Page  5 

 

 

 

 

Menu / User settings/Summer operation

 

 

Designation 

Area 

Standard 

Description

 

 

Summer operation 

1 > 

Summer operation can optional be set for 1 to 5 periods. 
Each period must minimum be 1 hour. Hours are typed 
under TT and minutes under MM. If not all  periods are 
being used, nothing are typed in these. Once the periods 
have been typed, press “No” and this changes to “Yes”. 
After this press “Save and restart

”. 

 

 
 
 
 
 
 
 
 
 

 

Menu / User settings /VVB Priority

 

If there is a temperature sensor installed in the hot water 
tank and connected to the controller, you can reset the 
summer operation in all periods and only run the boiler 
when hot water is needed. The temperature of this must 
be set under VVB priority. Summer operation must be 
activated to do this and this can be checked by the 
appearance of a sun in the graphics on the front page. 

Designation 

Area 

Standard 

Description

 

 

VVB Priority 

Make the boiler produce hot water (domestic water). To 
use the function use an Ekopower priority sensor and a 
230 V motor powered valve. In the menu you set the 
wanted hot water temperature, and how much the 
temperature is allowed to drop before the domestic 
water need heating again. 

 
 

 

 
 

 

VVB Priority 

Yes/No 

No 

Change to Yes, if this is connected to the installation. 

 
 

 

VVB Temp. 

0 - 70˚ 

60˚ 

The temperature in the hot water tank. 

 

 

VVB Drop 

     0 - 20˚ 

10˚ 

Temperature drop in the hot water tank before the boiler 

    

 

makes priorities. We recommend that the temperature 

 

 

 

 

 

 

 

 

 

drop 

does not get below 10

o

 
 

Содержание EkoHeat 1500

Страница 1: ...are up dating Page 17 Technical specifications Page 18 Warranty Page 19 CE Marking Page 20 23 Test of approval Page 24 Marks of approval The pellet boiler from Ekopower has been tested by Dansk Teknol...

Страница 2: ...not be more than 0 5 m long and must always be rising If the flue pipe extend more than 0 5 meter or if bendings are mounted then it must always be insulated The draught in the chimney must be stable...

Страница 3: ...a time Calibration of the auger must be done before start up of the boiler as it then will not obtain the ultimate combustion and thus have a lower efficiency Press Menu user settings adjust calibrat...

Страница 4: ...Boiler temperature 40 80 60 Here you set the wanted boiler temperature Should not be below 60 and always 10 higher than the set point of the shunt valve Fuel 0 Kilogram pellets which are added per hou...

Страница 5: ...r is needed The temperature of this must be set under VVB priority Summer operation must be activated to do this and this can be checked by the appearance of a sun in the graphics on the front page De...

Страница 6: ...this will run when the temperature of the boiler is above set point and stops when this is below again Ekopower recommends to set pump stop at 55 and the boiler temperature at 65 by engagement of summ...

Страница 7: ...ill destroy the thread for the spindle Efficiency for flue suction 0 100 100 Here you can adjust how much air need to be added in proportion to efficiency in percent You can adjust per 10 These number...

Страница 8: ...oiler temperature rises before the boiler stops and waits for a temperature drop The boiler starts again when the boiler temperature is below 45 degrees Max efficiency 20 100 60 The boiler can be set...

Страница 9: ...ifferent flags as a symbol of which language you want on the boiler Menu Self Testing Here you can choose which type of boiler you have 900 1500 2500 4000 Test boiler is only for Ekopower authorised t...

Страница 10: ...of wood pellets The ash can be used in the garden as compost The burner According to need take out the burner by loosening the two handles on each side of the burner The air vents which are placed in...

Страница 11: ...ensor and the ash plate can be taken out and the slag can be removed Photo sensor Once a month check the photo sensor for dirt on the eye Pull it carefully out of its holder and clean the glass part w...

Страница 12: ...Page 12 Electrical chart of the control...

Страница 13: ...sive pipe pocket on the return water Draught stabilizer To be used by too much draught or by fluctuating draught to give a more even draught in the chimney Connection kit A connection kit is used betw...

Страница 14: ...gnition error The amount of pellets for ignition is too small or too big The calibration might be incorrect The boiler must be calibrated If this does not help adjust the amount of pellets for ignitio...

Страница 15: ...lation of slag on the ash plate Clean the ash plate for slag The screw stick is not greased with aluminium paste or the screw block is worn out Grease the screw stick with aluminium paste Change the s...

Страница 16: ...Then carefully lift out the controller 3 The USB flash drive is inserted in the USB port app on the middle of the printed circuit board 4 Now press MENU in the display 5 Then press FITTERS SETTINGS an...

Страница 17: ...s 74 liters 104 liters Min chimney draught 0 1 mBar 0 1 mBar 0 1 mBar 0 1 mBar Electrical connection 230V 60Hz 1 5A 340 Watt 230V 60Hz 1 5A 340 Watt 230V 60Hz 1 5A 340 Watt 230V 60Hz 1 5A 340 Watt Fue...

Страница 18: ...the warranty D Ekopower reserve the right to send an external service company This can only be done by Ekopower The installer dealer who have no written agreement from Ekopower will not get any work...

Страница 19: ...t EK OHEAT 900 EKOHEAT 1500 EK OHEAT 2500 EK OHEAT 4000 M tdi ine DndRie 3 1 CE stuvl 1 EN 3ffi 5 ffiM ng oo ilm fir solii mls hind M Ld i llltDin i lti cilly stDhd rom naJ hei 11 Cl llp1i a I to 300h...

Страница 20: ...Page 20...

Страница 21: ...Page 21...

Страница 22: ...Page 22...

Страница 23: ...Page 23 We do hope that you have got a good profit from this manual Should you have further questions please do not hesitate to contact us at post ekopower dk...

Отзывы: