing time instead of the normal 30 sec. 
400 sec closing time instead of the normal 200 sec.

6

Auto-reset of  
external alarm

Connected Disconnected

12-13

Option to automatically or manually reset  
external fire alarm.

7

External fire alarm Connected Disconnected

12-13

Option to connect existing fire alarm.

8

Not used 

Connected Disconnected

DIP switch functions  
(Located under the front panel)

ON = Pressed on top edge
OFF = Pressed on bottom edge

2020-03

3 (5)

EKOVENT AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden
Tel +46 40 42 16 00, [email protected], www.ekovent.com

Содержание EKO-KE2

Страница 1: ...ee page 3 Automatic performance testing time The EKO KE2 control and monitoring system perfor mance tests connected dampers 10 hours after the unit has been supplied with voltage or after the manual test has been conducted the unit is then performance tested every 48 hours This displacement is to avoid performance testing taking place during the daytime The option to conduct performance testing at...

Страница 2: ...ashing Operation power on Red 2 Non flashing Fire alarm Yellow 3 Non flashing Detector loop error Yellow 3 Flashing Damper error Red Yellow 2 3 Flashing Service alarm detector Green 4 Non flashing Normal mode Red 5 Non flashing Alarm mode Red Yellow Green 1 2 3 Non flashing Night closing dampers When the system is starting up EKO KE2 detects which damper inputs are connected EKO KE2_2011 measure 1...

Страница 3: ...tor is present even if it is not selected In such case flashes red and yellow even during startup 2 Night closing Connected Disconnected 14 15 Alarm input 2 If night closing is not selected no jumper is required at the input If night closing is activated both red and yellow light Concluded with a manoeuvring operation 3 Post cooling Connected Disconnected 4 5 Releases buzzer alarm 1 seven minutes ...

Страница 4: ...er motor 24 V 20 21 22 23 1 S4 2 S1 S2 S6 Inkopp Ex KE2 Spj2_2011 EKO KE2 Damper motor 24 V Damper motor 24 V 16 17 18 19 1 2 S2 S6 4 conductor cable 4 conductor cable S1 1 2 S4 S2 S6 S1 S4 2 dampers Series connection example Damper 1 Damper 2 Damper group 1 2020 03 4 5 EKOVENT AB Mejselgatan 7 SE 235 32 Vellinge Sweden Tel 46 40 42 16 00 info ekovent se www ekovent com ...

Страница 5: ...gsexempel EKO KE2 kanaldetektor EKO RE i serie EKO RE Channel detector 2 1 5 6 7 2 2 kOhm EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 24 VAC separate supply for any auxiliary fan Smoke detectors connected in series When several smoke detectors are connected in series a terminating resistor must only be fitted to the last detector in the loo...

Отзывы: