GuaRdboX
-
Gd
series
IOM
(
Installation, Operation & Maintenance Manual) 0100-ENG
rev.5
5
Eisenbau s.r.l. a socio unico
Via T.A:Edison, 16 20090 Cusago (MI) Italy
Phone : +390293562116 Fax: +390293567735
Guardbox production unit : Via XXIV Maggio, 13
25017 – Sedena di Lonato (BS)
Phone : +390309131240 Fax: +390309130946
www.eisenbau.it
www.guardbox-ex.com
7.1
Replace the protective caps with suitably certified and temperature rated cable glands and blanking plugs permitted for use
with ATEX/IECEx flameproof enclosures.
7.2
Product IP rating is ensured only by the use of suitable IP rated cable glands and plugs
7.3
Make sure that the cable glands are steadily tightened so that the sealing ring reaches the proper compression to avoid the
transmission of mechanical stresses to the terminals (4).
7.4
Number, position and size of the provided cable entries are specified in the adhesive label outside the box cover. Number and
type of cable entries can also be determined by reference to the 4th digit of limit switch box model marked on both internal and
external labels. The certified cable entry options in the following table (3):
Table 3
– Cable entry options
Entry size
Max
quantity *
M20x1,5 M25x1,5 1/2
”NPT
3/4
”NPT
N°3
Metric thread conform to UNI 5870:1971
NPT thread conform to ANSI/ASME B1.20.1:1983
7.5
Unscrew the six box cover captive screws (8) , then remove the box cover (7).
7.6
Use cables suitable for temperature class as specified in following table (4):
Table 4
– Suitable cable temperature class
Ta
max
[°C]
*
Maximal allowed
power dissipation [W]
Temperature
class
Maximum surface
temperature
Suitable cable
temperature class
40
4
T6
85°C
70°C
10
T6
85°C
70°C
65
4
T6
85°C
80°C
10
T5
100°C
100°C
85
4
T5
100°C
100°C
10
T4
135°C
120°C
90
4
T4
135°C
105°C
10
T4
135°C
125°C
105
4
T4
135°C
120°C
*
Refer to label/s attached inside the box cover
7.7
Connect field wiring to the terminals (4) within the circuit board (9) according to the wiring diagram and terminal labelling
available inside the box.
7.8
Make sure that the electrical wires are steadily tightened and totally inserted into the terminals (4) and that there isn
’t non-
insulated conductor material.
7.9
For box with circuit board (9) installed, the terminals (4) must be tightened using a torque value between 0,5÷0,6Nm.
minimum
clearance
required to
remove the
box cover is
60mm
0,5÷0,6Nm
20Nm
* Every box housing can be customized with a
various combination , in quantity and size, of cable
entries up to a maximum of 3 , depending on
customer request
NOMINAL RANGE OF USE
Ambient temperature:
-60°C
≤
Ta
≤ 105°C
Nominal voltage:
0
– 125 VDC
0
– 250 VAC
Nominal current:
0,1
– 10 A