background image

39

5

823

1

10a 

12

Freestanding Installations 
 

If the chimney connector must pass through a combustible wall to reach 
the chimney, follow the recommendations in the Wall Pass-Through 
section that follows. 
The opening through the chimney wall to the flue (the “breach”) must be 
lined with either a ceramic or metal cylinder, called a “thimble”, which is 
securely cemented in place.  Most chimney breeches incorporate 
thimbles, but the fit must be snug and the joint between the thimble and 
the wall must be cemented firmly (Fig. A) 
A special piece called the “thimble sleeve”, slightly smaller in diameter 
than standard connectors and most thimbles, will facilitate the removal of 
the chimney connector system for inspection and cleaning.  Thimble 
sleeves are available from your local dealer. 
To install a thimble sleeve, slide it into the breech until it is flush with the 
inner flue wall.  Do not extend it into the actual flue passage, as it could 
interfere with the draft. 
The thimble sleeve should protrude 1-2” (25-50 mm) into the room.  Use 
fire cement and thin gasketing to seal the sleeve in place in the thimble.   
Secure the chimney connector to the outer end of the sleeve with sheet 
metal screws. 

 

Above a Fireplace   
 

In this installation, the chimney connector rises from the stove, turns 90°, 
and then goes into the fireplace chimney (Fig. B) The liner of the fireplace 
chimney should extend at least to the point at which the chimney 
connector enters the chimney.  Follow all the guidelines for installing a 
chimney connector into a freestanding masonry chimney, and pay special 
attention to these additional points: 

  Double check the connector clearance from the ceiling: 18” minimum. 

  The fireplace damper must be closed and sealed to prevent room air 

from being drawn up the flue, thereby reducing the draft.  However, it 
must be possible to re-open the damper to inspect the chimney. 

 
Wall Pass-Throughs

   

 

Whenever possible, design your installation so that the wall connector 
does not pass through a combustible wall.  If you are considering a wall 
pass-through in your installation, check with your building inspector before 
you begin.  Also check with the chimney connector manufacturer for any 
specific requirements. 
 
Accessories are available for use as wall pass-throughs.  If using one of 
these, make sure it has been tested and listed for use as a wall pass-
through. 
 
The National Fire Protection Association (NFPA) has established 
guidelines for passing chimney connectors through combustible walls.  

Содержание HARMONY I

Страница 1: ...CE INSTRUCTIONS Manufactured by Thermic Distribution Europe SA 5 Rue du Lion B 5660 Couvin Belgium SAVE THESE INSTRUCTIONS FOR FUTURE USE AND REFERENCE Please read this entire manual before you instal...

Страница 2: ...ce when enamel is exposed to high temperatures Your enamel finish will not be harmed nor will the function of the stove be impaired SPECIAL NOTE A barometric damper is recommended for installations of...

Страница 3: ...lbs Testing Listing Your Efel wood stove has been tested to UL Standard 1482 by OMNI Test Laboratories Inc Beaverton Oregon EPA Certification The Efel wood stoves have been tested to rigorous emissio...

Страница 4: ...A B D C Model A B C D Stanford 80 24 28 16 6 Stanford 140 29 31 20 7 Harmony I 23 26 15 6 Harmony III 29 29 18 7 Dimensions...

Страница 5: ...395823110a 5 Combustion System Stanford 80 and Harmony I...

Страница 6: ...395823110a 6 Combustion System Stanford 140 and Harmony III...

Страница 7: ...by means approved by the regulatory authority Refer to chart for single or double wall pipe Back and Side Wall Clearances Connector pipe A B C D Single wall 27 5 24 27 18 Double wall 21 5 18 27 18 Min...

Страница 8: ...eans approved by the regulatory authority Refer to chart for single or double wall pipe Back and Side Wall Clearances Connector pipe A B C D Single wall 18 13 32 20 Double wall 14 5 10 28 5 17 Minimum...

Страница 9: ...has a k value of 5 0 The following would determine the thickness necessary 5 0 x 1 2 inch 3 0 inches of common brick 0 84 3 Mark the position of the required floor protector on the floor Remove the u...

Страница 10: ...y complying with the requirements for Type HT chimneys in the standard UL 103 Minimum Chimney Height American National Standards Institute ANSI NFPA 211 92 draft 1 7 states that a chimney or vent shal...

Страница 11: ...395823110a 11...

Страница 12: ...ter end of the sleeve with sheet metal screws Above a Fireplace In this installation the chimney connector rises from the stove turns 90 and then goes into the fireplace chimney Fig B The liner of the...

Страница 13: ...ibles Placing a chimney connector pipe inside a ventilated thimble this is then separated from combustibles by 6 150 mm of fiberglass insulating material Placing a chimney connector pipe inside a sect...

Страница 14: ...as a radiant room heater and should be used for no other purpose Be sure to provide combustion air into the dwelling when using the appliance A partially open window or outside air register in the vi...

Страница 15: ...ture to the air whenever a structure is being heated for extended periods What is the best wood for the fire Some types of wood are easier to light than others The best fire wood is always the driest...

Страница 16: ...supplied in ready cut lengths stored immediately under a ventilated shelter dries quicker than wood stocked in high piles Quarters split wood dry quicker than round logs Wood which is too small to spl...

Страница 17: ...ls Start up Air Control Additional air for start up can be supplied from the ignition booster air control located on the back right corner of the Stanford 140 and Harmony III models This can be especi...

Страница 18: ...se recommendations 1 Open the primary air control to allow fire to recover for a few minutes 2 Close the primary air control and open the loading door 3 Rake the embers towards the front of the stove...

Страница 19: ...pty the ash pan regularly to prevent the ash from spilling over Do not allow ash to build up and touch the under side of the grate A layer of ash left over the grate when burning wood will protect the...

Страница 20: ...broken or loose parts or other problems are noted contact your dealer or qualified serviceman to inspect and repair the unit DO NOT OPERATE THE UNIT IF INSTALLED OR FUNCTIONING IMPROPERLY 4 Check the...

Страница 21: ...ey fire It is extremely important to have a clear plan on how to handle a chimney fire Procedure to follow in case of a chimney fire A Prepare to evacuate to ensure everyone s safety Have a well under...

Страница 22: ...l the 4 screws Do not over tighten the screws When replacing glass always replace glass seals Other maintenance Clean the unit the flue outlet and the chimney at the end of each heating season or more...

Страница 23: ...ft Lower Firebrick Stanford 140 Harmony III order code 41201 Upper Left Firebrick Stanford 140 Harmony III order code 41202 Lower Rear Firebrick Stanford 140 Harmony III order code 41204 4 6 117mm 7 8...

Страница 24: ...rebrick above tubes on ceiling Stanford 80 Harmony I order code 38745 Upper Rear Firebrick Stanford 80 Harmony I Fuel Grate Frame Stanford 80 Harmony I Fuel Grate Frame Stanford 140 Harmony III order...

Страница 25: ...er code 19777 22 Fuel Grate Stanford 80 Harmony I order code 39449 23 Fuel Grate Stanford 140 Harmony III order code 38262 29 Log Guard 30 Log Guard Stanford 140 Harmony III order code 41546 31 Left A...

Страница 26: ...code 41526 Baffle Assembly Ceramic Fiber Brick above secondaryair tubes Stanford 140 Harmony III order code 41540 Start up Air Channel Assembly Stanford 140 Harmony III Flue Outlet Collar Stanford 80...

Страница 27: ...rebrick 38744 LowerRearFirebrick 38743 LeftSide Firebrick 38742 RightSide Firebrick 38741 Note St 80 HarmIdo nothavefire brickonfire boxfloor fuel grate frame onflooronly Stanford 140 Harmony III Fire...

Отзывы: