background image

 

Pag. 2

 

 

 

 

 

1) 

KNX bus line terminal blocks 

2) 

KNX programming pushbutton 

3) 

KNX programming LED 

4) 

Power supply terminal blocks 

5) 

1-way microswitch A 

6) 

Ethernet port 

7) 

Ethernet port LED 

8) 

Device satus LED 

9) 

Modbus communication LED 

10) 

KNX communication LED 

11) 

Device error LED 

12) 

RS485 serial line terminal blocks (3 Com, 4 RT-, 5 RT+) 

13) 

1-way microswitch B 

 

Command elements 
•  Pushbutton that switches between normal mode and 

KNX physical address programming. 

 
1-way microswitches 
•  A - OFF: normal mode active. ON: Boot mode active 
•  B - OFF: open. ON: RS485 line termination inserted 

(120 

  termination  resistance  in  parallel  between 

RT+ and RT-) 

 
Display elements 
The device can run according to two operating modes: 
Normal  mode  (configuration  loaded,  Modbus  and  KNX 
communication  running)  and  Boot  mode  (no 
configuration or configuration still loading). 
 
•  Green LED (8) – Device status. Normal mode: Slow 

blinking (~1 Hz). Boot mode: ON= device on; OFF=

 

device off. 

•  Yellow  LED  (9)  –  Modbus  communication.  Normal 

mode: blinks when a frame is received on the RS485 
port. Boot mode: if fast blinking: no configuration, if 
very slow blinking (~0,5 Hz): loading configuration. 

•  Yellow  LED  (10)  –  KNX  communication.  Normal 

mode: blinks when a frame is received. Boot mode: if 
fast  blinking:  no  configuration,  if  very  slow  blinking 
(~0,5 Hz): loading configuration. 

•  Yellow LED (11) – Device error. Normal mode: ON=

 

at  least  one  Modbus  request  did  not  get  a  correct 
answer; OFF=

 

no error. Boot mode: if fast blinking: 

no  configuration,  if  very  slow  blinking  (~0,5  Hz): 
loading configuration. 

•  Green LED (7) – Ethernet port. Normal mode: ON=

 

Ethernet  connector  plugged;  OFF=  Ethernet 
connector  unplugged.  Boot  mode:  ON=

 

Ethernet 

connector  plugged;  OFF=  Ethernet  connector 
unplugged. 

•  Red  LED  (3)  –  KNX  programming.  Normal  mode: 

ON=

 

physical address programming mode on; OFF=

 

physical address programming mode off. Boot mode: 
if fast blinking: no configuration, if very slow blinking 
(~0,5 Hz): loading configuration. 

 

Installation 

The device has IP20 protection degree and is therefore 
suitable for dry indoor environments. The case is suitable 
for mouting on a DIN rail (according to EN 60715) inside 
eletrical  distribution  cabinets.  The  proper  installation 
involves the bus terminal blocks to be in the lower side. 
For installation proceed as follows: 
 
•  with the aid of a tool bring the locking device in 

completely lowered position (1); 

•  place the device on the upper edge of the DIN rail 

(2); 

•  rotate the device towards the DIN rail (3); 
•  push the locking device up untili il stops (4). 
 

 

 

 

 

 

 

 

 

 

 

 

 

 
To unmount the device, make sure to unplug the network 
connection and the bus terminal from its housing.

 

Use a 

screwdriver to slide down the lock and remove the device 
from the rail. 
 

 

Note.  It  is  recommended  to  install  the  device  so  to 
always  guarantee  full  frontal  accessibility,  in  order  to 
properly display the status LEDs. 

 

Power supply connection

 

The  device  supports  a  very  wide  range  of  supply 

1

 

2

 

5

 

4

 

12

 

6

 

7

 

8

 

9

 

10

 

11

 

13

 

3

 

Failure

KNX

Modbus

Device state

EK-BH1-TP-485

Modbus Master RS485 RTU
/ KNX TP Converter

1

2

8...24 Vac

+V

0V

POWER S.

12...35 Vdc

3

4

5

RS485

ETHERNET

Dev.

Line

Area

ON

ON

RT-

Com

RT+

DC
E

K

B

H1T

P

4

8

5

 

 