Parameterisation
MSM-USM2G-BA-UK-001
Page 35 of 46
5.2.4.2 Submenu reporting sequence
Fig. 5.15: Page reporting sequence
In this sub-menu the reporting sequence and the horn triggering can be parameterised. To ensure a
flexible adaption of the sequence to the requirements, the reporting sequence is composed from
different components, which are explained in the following.
Reporting sequence
Title
Options
Note
Signalling
1-Frequency
1-frequency flashing
2-Frequency
2-frequency flashing
Status indication
Self-acknowledging alarm: alarm is displayed as
acknowledged alarm and recedes, when the
corresponding input drops.
Reporting
sequence
New value
New value reporting (no-first-up)
First up
First-up reporting
Steady-steady-light
Can only be chosen for 2-frequency flashing
Collective report
Input parallel static
The collective report is set with the first incoming
alarm and resets with the last receding alarm.
Input parallel static-dynamic
The collective report is set with the first incoming
alarm. For each subsequent alarm, the collective
report is reset for approx. 0.8 s and then set again.
Once all alarms have receded the collective report
is reset permanently.
Output parallel static
The collective report is set with the first incoming
alarm. Once all alarms have receded and been
acknowledged the collective report is reset.
For device and channel design
ation, all characters from A…Z and 0…9 are allowed.
The special characters „ { } | $ & # ; “ are not allowed.
For channel designations, „
\
“
(backslash) is used as separation mark to start a new line.