III. ELECTRICAL HOOK-UP
WARNING
BEFORE DOING ANY WORK ON THE UNIT BE SURE BOTH
BREAKERS ARE
“OFF”
TO AVOID ANY DANGER OF SHOCK.
“Eemax Home Advantage” heaters are manufactured to the following specifications:
The L1, L2, or N should be connected to the slots in the contactor marked L1 and L2.
(Fig. 2b). The ground lead must be connected to the stud marked GND.
GROUND MUST BE BROUGHT TO THE “GROUND” AT THE CIRCUIT BREAKER PANEL.
Use dedicated independent circuits and appropriate wiring and circuit breaker configurations
M O DE L TY P E
V oltage
k W output
A M P E RA G E
PA 014240
1φ 240
V
15.0
63 (2 x 31.5)
PA 016277
1φ 277
V
16.0
58 (2 x 29)
PA 019240
1φ 240
V
19.0
80 ( 2 x 40)
PA 020277
1φ 277
V
20.0
72 (2 x 36)
PA 023240
1φ 240
V
23.0
96 (2 x 48)
Table 1
Use dedicated independent circuits and appropriate wiring and circuit breaker configurations
dictated by the power requirements of the unit. (Table 1 and Fig. 3)
DANGER
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY.
7
Figure 3
Dedicated
Single Pole (277 Volts)
or
Double Pole (240 Volts)
Circuit
O
N
O
F
F
or
Circuit Breaker Panel
O
N
O
N
O
F
F
O
F
F
Содержание PA014240
Страница 4: ...Mounting Layout for Series 2 Systems 4 Figure 1 ...
Страница 10: ...EX1049 1 TRIAC EX1050 1 EX278C ECO ...