Technical data 

Supply voltage  

AC 220–230 V, 50/60 Hz

Power consumption  

20 VA

Alarm outputs 

Potential-free break contacts, 230 V, 5 A

Alarm input 

10 mA closed position, 1.8 V open position*

EMC 

SS-EN50 130-4

Max number of smoke detectors  

4

Ambient temperature  

0°C to +43°C

Enclosure class 

IP 65

Weight 

1.2 kg

* Connected contact must be potential-free.

Technical data for Monitoring system EKO-KE2

Measurement data

Function and location of LEDs

Colour 

Location Light 

Function

Green 

Non-flashing   Operation/power on

Red 

Non-flashing   Fire alarm

Yellow 

Non-flashing   Detector loop error

Yellow 

Flashing 

Damper error

Red/Yellow 

2 & 3 

Flashing 

Service alarm detector

Green 

Non-flashing   Normal mode

Red 

Non-flashing   Alarm mode

Red/Yellow/Green  1, 2, & 3 

Non-flashing   Night closing dampers

When the system is starting up, 

EKO-KE2 detects which damper 

inputs are connected.

EKO-KE2_2011 measure

180

86

130

TEST

RESET

ALARM

DAMPER

NORMAL

ALARM/

ERROR

ERROR

OPERATION

CONTROL AND MONITORING SYSTEM EKO-KE2

2

 (Alarm)

3

 (Error)

1

 (Operation)

4

 (Normal)

 

5

 (Alarm/Error)

Test

Reset

2020-03

2 (5)

EKOVENT AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden
Tel +46 40 42 16 00, [email protected], www.ekovent.com

Содержание EKO-KE2

Страница 1: ...ee page 3 Automatic performance testing time The EKO KE2 control and monitoring system perfor mance tests connected dampers 10 hours after the unit has been supplied with voltage or after the manual test has been conducted the unit is then performance tested every 48 hours This displacement is to avoid performance testing taking place during the daytime The option to conduct performance testing at...

Страница 2: ...ashing Operation power on Red 2 Non flashing Fire alarm Yellow 3 Non flashing Detector loop error Yellow 3 Flashing Damper error Red Yellow 2 3 Flashing Service alarm detector Green 4 Non flashing Normal mode Red 5 Non flashing Alarm mode Red Yellow Green 1 2 3 Non flashing Night closing dampers When the system is starting up EKO KE2 detects which damper inputs are connected EKO KE2_2011 measure 1...

Страница 3: ...tor is present even if it is not selected In such case flashes red and yellow even during startup 2 Night closing Connected Disconnected 14 15 Alarm input 2 If night closing is not selected no jumper is required at the input If night closing is activated both red and yellow light Concluded with a manoeuvring operation 3 Post cooling Connected Disconnected 4 5 Releases buzzer alarm 1 seven minutes ...

Страница 4: ...er motor 24 V 20 21 22 23 1 S4 2 S1 S2 S6 Inkopp Ex KE2 Spj2_2011 EKO KE2 Damper motor 24 V Damper motor 24 V 16 17 18 19 1 2 S2 S6 4 conductor cable 4 conductor cable S1 1 2 S4 S2 S6 S1 S4 2 dampers Series connection example Damper 1 Damper 2 Damper group 1 2020 03 4 5 EKOVENT AB Mejselgatan 7 SE 235 32 Vellinge Sweden Tel 46 40 42 16 00 info ekovent se www ekovent com ...

Страница 5: ...gsexempel EKO KE2 kanaldetektor EKO RE i serie EKO RE Channel detector 2 1 5 6 7 2 2 kOhm EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 24 VAC separate supply for any auxiliary fan Smoke detectors connected in series When several smoke detectors are connected in series a terminating resistor must only be fitted to the last detector in the loo...

Отзывы: