background image

GuaRdboX

 - 

Gd

 

series   

 

 

IOM 

(

Installation, Operation & Maintenance Manual)    0100-ENG 

rev.5 

                                      

    

        

 

 

Eisenbau s.r.l. a socio unico 

Via T.A:Edison, 16 20090 Cusago (MI) Italy                

Phone : +390293562116 Fax: +390293567735 

Guardbox production unit : Via XXIV Maggio, 13   

25017 – Sedena di Lonato (BS)   

Phone : +390309131240 Fax: +390309130946

        

 

 

www.eisenbau.it 

www.guardbox-ex.com 

 

 

 

3.13

 

The box is provided with two grounding connection facilities, one inside and one outside the housing. The facilities allow for 
the effective connection of at least one conductor with a cross-sectional area given below in table (2):

 

 

Table 2 

– minimum cross-sectional area of protective conductors 

 

Cross-sectional area of phase conductor, 

S

 

[mm

2

]

 

Minimum cross-sectional area of the 

corresponding protective conductor, 

S

p

 

[mm

2

]

 

≤ 16 

16 < S 

≤ 35 

≥ 35 

S  

16  

0,5S

 

 

3.14

 

For  Explosion  Proof  installations,  the  internal  ground  connection  shall  be  used.  The  external  ground  connection,  is  an 
additional wiring allowed where local authorities permit, or is required. Use a ground wire of proper cross section.

 

3.15

 

Both internal and external grounding connections are clearly identified and permanently marked on the box housing and are 
projected to facilitate the installation of the ground cable preventing it from rotating. 

 

3.16

 

A  grounding  connection  kit  composed  by  n°2  phillips  head  screws  plus  n°2  toothed  washers,  is  provided  in  a  sealed  bag, 
available inside the box. The two anti-vibration washers help to ensure the securing of the cable.

 

3.17

 

 

WARNING!:

 

Risk of electrostatic charges accumulation on non-conductive parts of the box (eg. Plastic indicator dome). 

The external surfaces of the box 

must be preserved by the accumulation of dust through periodic cleaning. 

Clean Only with a 

Damp Cloth.

 

3.18

 

No maintenance or repair of the flameproof enclosure is permitted. For additional assistance, please contact the manufacturer.

 

3.19

 

 

CAUTION!:

 The metallic alloy used for the housing material may be at the accessible surface of this equipment; in the 

event of rare accidents, ignition sources due to impact and friction sparks could occur.

 

3.20

 

 

CAUTION!:

 

The box can work in plants in presence of extreme environments and in contact with highly aggressive and 

corrosive substances that may affect the integrity of the product and its protection mode. To operate in such conditions the 
box is projected to be realized in different materials that ensure durability and reliability in operation. For the right choice of the 
available options, please contact Eisenbau.

 

 

4.

 

  

     

    

DECLARATION OF CONFORMITY in accordance with the    

            

 

    Relevant union harmonization legislation atex directive 2014/34/

eu

    

            

 

The manufacturer Eisenbau s.r.l. herewith declare under his sole responsibility, that the limit switch boxes GD-series complies, when 
installed in accordance with the installation and safety instruction, with all the following applicable EU directives, Regulations and all 
the essential Health and Safety requirements:  

 

         Ex 

– Equipment Marking           

               

II2G  Ex db IIC T6

…T4 Gb 

                                                                             II2D  Ex tb IIIC T85°C

…T135°C Db  

 

IEC 60079-0:2011 (Ed6.0); IEC 60079-1:2014-06 (Ed7.0); IEC 60079-31:2013 (Ed2.0) 

EN 60079-0:2012/ A11:2013; EN 60079-1:2014; EN 60079-31:2014 

ATEX EC 

– 

Type examination certificate

:   EXA 15 ATEX 0039X 

     IECEx 

– 

Certificate of Conformity

:  IECEx EXA 15.0008X 

                                                ATEX - 

Production Quality Assurance Notification

:

 

EXA 15 ATEX Q051

 

           IECEx - 

Product Quality Assessment Report

 : HR/EXA/QAR15.0001/00 

Guardbox GD-series Limit switch boxes are also available, on request, with the following certification: 

  

- Customs union certificate of conformity :

      N° TC RU C-IT.BH02.B.00123       Series RU   N° 0325960

 

5.

 

 Installation:  

       

 

 

 

    

 

    

 

QR code or data matrix to directly 

download drawings, wiring diagrams, 

manuals and certificates directly on field 

 

Содержание GuaRdboX GD Series

Страница 1: ...alves or actuators which drive the process valves from closed to open position Normal acting or from open to closed position Reverse acting Normal acting is considered full CW when the process valve i...

Страница 2: ...acteristics of the electrical connection are compatible with electrical operation parameters of operation of the box 3 5 Do not exceed the limit switch box performance limitation Exceeding the limitat...

Страница 3: ...r repair of the flameproof enclosure is permitted For additional assistance please contact the manufacturer 3 19 CAUTION The metallic alloy used for the housing material may be at the accessible surfa...

Страница 4: ...2 mm 6 4 The motion transmission from the actuator or valve to the box GD is attained by a mechanical coupling Before installation on a valve or an actuator make sure that the orientation of the posit...

Страница 5: ...3 Metric thread conform to UNI 5870 1971 NPT thread conform to ANSI ASME B1 20 1 1983 7 5 Unscrew the six box cover captive screws 8 then remove the box cover 7 7 6 Use cables suitable for temperatur...

Страница 6: ...s are factory presetted in order to operate in a box installed parallel See section 6 Mounting to CCW rotating actuators Normal acting The lower cam 1 is regulated to operate the switch in the full CW...

Страница 7: ...Pi PN inductive proximity inductive proximity namur Board assembly Turn the actuator pinion full CW and regulate the cam till the switch 1 is activated Turn the actuator pinion full CCW and regulate t...

Страница 8: ...tion of mounting screws bolts O rings and terminal wiring for signs of loosening or corrosion as part of the routine plant maintenance 10 3 Guardbox boxes have been projected to withstand the most sev...

Отзывы: