Refer to section 13.1 for operating characteristics in compliance with the UL 1741 SA standard.

 

 

Table 2: PCS Field Wiring Ratings – AWG / Torque

 

Field Wiring

 

Use Copper Wire Only,  90°C or higher rated 

Terminal

 

Minimum Wire Size  mm

2

 

(AWG) 

Maximum Wire Size  mm

2

 

(AWG) 

Tightening Torque, Nm (in. 

lbs) 

Ground Lug 

16 mm

2

 (6 AWG) 

16 mm

2

 (6 AWG) 

5.0 (45) 

AC Grid Terminals 

10 mm

2

 (8 AWG) 

16 mm

2

 (6 AWG) 

Push-lock spring cage 

AC Load Terminals 

10 mm

2

 (8 AWG) 

16 mm

2

 (6 AWG) 

Push-lock spring cage 

PV Feed Through 

10 mm

2

 (8 AWG) 

16 mm

2

 (6 AWG) 

Push-lock spring cage 

 

 

Table 3: Battery Cabinet Electrical / Mechanical Ratings 

Model 

Battery Cabinet 

ACB05U-LB (contained in Evolve 0013U, 0007U) 

Maximum DC Voltage (Cabinet) 

80 V DC 

Operating DC Voltage Range (Cabinet) 

0 to 80 V DC 

Operating DC Voltage Range at 100% Output Power (LG 

Chem EM048126P3S8 module) 

42 to 58.8 V DC 

DC Breaker 

Panel (if 
applicable) 

Main DC current rating 

125 A 

Max wire size of main DC 

70 mm

2 (

AWG 2/0) 

Circuit Breaker, Positive Pole 

180A or 175A, UL 489 

Max # of branch circuits 

Max wire gauge of branch circuit 

50 mm

2 (

AWG1/0) 

Grounding terminal,  
DC negative grounded 

70 mm

2 (

AWG 2/0) 

Maximum Number of Battery Modules supported 

Battery Pack capacity (EM048126P3S7) 

6.5 kWh 

Maximum Continuous Output Power (total) 

5000 W 

Normal Operation Temperature Range 

-10 to +45 °C 

Maximum Full Power Operating Ambient 

45 °C 

Storage Temperature Range (EM048126P3S7) 

-30 to +60 °C 

Enclosure Rating 

Type 3R 

Dimensions 

22.5”W x 30.8”H x 15.6”D (572 x 783 x 397 mm) 

Weight (including 2 battery modules) 

223 lbs (101 kg) 

Compliance 

Safety 

UL 9540, UL 1973 

 

Table 4: Battery Cabinet Field Wiring Ratings – AWG / Torque 

Field Wiring

 

Use Copper Wire Only,  90°C or higher rated 

Terminal

 

Minimum Wire Size  mm

2

 

(AWG) 

Maximum Wire Size  mm

2

 

(AWG) 

Tightening Torque, Nm (in- 

lbs) 

Ground Lug (field connection) 

16 mm

2

 (6 AWG) 

70 mm

2

 ( 2/0) 

5.7 (50) 

Ground Lug (internal) 

70 mm

2

 ( 2/0) included 

6.8 (60) 

PCS DC+ Lug 

70 mm

2

 ( 2/0) included 

4.0 (35) 

PCS DC-  Lug 

70 mm

2

 ( 2/0) included 

6.8 (60) 

Battery Module terminals (+/-) 

50 mm

2

 ( 1/0) included 

4.5 (40) 

Содержание ACB05U-LP

Страница 1: ...DO 58160 Rev1 Evolve ESS Installation Startup Manual For use only with battery model LG Chem EM048126P3S7...

Страница 2: ...edicated branch circuit in the main electrical panel An external disconnect switch shall be provided in the end installation by others for the AC Grid output circuit CAUTION This equipment contains hi...

Страница 3: ...DISPLAY INDICATORS 13 9 2 PCS DISPLAY PANEL INDICATOR SUMMARY 14 14 9 3 SERVICE BUTTON 14 9 4 BACKUP POWER OPERATION 14 9 4 1 Backup Power Display Modes 15 9 5 RESTARTING THE BATTERY SYSTEM AFTER LOW...

Страница 4: ...to the remote monitoring system for operating status 1 1 In case of emergency In all cases If safe to do so switch off the AC breakers external to the system Contact the fire department or other requ...

Страница 5: ...is manual and are familiar with its operation and hazards Only connect the PCS cabinet to a compatible electrical service as defined in the model specifications The PCS must be connected to a dedicate...

Страница 6: ...and start up sequence of the Eguana Evolve ESS including the PCS and master battery cabinets This product is permanently wired to the home electrical service and must be installed by a licensed electr...

Страница 7: ...bearing M8 5 16 hardware suitable for use with mounting structure Term Definition Term Definition AC Alternating Current LED Light Emitting Diode ARC Auto Recovery Circuit NC Normally Closed CPU Centr...

Страница 8: ...nufactured wall brackets CAUTION Do not install in direct sunlight Battery performance is dependent upon operating ambient temperature Radiant heat absorbed in direct sunlight will greatly reduce the...

Страница 9: ...drawing shown the last washer and wing nut are mounted from inside the cabinet 4 Mount the leveling bracket to the cabinet Each side of the cabinet must have a rubber washer in direct contact with the...

Страница 10: ...two cabinets lower front Slide the battery cabinet towards the left until mating to the gasket 14 Place the coupling plate inside the PCS cabinet and insert the four mounting bolts and washers throug...

Страница 11: ...can result in an arc fault hazard and risk of fire Damage as a result of improper termination is not covered by the manufacturer warranty 1 Remove the plastic safety barrier on the power panel assembl...

Страница 12: ...odes The installer is responsible for ensuring that over current protection is installed and sized appropriately for the AC grid and off grid output circuits in accordance with the National Electrical...

Страница 13: ...nection of the wiring panel may result in equipment damage and cause personal injury Disconnect all AC and DC Sources prior to installation CAUTION The AC grid and load ports are independent circuits...

Страница 14: ...the AC circuit only The DC source loop is internal to the battery cabinet and is rated accordingly Lightning Grounding The inverter has built in lightning protection In order for the lightning protec...

Страница 15: ...depending on the difference in battery module SOC Please refer to the PCS Service Manual for more information 1 Remove the front cover from the battery cabinet adjacent to the PCS cabinet 2 Press the...

Страница 16: ...sconnect switch inside the battery cabinet 5 The PCS module will initialize indicated by a brief flash of all LEDs on the display panel followed by a status of the battery and PCS Refer to section 9 2...

Страница 17: ...frigerator home lighting home electronics and small appliances NOTE This product is not an uninterrupted power source UPS Following a utility outage a four second power interruption will occur before...

Страница 18: ...kup operation To restart the system IMPORTANT Ensure there is adequate sunlight for the solar PV system to charge the battery before restarting the system If the battery system is installed without a...

Страница 19: ...resume backup operation until adequate sunlight is present to provide a solar charge of the battery All panel lights flashing System is attempting to communicate with the battery modules Notify servi...

Страница 20: ...ry OVC I II III or IV OVC III Pollution Degree 3 Lightning protection IEEE 62 41 2 location category B low exposure Normal Operation Temperature Range Humidity 40 to 50 C limited by battery see below...

Страница 21: ...wire size of main DC 70 mm2 AWG 2 0 Circuit Breaker Positive Pole 180A or 175A UL 489 Max of branch circuits 6 Max wire gauge of branch circuit 50 mm2 AWG1 0 Grounding terminal DC negative grounded 70...

Страница 22: ...uration s Maximum Trip Time s Operating Mode During Ride Through High Voltage 2 HV2 V 120 N A 0 16 N A High Voltage 1 HV1 110 V 120 12 13 Momentary Cessation zero power Near Nominal NN 88 V 110 Indefi...

Страница 23: ...Mandatory Operation FW Continuous Operation CO 57 0 f 63 0 Indefinite Indefinite Continuous Operation FW Under Frequency 1 UF1 56 0 f 57 0 20 21 Mandatory Operation Under Frequency 2 UF2 f 56 0 N A 0...

Страница 24: ...0 33 Table 10 SA12 specified power factor settings SA12 Specified Power Factor Parameter Value for Rule 21 Value for Rule 14H Apparent power rating for function VA 5000 Output power rating for functio...

Страница 25: ...Default function status Enabled Enabled Default response time ramp to Qmax ind s 10 10 Default power prioritization Q Q Default Voltage at Q1 V 110 4 112 8 Default max reactive power production setti...

Страница 26: ...oltage Watt Parameter Value for Rule 21 Value for Rule 14H Output power rating for function W 5000 AC voltage range with function enabled V 120 0 132 0 Nominal AC voltage V 120 AC voltage accuracy Vno...

Страница 27: ...e 13 kWh battery cabinet 0 1000 2000 3000 4000 5000 6000 0 20 40 60 80 100 AC POWER VA SOC Evolve 0513U Charging AC Power Derating Full Range Derated 15 to 45 C 10 C 10 C 50 C 0 1000 2000 3000 4000 50...

Страница 28: ...CAN port A2 801003533 BMS cable short Interconnects modules within same cabinet A3 801003247 BMS cable long Interconnects modules between cabinets A4 Battery power cables Positive negative pair PCS 18...

Страница 29: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Отзывы: