REPAIRS 

 

 

1. 

Should  an  electrical  component  fail,  consult  the  Factory  Service 
Center to obtain the proper replacement part. 

 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use 
a  refrigeration  technician  to  correct  the  fault.    Contact  the  Factory 
Service Center prior to initiating this action.  

 

 

 

Any  competent  refrigeration  technician  will  be  able  to  service  the 
equipment.  The following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The  machine  should  be  thoroughly  evacuated  before 

recharging. 

 

 

 

 

c.  The  unit  must  be  recharged  with  refrigerant  measured 

accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped 

and brazed charging stub attached to the side of the refrigerant 
compressor. 

 

 

 

 

The  charging  stub  should  be  crimped  and  rebrazed  after 
servicing.  

N

EVER

 

allow permanent service valves to be fitted to 

any part of the circuit.  Service valves may leak causing further 
loss of refrigerant gas. 

 

 

 

3. 

The  refrigerant  compressor  fitted  to  the  dehumidifier  is  a  durable 
unit that should give many years of service.  Compressor failure can 
result from the machine losing its refrigerant gas.  The compressor 
can be replaced by a competent refrigeration technician.   

 
 

 

Failure  of  the  compressor  can  be  confirmed  by  the  following 
procedure: 

 
 

 

a.  Establish  that  power  is  present  at  the  compressor  terminals 

using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal 

winding  by  using  meter  across  the  compressor  terminals.    An 
open circuit indicates that the compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that 

a  circuit  does  not  exist  between  the  compressor  terminals  and 
the shell of the compressor.   

Содержание CD35SP

Страница 1: ...Page 1 of 12 Drawing TPC509 Issue 1 Date 29 01 20 CD35SP INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk ...

Страница 2: ... 2 of 12 Drawing TPC509 Issue 1 Date 29 01 20 CD35SP PACKAGE CONTENTS Item Description Quantity 10186SP US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC509 Manual 1 ...

Страница 3: ...permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier ...

Страница 4: ...sed in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CD35SP HEIGHT 22 WIDTH 13 5 DEPTH 14 WEIGHT 63 lbs AIRFLOW 170 CFM POWER SUPPLY 110V 60Hz 1 ph CURRENT MAX 3 A REFRIGERANT R 134a REF CHARGE 0 19Kg CONSTRUCTION 18 AWG Epoxy Power Coated galvanized st...

Страница 5: ...ate pump This condensate pump will allow the unit to run unattended with the condensate run off to a permanent drain and can be used up to 13 feet 4 meters below the level of a permanent condensate drainage point UNPACKING INSTALLATION After removing the CD35 from its shipping container visually check for signs of damage If there is evidence of damage do not operate Call your supplier for advice D...

Страница 6: ...otor shaft and that the fan rotates freely 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the cover The evaporator coil should be evenly frost coated across its surface At temperatures above 20 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or...

Страница 7: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Страница 8: ... the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Factory Service Center 2 Contact the Factory Service Center Unit vibrates excessively 1 Loose compressor 2 Damaged fan 1 Tighten the nuts on the compressor mounts 2 Replace fan Water flooding...

Страница 9: ...014253 CAPILLIARY TUBE 3020811 BY PASS VALVE 3020937 FILTER DRYER 3033033 MICROSWITCH 3035145 HUMIDISTAT 3035346 PANEL MOUNTED TERMINAL BLOCK 3036636 RED LAMP ASSY 3040129 FAN BLADE 3050216 CASTOR 1619519 PCB 2141095 MAINS POWER CABLE 3944958 COMPRESSOR 3030421 SOLENOID COIL 3035773 MOTOR 2013837 DRAIN TRAY 3160155 CONDENSATE PUMP Spare parts available online www EIPLDIRECT com ...

Страница 10: ...Y WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARRANTY REGISTRATION To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty please complete and mail this...

Страница 11: ...yoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label Due to the high pressures within the refrigeration circuit under no circumstances must direct ...

Страница 12: ...www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Products Ltd Gartenfelder Str 29 37 Gebäude 35 D 13599 Berlin Germany Tel 49 3043 557241 Fax 49 3043 557240 www eip ltd de sales eip ltd...

Отзывы: