4
Configuration and commissioning
Configuration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by a qualified planner.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the bus;
• carry out the device addressing, as described in the
product Datasheet and in the application manual.
Device addressing
•
Simplified method
: 1 ballast connected at a time
• Random Address Allocation
DALI channels maps
The intensity and ON / OFF switching of the output is ma-
naged via the DALI channel.
Characteristics of the DALI terminal block
• Screw tightening of the conductors
• Command & bus wiring: 1.5 mm2 solid – 1 mm2 stran-
ded – 30 - 14 AWG
• Command & bus stripping: 6 mm
• Conductor stripping recommended approx. 10 mm
• Maximum length of the connection between dimmer-
driver and control device < 10 m
• Length of connection cables < 10 m
Connection of power supply and LEDs
For the power supply use SELV power suppliers with li-
mited current, short circuit protection only and the power
must be correctly dimensioned. In case of usage of a po-
wer supplier with ground terminals, all points of the pro-
tective earth (PE = Protection Earth) must be connected
to a valid and certified protection earth.
The connection cables between the power source “low
voltage” and the product must be correctly dimensioned
and they should be isolated from every wiring or parts at
not-SELV voltage. Use double insulated cables.
The power supply must be dimensioned according to
the load connected to the device. If the power supply is
oversized with respect to the maximum absorbed current,
then insert a protection against over-current between the
power supply and the device.
Characteristics of the supply and LEDs terminal block
• Screw tightening of the conductors
• Power & LEDs wiring: 2. 5mm2 solid – 1.5 mm2 stran-
ded – 30 - 12 AWG
• Power and LEDs stripping recommended approx.: 7.5
mm
• Max torque 0.5 Nm
Outputs
The length of the connection cables between the product
and the LED module must be less than 10m; the cables
must be correctly dimensioned and they should be isola-
ted from every wiring or parts at not-SELV voltage. It is
preferable to use shielded and twisted cables.
In case it is needed to connect the device and LED mo-
dules with cables longer than 10m, the installer must gua-
rantee the correct functioning of the system. In any case,
do not exceed 30m of the connection between the device
and the LED modules.
SUPPLY
+
L N
230 Vac
12-48 Vdc
DALI
50-60 Hz
-
-
OUT
L-
+
Dimmer LED
EK-GH1-DL
DC In: 12-48V
Out: max 8A
DALI IN
DA DA
DA DA
DALI OUT
Installation scheme
Address
Function
Map: dimmer
0
Dimmer
Dimmer (Intensity value) 0 .. 254
Signalling LEDs
On the device front panel a signaling LED is present. If
there is no BUS power supply or there is a BUS error,
the signaling LED flashes quickly (2 pulses per second).
If there is BUS power supply but a BUS error occurs, the
signaling LED flashes slowly (1 pulse per second). If the
BUS signal is connected and working correctly, the LED
remains on steady.
Relationship between DALI bus and local commands: on
power-up, in case the bus connection is not present, the
local command is active. When the BUS connection is
detected, the control passes to the BUS as long as the
signal is present. In the absence of the signal, if the local
command is an N.O. button, the control is passed to the
local commands when the button is pressed. On the other
hand, if the local command is 0-10V or 1-10V, the control
immediately passes to the local command.