7.1

     

Replace the protective caps with suitably certified and temperature rated cable glands and blanking plugs permitted for use 
with ATEX/IECEx flameproof enclosures.  

7.2

 

Product IP rating is ensured only by the use of suitable IP rated cable glands and plugs 

7.3

 

Make sure that the cable glands are steadily tightened so that the sealing ring reaches the proper compression to avoid the 
transmission of mechanical stresses to the terminals (4). 

7.4

 

Number, position and size of the provided cable entries are specified in the adhesive label outside the box cover. Number and 
type of cable entries can also be determined by reference to the 4th digit of limit switch box model marked on both internal and 
external labels. The certified cable entry options in the following table (3): 

               

 

                                                   Table 3 

– Cable entry options 

 

Entry size  

Max 

quantity * 

M20x1,5  M25x1,5  1/2

”NPT 

3/4

”NPT

 

N°3

 

Metric thread conform to UNI 5870:1971 

NPT thread conform to ANSI/ASME B1.20.1:1983

 

 

7.5

 

Unscrew the six box cover captive screws (8) , then remove the box cover (7). 

7.6

 

Use cables suitable for temperature class as specified in following table (4): 

                                                                              Table 4 

– Suitable cable temperature class 

Ta 

max

 [°C] 

*

 Maximal allowed 

power dissipation [W] 

Temperature 

class  

Maximum surface 

temperature 

Suitable cable 

temperature class 

40 

T6

 

85°C

 

70°C

 

10 

T6

 

85°C

 

70°C

 

65 

T6

 

85°C

 

80°C

 

10 

T5

 

100°C

 

100°C

 

85 

T5

 

100°C

 

100°C

 

10 

T4

 

135°C

 

120°C

 

90 

T4

 

135°C

 

105°C

 

10 

T4

 

135°C

 

125°C

 

105 

T4

 

135°C

 

120°C

 

Refer to label/s attached inside the box cover

 

7.7

 

Connect  field  wiring  to  the  terminals  (4)  within  the  circuit  board  (9)  according  to  the  wiring  diagram  and  terminal  labelling 
available inside the box.  

7.8

 

Make sure that the electrical wires are steadily tightened and totally inserted into the terminals (4) and that there isn

’t non-

insulated conductor material. 

7.9

 

For box with circuit board (9) installed, the terminals (4) must be tightened using a torque value between 0,5÷0,6Nm. 

 

 

 

 

minimum 

clearance 

required to 

remove the 

box cover is 

60mm 

0,5÷0,6Nm 

20Nm 

 

*  Every  box  housing  can  be  customized  with  a 

various combination , in quantity and size, of cable 

entries  up  to  a  maximum  of  3  ,  depending  on 

customer request

 

NOMINAL RANGE OF USE 

Ambient temperature: 

-60°C 

≤ 

Ta

 

≤ 105°C 

 

Nominal voltage: 

– 125 VDC  

– 250 VAC 

 

Nominal current: 

0,1 

– 10 A 

Содержание GuaRdboX GD Series

Страница 1: ...alves or actuators which drive the process valves from closed to open position Normal acting or from open to closed position Reverse acting Normal acting is considered full CW when the process valve i...

Страница 2: ...acteristics of the electrical connection are compatible with electrical operation parameters of operation of the box 3 5 Do not exceed the limit switch box performance limitation Exceeding the limitat...

Страница 3: ...r repair of the flameproof enclosure is permitted For additional assistance please contact the manufacturer 3 19 CAUTION The metallic alloy used for the housing material may be at the accessible surfa...

Страница 4: ...2 mm 6 4 The motion transmission from the actuator or valve to the box GD is attained by a mechanical coupling Before installation on a valve or an actuator make sure that the orientation of the posit...

Страница 5: ...3 Metric thread conform to UNI 5870 1971 NPT thread conform to ANSI ASME B1 20 1 1983 7 5 Unscrew the six box cover captive screws 8 then remove the box cover 7 7 6 Use cables suitable for temperatur...

Страница 6: ...s are factory presetted in order to operate in a box installed parallel See section 6 Mounting to CCW rotating actuators Normal acting The lower cam 1 is regulated to operate the switch in the full CW...

Страница 7: ...Pi PN inductive proximity inductive proximity namur Board assembly Turn the actuator pinion full CW and regulate the cam till the switch 1 is activated Turn the actuator pinion full CCW and regulate t...

Страница 8: ...tion of mounting screws bolts O rings and terminal wiring for signs of loosening or corrosion as part of the routine plant maintenance 10 3 Guardbox boxes have been projected to withstand the most sev...