KNX bus line
The connection to the KNX bus line is made with the ter-

minal block (black/red) included in delivery and inserted 

into the slot located on the left bottom part of the front. 

Characteristics of the KNX terminal block:
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm (20 

~ 22AWG)

•  recommended wire stripping approx. 5 mm

• 

color  codification:  red  =  +  (positive)  bus  conductor, 

black = - (negative) bus conductor

Auxiliary output
The 30 Vdc auxiliary output has a dedicated connection 

screw terminal block. 

Characteristics of the terminal block for the auxiliary ou-

tput:

•  screw clamping of conductors

•  conductor wiring size: solid 0.5 ~ 4.0 mm2 or stranded 

0.5 ~ 2.5 mm2  (12 ~ 26AWG)

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

For the connection of the auxiliary output and the powe-

red devices it is recommended to use a cable with a she-

ath of a different color than the cable connecting the KNX 

bus line.

Warning!

 The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off. 

!

Note.

 The configuration and commissioning of KNX 

devices require specialized skills. To acquire these 

skills, you should attend the workshops at KNX cer

-

tified training centers.

i

Before removing the device, be sure the inputs have been 

disconnected and the bus terminal has been extracted 

from its slot. Use a screwdriver to slide down the locking 

device and remove the device from the rail.

Electrical connections

Input main supply
The connection to the input main supply 180 ~ 264 Vac, 

176 ~ 280 Vdc is made with screw terminals (    , L, N) 

located on the upper front of the device. 
Characteristics of the terminal blocks:
•  screw clamping of conductors (use a slotted screwdri-

ver 2.5*0.4-3.5*0.6)

•  Conductor wiring size: 0.5 ~ 4.0 mm solid core or 0.5 ~ 

2.5mm finely stranded

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

Configuration and commissioning

Configuration
The device does not require any configuration with ETS® 

(Engineering Tool Software) tool. The application softwa-

res APEKAM1TP##.knxprod (## = version) is available in 

order to add the power supply to an ETS project.
Commissioning
For the commissioning of the device turn on the input 

mains power supply to which the device is connected. 

The LED marked “Vbus” solid green indicates the device 

operating in the normal range.

Reset

The device has a reset pushbutton. By keeping it pressed 

for at least 20 seconds, the bus line is not powered for 

20 seconds and the bus devices connected are restored 

to their original condition. During this interval of time the 

reset LED (red) is turned permanently on.

Failure

When the LED labeled “I > Imax”, is turned on solid oran-

ge or red, this means that the KNX output is overloaded or 

short-circuited. The problem can be solved by removing 

the cause of the short circuit or by reducing the number of 

KNX devices connected to the line. After the removal of 

the problem only the green LED “V

bus

” is turned on, at this 

time it is recommended to reset the line.

L

N

PE

+

-

V input

AUX

30Vdc

Bus

KNX

+

-

Содержание EK-AM1-TP

Страница 1: ...the 30 Vdc voltage required to operate the bus system It has a 30 Vdc additional output which can be used as a SELV sa fety extra low voltage auxiliary power for bus devices The device has an integrat...

Страница 2: ...m number of bus devices connected is 256 the maximum length of a line segment is 350 m me asured along the line between the power supply and the furthest bus device the maximum distance between two bu...

Страница 3: ...ted and the bus terminal has been extracted from its slot Use a screwdriver to slide down the locking device and remove the device from the rail Electrical connections Input main supply The connection...

Страница 4: ...e appli cable technical standards and laws of the respective countries The use of the device in security applications is not allowed The device may however be used for auxiliary signaling functions Op...

Страница 5: ...ssed to the EKINEX technical support in case of malfunctio ning of the device KNX and ETS are registered trademarks of KNX Association cvba Brussels EKINEX S p A The company reserves the right to make...

Страница 6: ...bus devices can not exceed 700 m the maximum length of a bus line is 1000 m keeping into account all segments It is possible to connect two EK AM1 TP in parallel with the following conditions two cho...

Страница 7: ...7 Annex 3 Block diagram Annex 4 Characteristics Derating curve Static characteristics...

Отзывы: