UPS: MKD 700
– 3000 VA RT (XL)
Installation and Connection
5.
Installation and connection of the UPS
All limit values listed in the technical data regarding the ambient and operation
conditions are to be maintained in order to ensure the proper functioning of
UPS.
The system must only be installed and switched on by trained electricians in
compliance with the corresponding safety regulations, standards and within the
national guidelines! This also includes the safety regulations for handling
accumulators.
The UPS must be installed in a well-ventilated environment, far from liquids,
inflammable gases and corrosive agents.
5.1
Installation in 19“ cabinet (RACK)
In general, the following rules apply for installing the UPS in a switch cabinet:
–
Always mind that there is sufficient space behind the UPS in order to
be able to perform the necessary connection work and use
appropriate guide rails based on the weight of the UPS. The carrying
capacity of the guide rails / base must on all accounts be
guaranteed;
–
Observe the prescribed mounting position and fasten the device only
on the established screw points (
Fehler! Verweisquelle konnte
nicht gefunden werden.
);
–
Make sure that the ventilation of the device is safeguarded. Because
this UPS will be aired lengthwise, a minimum distance of 50 mm in
front of and behind the UPS from the fitted cabinet. Pay attention to
the corresponding current channel;
–
Mind the set-up of the device. Due to the heat build-up in the device,
the battery bank should always be installed under the UPS. When
installing the UPS in superior systems (e.g. machines, systems), be
noted that the UPS is operated in the specified temperature range. In
the event of heat accumulation in the installation room, this must be
resolved with sufficient external ventilation;
–
The UPS must only be installed in a clean, dust-free and dry area;