background image

3

INSTALLATION TECHNICAL NOTES

•  Installation and maintenance must be 

performed only if the power supply has 

been turned off.

•  Installation and maintenance must only 

be  performed  by  qualified  personnel  in 

compliance with current regulations.

•  The product  must  be  installed  insi-

de an electrical panel protected against 

overvoltages.

•  The product must be installed in a verti-

cal position with the front / label facing 

the front or in a horizontal position with 

the front / label facing upwards. Other 

product installation positions are not al-

lowed. The bottom position with the front 

panel / label facing down is not allowed.

•  Keep separated the circuits at 230V (LV) 

and the circuits not SELV from circuits 

to low voltage (SELV) and from any con-

nection with this product. It is absolutely 

forbidden to connect, for any reason 

whatsoever, directly or indirectly, the 

230V mains voltage to the bus or to other 

parts of the circuit.

!

Setup and installation

In order to setup the dip-switch, it is necessary to open 

the device front cover, by means of a screwdriver as de-

tailed in the image below.

Configuration

Settings

Switch 1-2 = dimming curve

Switch 3-4 = input type

Switch 5-6 = Output Frame Rate – 

Frequency

Note: Factory settings = ALL OFF

Switches 1-2 (dimming curve settings)

Default

Exponential

Quadratic

Linear

Switches 3-4 (input local command settings)

Command

Description

Connection

Configuration

Pushbutton

N.O. pushbutton

without memory

N.O. pushbutton

with memory

0 - 10 V

Analog input 

0-10V

1 - 10 V

Analog input

1-10V

or

Potentiometer

Switches 5-6 (output dimming frequency settings)

300 Hz

600 Hz

1200 Hz

Reserved

DALI bus line and command connections

The connection to the DALI bus network and the local 

commands is done via the screw terminal, located on the 

front of the device in the upper part.

The length of the connection cables between the local 

commands (N.O. Pushbutton, 0-10V, 1-10V, Potentiome-

ter or other) and the product must be less than 10m; the 

cables must be dimensioned correctly and they should be 

isolated from every wiring or parts at voltage not SELV. 

Use double insulated shielded and twisted cables.

The length and type of the connection cables to the DALI 

bus must be compliant with the protocol specification and 

with the present regulations and they should be isolated 

from every wiring or parts at voltage not SELV. Use dou-

ble insulated shielded and twisted cables.

All the devices and the control signal connected to the 

DALI bus and to the local command (N.O. Pushbutton, 

0-10V, 1-10V, Potentiometer or other) must be SELV (the 

devices connected must be SELV or supply a SELV si-

gnal).

The 6-way dip-switch setting (under the front cover) offers 

a wide choice of possible configurations.

Содержание EK-GH1-DL

Страница 1: ...5 Brightness adjustment up to full off Dim to Dark Minimum brightness level 0 1 1 in push D PWM Modulation Adjusting D PWM frequency 300 600 1200 Hz Adjusting output curve Linear Quadratic Exponential Soft start and soft stop Technical data Inputs Input constant voltage 12 24 48 Vdc Supply voltage min 10 8 Vdc max 52 8 Vdc Power absorbed while awaiting command 500 mW Dimming Dimming frequency D PW...

Страница 2: ... push the locking device upward until it stops d Note When mounting the device in boards and ca binets it shall be provided the necessary ventilation so that the temperature can be kept within the ope rating range of the device i a b d c 1 Screw terminal for 12 24 48 Vdc input and output loads 2 Screw terminal for local commands and DALI line connection 3 Signalling LED OUT L Dimmer LED EK GH1 DL ...

Страница 3: ...ve settings Default Exponential Quadratic Linear Switches 3 4 input local command settings Command Description Connection Configuration Pushbutton N O pushbutton without memory N O pushbutton with memory 0 10 V Analog input 0 10V 1 10 V Analog input 1 10V or Potentiometer Switches 5 6 output dimming frequency settings 300 Hz 600 Hz 1200 Hz Reserved DALI bus line and command connections The connect...

Страница 4: ...t then insert a protection against over current between the power supply and the device Characteristics of the supply and LEDs terminal block Screw tightening of the conductors Power LEDs wiring 2 5mm2 solid 1 5 mm2 stran ded 30 12 AWG Power and LEDs stripping recommended approx 7 5 mm Max torque 0 5 Nm Outputs The length of the connection cables between the product and the LED module must be less...

Страница 5: ...ectromagnetic Compatibility Directive 2014 30 EU and the RoHS 2 Directive 2011 65 UE Reference Standards EN 61347 1 2008 A1 2011 A2 2013 EN 61000 2014 3 2 EN 61000 2013 3 3 EN 62384 2006 A1 2009 EN 55015 2013 A1 2015 EN 61547 2009 EN 50581 2012 Maintenance The device is maintenance free To clean use a dry cloth It must be avoided the use of solvents or other aggressive substances Disposal At the e...

Страница 6: ...al support at the e mail address support ekinex com or visit the website www ekinex com Each ekinex device has a unique serial number on the label The serial number can be used by installers or system integrators for documentation purposes and has to be added in each communication addressed to the EKINEX technical support in case of malfunctio ning of the device KNX and ETS are registered trademar...

Отзывы: