Menu / User settings/Summer operation
Designation
Area
Standard
Description
Summer operation
1 >
Summer operation can optional be set for 1 to 5 periods.
Each period must minimum be 1 hour. Hours are typed
under TT and minutes under MM. If not all periods are
being used, nothing are typed in these. Once the periods
have been typed, press “No” and this changes to “Yes”.
After this press “Save and restart
”.
Menu / User settings /VVB Priority
If there is a temperature sensor installed in the hot water
tank and connected to the controller, you can reset the
summer operation in all periods and only run the boiler
when hot water is needed. The temperature of this must
be set under VVB priority. Summer operation must be
activated to do this and this can be checked by the
appearance of a sun in the graphics on the front page.
Designation
Area
Standard
Description
VVB Priority
Make the boiler produce hot water (domestic water). To
use the function use an Ekopower priority sensor and a
230 V motor powered valve. In the menu you set the
wanted hot water temperature, and how much the
temperature is allowed to drop before the domestic
water need heating again.
VVB Priority
Yes/No
No
Change to Yes, if this is connected to the installation.
VVB Temp.
0 - 70˚
60˚
The temperature in the hot water tank.
VVB Drop
0 - 20˚
10˚
Temperature drop in the hot water tank before the boiler
makes priorities. We recommend that the temperature
drop
does not get below 10
o
.