The  Adjustable  Humidistat:

  The  CD-35  dehumidifier  unit  is  fitted  with  a 

control  humidistat  which  measures  the  relative  humidity  of  the  air  within  the 
room.    The  humidistat  incorporates  a  pointer  and  scale,  which  can  be 
adjusted, and set to a relative humidity level that is acceptable to maintain the 
required  conditions  within  the  room.  The  humidistat  controls  the  on/off 
function of the dehumidifier.  When the relative humidity of the air in the room 
falls below the set point of the humidistat the dehumidifier will switch off, but 
when  the  relative  humidity  of  the  air  starts  to  rise  again  and  passes  the  set 
point the unit will switch on. The humidistat is used for the on/off function as it 
is a cost effective method which ensures power is only used when needed. 
 

Condensate pump: 

The CD-35 dehumidifier unit can be fitted, either in the 

factory, or as retro-fit, with a condensate pump.  This condensate pump will 
allow the unit to run unattended, with the condensate run off to a permanent 
drain and can be used up to 13 feet (4 meters), below the level of a 
permanent condensate drainage point.

 

 
 

UNPACKING & INSTALLATION 

 
 

After removing the CD35 from its shipping container, visually check for signs 
of damage. If there is evidence of damage, do not operate. Call your supplier 
for advice. Do not discard the packing as it will be useful when transporting 
the machine in the future. 
 
Wiring: Connect the power cord to a grounded single phase, 15 Amp fused, 
standard household wall socket. 
 
 

POSITIONING 

 
 

Single Room:

 Position the CD35 in the center of the room to be dried. 

However, if a damp patch is particularly apparent, the outlet grille should be 
directed towards it. If the CD35 cannot be positioned centrally, a minimum 
space of 6” should be allowed around the dryer. 
 

Several Rooms

: To dry a number of rooms simultaneously with the most 

efficiency, the dryer as to be positioned between the rooms. Ensure that all 
doors are left ajar allowing a patch for the air to circulate to the unit. An 
auxiliary circulation fan would be helpful. 

Содержание CD35SP

Страница 1: ...Page 1 of 12 Drawing TPC509 Issue 1 Date 29 01 20 CD35SP INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk ...

Страница 2: ... 2 of 12 Drawing TPC509 Issue 1 Date 29 01 20 CD35SP PACKAGE CONTENTS Item Description Quantity 10186SP US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC509 Manual 1 ...

Страница 3: ...permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier ...

Страница 4: ...sed in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CD35SP HEIGHT 22 WIDTH 13 5 DEPTH 14 WEIGHT 63 lbs AIRFLOW 170 CFM POWER SUPPLY 110V 60Hz 1 ph CURRENT MAX 3 A REFRIGERANT R 134a REF CHARGE 0 19Kg CONSTRUCTION 18 AWG Epoxy Power Coated galvanized st...

Страница 5: ...ate pump This condensate pump will allow the unit to run unattended with the condensate run off to a permanent drain and can be used up to 13 feet 4 meters below the level of a permanent condensate drainage point UNPACKING INSTALLATION After removing the CD35 from its shipping container visually check for signs of damage If there is evidence of damage do not operate Call your supplier for advice D...

Страница 6: ...otor shaft and that the fan rotates freely 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the cover The evaporator coil should be evenly frost coated across its surface At temperatures above 20 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or...

Страница 7: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Страница 8: ... the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Factory Service Center 2 Contact the Factory Service Center Unit vibrates excessively 1 Loose compressor 2 Damaged fan 1 Tighten the nuts on the compressor mounts 2 Replace fan Water flooding...

Страница 9: ...014253 CAPILLIARY TUBE 3020811 BY PASS VALVE 3020937 FILTER DRYER 3033033 MICROSWITCH 3035145 HUMIDISTAT 3035346 PANEL MOUNTED TERMINAL BLOCK 3036636 RED LAMP ASSY 3040129 FAN BLADE 3050216 CASTOR 1619519 PCB 2141095 MAINS POWER CABLE 3944958 COMPRESSOR 3030421 SOLENOID COIL 3035773 MOTOR 2013837 DRAIN TRAY 3160155 CONDENSATE PUMP Spare parts available online www EIPLDIRECT com ...

Страница 10: ...Y WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARRANTY REGISTRATION To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty please complete and mail this...

Страница 11: ...yoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label Due to the high pressures within the refrigeration circuit under no circumstances must direct ...

Страница 12: ...www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Products Ltd Gartenfelder Str 29 37 Gebäude 35 D 13599 Berlin Germany Tel 49 3043 557241 Fax 49 3043 557240 www eip ltd de sales eip ltd...

Отзывы: